Installation / Operation Instruction Manual

43
Error
Code
Definition of Code Cause of Problem and Actions Taken to Correct
105
Flame detected out of
sequence
Check to see if flame is present inside the combustion chamber before or after the
ignition cycle.
If so, check to make sure the gas valve is wired correctly.
Check for voltage at the gas valve connection.
Replace the gas valve if defective.
If no flame is visible outside of the ignition sequence/run cycle, then make sure the
flame sensor is wired to the correct terminal.
Make sure the ignition cable is not crossing the flame sensor wire or ignition ground
wires.
If problem persists and all other checks have been verified, replace the control
module.
109,
110
Ignition Failure
Occurred.
Burner failed to light or stay lit after 4 retries.
Hold condition – will reattempt ignition after 15 minute waiting period. A log will be
stored in service history.
Check gas valve wiring and gas valve operation during the ignition cycle.
If burner lights but quickly goes out, check the flame sensor wire or the flame
sensor.
If the flame sensor rod is badly corroded with deposits, clean with sandpaper or
replace.
Check the inlet gas supply to make sure the pressure is sufficient and does not
drop after the gas valve opens.
Make sure the combustion blower is operating during the ignition and run cycle.
Check the venting system to make sure the inlet and exhaust terminals and venting
system is not blocked.
122,123
Light-off Rate Proving
Failed
If blower speed is not verified from the PWM (Pulse Width Modulation) signal within
5 minutes, the previously described error code “62” changes from a hold condition
to this lockout code condition
Check the harness and pin terminals for a good connection to the control module.
Replac
e the blo
w
er
or control module if the wi
re harness is good.
172
Water temperature
sensor resistance
invalid
Hold 93 will be displayed if this value remains out of range
Measure the resistance of the water temperature sensor and compare it with the
tank temperature using the chart below.
NOTE
If there is do display, check primary/secondary voltage
Before troubleshooting always verify the following
o Gas inlet pressure
o Static to dynamic gas pressure drop
o No vent and intake restrictions
o All wire connections are tight
o No grounded wires or missing grounds
o
No water leaks