Installation / Operation Instruction Manual

18
Venting continued-
CAUTION
Check to make sure flue gases DO NOT recirculate into the air intake terminal when using direct venting. If the water
heater is having service issues, flue recirculation may be a contributing factor. Even when the minimum vent terminal
separation distances are followed, recirculation may still occur depending upon the location outside the building, the
distance from other buildings, proximity to corners, weather conditions, wind patterns, and snow depth. Periodically
check to make sure that flue recirculation is not occurring. Signs of flue gas recirculation include frosted or frozen
intake terminals, condensate in the intake terminal and venting system, oxidation or white chalk material on the flame
sensor or igniter shield. Correction to flue recirculation may involve angling the intake away from the exhaust terminal,
increasing the distance between them, relocating the air intake to another side of the building, or using inside air for
combustion. Check to be sure the intake and exhaust terminals are not obstructed, especially during periods of below
freezing weather.
NOTICE
For installations in Canada, field supplied vent piping must comply with CAN/CGA B149.1 (latest edition) and be
certified to the Standard For Type BH, Class II, 65°C, Gas Venting Systems, ULC S636. Components of this listed
system shall not be interchanged with other vent systems or unlisted pipe/fittings. All components and specified primers
and cements of the certified vent system must be from a single system manufacturer and not intermixed with other
system manufacturer’s vent system parts. The supplied vent connector and vent termination are certified under ULC
S636 and are also certified as part of the water heater. Refer to the following tables for approved venting materials,
primers, and cements. All approved primers and cements are to be used within their marked time limitations.
Approved Venting Materials
For installations in the US only
PVC DWV (ASTM D-2665)
PVC Sch. 40 (ASTM-D1785)
CPVC Sch. 40 (ASTM-F441, ASTM-D2846)
PVC and CPVC (UL 1738, ULC S636)
ABS Sch. 40 DWV (ASTM-D2661)
Polypropylene (UL 1738, ULC S636)
Stainless Steel (UL 1738, ULC S636)
For installations in CANADA
ULC S636 approved PVC for flue gas
venting rated Class II, 65°C
ULC S636 approved CPVC for flue gas
venting rated Class II, 65°C
ULC S636 approved Polypropylene for flue
gas venting rated Class II, 65°C
Stainless Steel (ULC S636)
Approved Primers and Cements
For installations in the US only
PVC and CPVC Primer (ASTM-F656)
PVC Cement (ASTM D-2564)
CPVC Cement (ASTM F493)
ABS Primer and Cement (ASTM D-2235)
For installations in CANADA
ULC S636 approved Primer and Cement for
flue gas venting rated Class II, 65°C
NOTICE
Use of cellular core PVC (ASTM F891), cellular core CPVC, or Radel
®
(polyphenosulfone) in non-metallic venting systems is prohibited and covering non-
metallic venting with thermal insulation is prohibited.
NOTICE
Before beginning installation of any vent pipe, read the vent pipe manufacturer’s installation instructions.
DO NOT install the water heater in any location where the ambient temperature may fall below freezing. Water heater
must be protected from freezing downdrafts during shutdown periods.
Provide protection of the building materials from degradation by flue gases from the exhaust vent terminal.