Installation / Operation Instruction Manual
Table Of Contents
- Table of contents
- 1 Key to symbols and safety instructions
- 1.1 Key to symbols
- 1.2 Safety instructions
- 2 FCC rules
- 3 Appliance details
- 4 Installation instructions
- 4.1 Specialized tools
- 4.2 Introduction
- 4.3 Venting
- 4.3.1 Vent options
- 4.3.2 Vent specifications
- Venting specifications
- Condensate drain requirements
- Minimum combustion air and exhaust pipe length
- Maximum combustion air and exhaust pipe length
- Use of elbows
- Calculation example for 3" PVC, CPVC, or ABS venting:
- Calculation example for 4" PP, PVC, CPVC, or ABS venting:
- Calculation example for 2" PVC venting:
- Required direct vent terminal clearances (twin pipe / concentric penetration) for PVC, CPVC, ABS, and PP.
- Required other than direct vent terminal clearances (single pipe penetration) for PVC, CPVC and ABS systems.
- 4.3.3 Vent configuration examples for PP, PVC, CPVC, or ABS systems
- 4.3.4 Vent connections for PP, PVC, CPVC, and ABS systems
- 4.3.5 Connecting the condensate water drain
- 4.3.6 Freeze prevention for PVC, CPVC, and ABS systems
- 4.3.7 Common venting of 2 to 4 units
- 4.3.8 Fan speed adjustment
- 4.4 Combustion air requirements
- 4.5 Proper location for installing your heater
- 4.6 Heater placement and clearances
- 4.7 Hanging appliance on the wall
- 4.8 Mounting installation
- 4.9 Gas piping & connections
- 4.10 Water connections
- 4.11 Water quality
- 4.12 Filling the condensate trap
- 4.13 Domestic hot water recirculation
- 4.14 Space heating applications
- 4.15 Measuring gas pressure
- 5 Electrical connections
- 6 Operation instructions
- 7 Maintenance and service
- 8 Troubleshooting
- 9 Problem solving
- 10 Electrical diagram
- 11 Sensor resistance charts
- 12 Functional scheme
- 13 Interior components diagram
- 14 Protecting the environment
- 15 LIMITED TANKLESS HEATER WARRANTY
- 16 Installer Checklist to be completed by installer upon installation
Installation instructions
RTG 199 HE – 6 720 811 617 (2016/01)
21
4.3.8 Fan speed adjustment
Installation adjustment:
After installing the tankless water heater, the fan speed values for
minimum power (P2) and maximum power (P1) may need adjustment
due to variations in altitude and vent pipe length. Failure to make
necessary adjustments to fan speed values may result in improper
operation of the appliance.
First calculate the total equivalent vent length. This is the straight pipe
length of both exhaust and combustion air plus the number of elbows
used. To determine the length equivalency of each elbow refer to tables
8 and 9.
Use the equivalent vent length value to determine the appropriate fan
speed values found in table 28 and 29. Refer to page 22 on how to adjust
the fan speeds if an adjustment is necessary. After changing fan speed
values, proceed to chapter 7.5 to confirm CO
2
values are within
specified ranges.
NOTICE: IMPORTANT INFORMATION!
▶ Natural gas heaters with installation altitudes below
2,000 ft above sea level disregard this section.
Natural Gas
Liquid
propane
Natural Gas
Liquid
propane
Altitude (above sea
level)
Vent
terminal
Total equivalent vent
length
1)
1) Full equivalent length (inlet + outlet piping + fittings)
Minimum
power fan
speed (P2)
Minimum
power fan
speed (P2)
Maximum
power fan
speed (P1)
Maximum
power fan
speed (P1)
0 - 2000 ft
(0 - 610 m)
Twin
system
3.5 - 11 ft 12
3)
17
3)
52
3)
52
3)
12 - 19 ft 12
3)
17
3)
52
3)
52
3)
2000 - 4500 ft
2)
(610 - 1372 m)
2) When installing in altitude, the unit may not reach the rated Input
Twin
system
3.5 - 11 ft 13
3)
17
3)
52
3)
52
3)
12 - 19 ft 13
3)
3) When adjusting the unit, CO2 levels must be checked with a combustion gas analyzer, see chapter 7.5 for instructions.
17
3)
52
3)
52
3)
Table 27 Fan speed adjustment for 2" piping
Natural Gas
Liquid
propane
Natural Gas
Liquid
propane
Altitude (above sea
level)
Vent
terminal
Total equivalent vent
length
1)
Minimum
power fan
speed (P2)
Minimum
power fan
speed (P2)
Maximum
power fan
speed (P1)
Maximum
power fan
speed (P1)
0 - 2000 ft
(0 - 610 m)
Concentric 6 - 25 ft No
modification
required
No
modification
required
No
modification
required
No
modification
required
For operation at
elevations above
2,000 ft (610 m)
the equipment
ratings shall be
reduced at the rate
of 4% for each
1,000 ft (305 m)
above sea level
26 - 46 ft
Twin
system
6 - 37 ft
38 - 62 ft
2000 - 4500 ft
(610 - 1372 m)
Concentric 6 - 25 ft 11* 14* 52* 52*
26 - 46 ft 11* 14* 53* 53*
Twin
system
6 - 37 ft 10* 13* 52* 52*
38 - 62 ft 11* 14* 53* 53*
4500 - 8000 ft
(1372 - 2439 m)
Concentric 6 - 25 ft 11* 14* 53* 53*
26 - 46 ft 13* 16* 53* 53*
Twin
system
6 - 37 ft 11* 14* 53* 53*
38 - 62 ft 12* 15* 53* 53*
* Above 2000 ft, CO2 levels must be checked with a combustion gas analyzer, see chapter 7.5 for instructions.
Table 28 Fan speed adjustment for 3" piping
1) Full equivalent length (inlet + outlet piping + fittings)