Datasheet
+44(0) 151 220 2500 sales@brainboxes.com www.brainboxes.com
ED-527 Ethernet 16 DO
Browser Interface
Webserver Interface Congure IP address, monitor state of i/o lines, set the Watchdog Timers Output Reset Value, Set Power on digital output
value
Programming Interface No device driver needed, just open a TCP connection and send simple ASCII commands.
Software drivers give local COM Port interface for conguration
Utility Programs Find device, congure IP address
102 mm
128 mm
22.6 mm
Type of Port
Terminal
Block
Pin 1 Pin 2 Pin 3 Pin 4 Pin 5
Digital Out Yellow GND DOut 0 DOut 1 DOut 2 DOut 3
Digital Out Orange GND DOut 4 DOut 5 DOut 6 DOut 7
Gateway Grey GND RS-485 D- RS-485 D+ RS-485 D+ RS-485 D-
Digital Out Green GND DOut 8 DOut 9 DOut 10 DOut 11
Digital Out Blue GND DOut 12 DOut 13 DOut 14 DOut 15
Power Black Power GND +Vin A +Vin B Power GND Func GND
Link LED
Status LED
Activity LED
Gateway LED
Reset Hole
Ethernet Port
Housing
IP-20 rated non-conducting polyamide case with integrated DIN rail mount
Watchdog
Power up On power up all outputs go to user programmable power on known good state
Watchdog coms link On loss of communications link all outputs go to a user programmable watchdog comms known good state.
Watchdog hardware timer If the rmware does not refresh the watchdog timer within a predetermined interval then all outputs go to a user
programmable watchdog hardware good state
Ethernet
Ethernet Port 1 x RJ45 jack, 10/100Mhz autosensing, crossover auto sensing (Auto MDIX)
Protection 1,500Volts magnetic isolation between I/O ports and network
Network Protocols ICMP, IP, TCP, DHCP, Telnet, HTTP
Connection to Network Ethernet 10BaseT / 100BaseTX