Aerada 900 Series Faucet Installation
2/6/2018 Bradley • 215-1680 Rev. E; ECN 17-02-005
Before attempting to troubleshoot the valve or disassemble the components, check for the following conditions:
If stop valves are used, make sure that they are fully open.
Make sure that the hot and cold inlet pipes are connected properly, and that there are no cross-
connections or leaking stop valves.
Check the hot water heater output to make sure that it is at least 10° F above the set temperature.
Troubleshooting – Thermostatic Mixing Valve
Close the appropriate shut-off valves prior to disassembly and reopen valves after inspection and
repair is complete.
Problem Cause Solution
External leaks. Damaged cartridge or
O-rings.
Replace cartridge with part number 269-1927
Improper water temperature or
temperature fluctuation.
Hot water supply is not 10°
above desired set point.
Increase hot water supply temperature
Valve temperature is not
properly set.
Adjust the temperature as shown on page 4 step 3.
Limited water flow. Dirt and debris have built
up in the valve or strainer.
1. Check to make sure both hot and cold supplies are connected to the
Navigator mixing valve and that they have water flow.
2. Remove cover and U-clip. Remove the cartridge and clean the
strainer. It is not required to grease cartridge, however if desired, use
silicone grease only.
Do not use grease on check valves.
Ref. Part No. Description
1 160-463 Cap Screw
2 107-582 Cover
3 269-1927 Thermostatic Cartridge
4 198-014 Check Valve*
5 132-051 Retaining Ring*
6 146-079 U-Clip
7 118-319 Valve Body
* Included with Prepack S65-326
1
3
2
7
4
5
6
Strainer
173-028
Tempered Line Adapter Option:
Part no. S39-804
Parts List for S01-526
S01-526