Submittal

Specications
Voltage Input Multi-mode power adapter: 9-30VDC or 12 - 24VAC
Power Consumption @ 12V RER = 150mA
LER = 279mA
Operating Temperature -40°F to 167°F (-40°C to 75 °C)
Operating Humidity 5-90% RH, non-condensing
Connections RS-485 Port for BACnet MP/TS or Metasys N2
Ethernet Port for BACnet IP
LonWorks Port
Weight 0.4 lbs (0.2 kg)
Dimensions 4.5 L x 3.2 W x 1.6 H inches (11.5 x 8.2 x 4.0 cm)
Surge Suppression EN61000-4-2 ESD EN61000-4-3 EMC EN61000-4-4 EFT
Approvals BACnet Testing Labs (BTL) B-ASC - RER Series
LonMark 3.4 Certied - LER Series
CE (EN55022;EN55024; EN60950)
TUV approved to UL 916 standard and CSA C22-2
FCC Class A Part 15
CSA 205 Approved
RoHS Compliant
DNP3 Conformance Tested
OPC Self Certied to Compliance
BACnet Support BTL Listed
BACnet COV’s
Support up to 2,000 Host & Field points
DIP switches are for setting MAC Address, Node-ID,
Baud Rate on the RS-485 Field protocol
LonMark Certication SPID: 80:00:95:46:00:84:04:07
Proles: 0000 - Node object (1), 0001
0001 - Open Loop Sensor Object (5)
0003 - Open Loop Actuator Object (5)
Warranty Two years from date of purchase, return to factory
Bradford White Corporation reserves the right to change specications, components, features, or to discontinue products without notice.
Litho in U.S.A. © Bradford White 1404 Document 4237A-BW
BACnet® is a registered trademark of ASHRAE. LonWorks® is a registered trademark of Echelon Corp. Metasys® is a registered trademark of Johnson Controls, Inc.
www.BradfordWhite.com