Datasheet
Connect, Congure, Control
ED-527 ETHERNET TO Digital IO 16 Outputs
Ethernet to Digital Out
ED-527
• 16 Digital Outputs
• Drives high current and high voltage loads
• Ideal for inductive, capacitive & resistive loads
• Gateway Port for NuDAM/ADAM modules
• -30
o
C to +80
o
C Temperature range
• +5V to +30V DC Input Power
ED-527
Digital Channels
Outputs Output Channels 16 non-isolated output channels
Maximum output current
Sinks up to 1 Amp per pin, 40V max load
Max combined load 4.0 Amps per ED device
Characteristic: Open drain output, protected MosFET with intelligent short circuit
protection up to 36V
Over temperature shutdown:175
0
C typical 150
0
C min
Maximum output load Voltage
40V
ESD Protection
16kV
1 2 3 4 5 6
A
B
C
D
D
C
B
A
654321
Date: Sheet of
Drawn By: Checked By:
Number Revision
Title
D OUT1 (Pin 3)
GND (Pin 1)
D OUT0 (Pin 2)
D OUT3 (Pin 5)
D OUT2 (Pin 4)
D OUT1 (Pin 3)
GND (Pin 1)
D OUT0 (Pin 2)
D OUT3 (Pin 5)
D OUT2 (Pin 4)
1
2
2
1
EXTERNAL GROUND
ALWAYS CONNECT
External CircuitExternal Circuit
1
Bit=1
0
Bit=0
UN_OUT02
SWITCH
UN_OUT02
1K1K
24VOLTS 24VOLTS
10-7-2013_16:19
?EAMONN
56
2
90ED073R2
ETHERNET TO DIO 7 DI 3DO 2 PORT SWITCH
ED-588ED-588
Resistor current= 0
OUTPUT PIN=24V
ALWAYS CONNECT
EXTERNAL GROUND
OUTPUT PIN=~0V
Resistor current= 24mA
LAMP= ONLAMP= OFF
Driving an Andon Light