Datasheet
Connect, Congure, Control
ED-516 ETHERNET TO Digital IO 16 Inputs
Ethernet to Digital In
ED-516
• 16 Digital Inputs
• 0 to 30 Volt inputs ideal for dry/Volt free
contacts or wet contacts
• Ideal for inductive, capacitive & resistive loads
• Gateway Port for NuDAM/ADAM modules
• -30
o
C to +80
o
C Temperature range
• +5V to +30V DC Input Power
ED-516
Digital Channels
Inputs Input Channels 16 non-isolated input channels
NPN/PNP One jumper configures all inputs as either pull up for NPN, active low,
type sensors or pull down for PNP, active high, type sensors
Logic Level 0: 0V to +1V maximum
Logic Level 1: +3.5V to +30V maximum
Latched Inputs: Triggered by user programmable positive or negative edges, stays
true until acknowledged
Counter Inputs: User programmable- counts positive or negative transitions 0-65335
Dry/Volt free Contact Example