Locating The Storage Unit continued-
This storage unit must be located in an area where leakage of the tank or
water line connections and the combination temperature and pressure relief
valve will not result in damage to the area adjacent to the storage unit or to
lower floors of the structure. When such locations cannot be avoided, a
suitable drain pan must be installed under the storage unit. The drain pan
must have a minimum length and width of at least 4 in. (10.2 cm) greater
than the diameter of the water heater. The drain pan, as described above,
can be purchased from your plumbing professional. The drain pan must be
piped to an adequate drain. The piping must be at least 3/4 in (1.9 cm) in
diameter and pitched for proper drainage.
This storage unit MUST be installed indoors out of the wind and
weather.
To comply with NSF requirements this water heater is to be:
a) Sealed to the floor with sealant, in a smooth and easily cleanable
way, or
b) Installed with an optional leg kit that includes legs and/or extensions
that provide a minimum clearance of 6” beneath the water heater.
Note: For California installation this storage unit must be braced,
anchored, or strapped to avoid falling or moving during an earthquake.
See instructions for correct installation procedures. Instructions may
be obtained from the DSA Headquarters Office, 1102 Q Street, Suite
5100, Sacramento, CA 95811.