Specifications

Detailed
Installer Guide
Non-Programmable Thermostats
1
Specifications
2
Installation and Wiring
3
Quick Reference
4
Installer Settings
5
System Testing
• Possible electric shock or damage to equipment can occur.
• Disconnect power before beginning installation.
Caution
This thermostat requires 24 Volt AC Power or 2 properly installed “AAAlkaline
batteries for
proper operation. When connecting 24 Volt AC Power the batteries may
be installed as a backup.
For use only as described in this manual. Any other use will void warranty.
3020
Single Stage Heat / Cool Conventional
or Heat Pump
3220
Up to 3 Heat / 2 Cool Heat Pump
Up to 2 Heat / 2 Cool Conventional
Warning
For installation by experienced service technicians only.
®
This thermostat is compatible with:
• Singlestageheat/coolconventionalandheatpumpsystems
• Conventionalsystemsupto2stagesofheatingand2stagesofcooling(3220only)
• Heatpumpsystemsupto3stagesofheatingand2stagesofcooling(3220only)
• 250–750millivoltheatingonlysystems
• 2or3wirehydroniczonesystems
Electrical and control specifications:
• ElectricalRating:24VoltAC
• 1ampmaximumloadperterminal
• ACPower:18–30VoltsAC
• DCPower:3.0VoltDC(2“AAAlkalineBatteriesIncluded)
• ControlRange:45°–90°F(7°–32°C)
• TemperatureAccuracy:+/-1°F(+/-.5°C)
• OutdoorTemperatureDisplayRange:-40°-120°F(-40°-49°C)
Terminations
• 3020:G,Rc,Rh,W1,O/B/V3,Y1,C,S1,S2
• 3220:G,Rc,Rh,W1/E/W3,W2,O/B/V3,Y1,Y2,C,L,S1,S2
1
Specifications
3020W-100-02
Model number is located on back of thermostat.