Table 7: Common faults and their remedial actions
Sr.
No.
Faults Remedial Actions
Possible Issues in MANUAL Mode
1
The controller does not power ON.
Check the battery voltage.
Check the fuse on the battery supply.
Check continuity between battery positive and controller
terminal # 2.
Check continuity between battery negative and controller
terminal # 1.
2 The controller fails to crank-start
the engine.
Check the battery voltage.
Enter “Configuration Mode” in controller and verify the
configuration for the “START” output. Also, check that
“START” output is working correctly by measuring its
output voltage.
Enter “Configuration Mode” in controller and verify the
configuration of “CRANK DISCONNECT” method.
3 The “Emergency Stop” alarm
comes up even when the
“Emergency Stop” is not pressed.
Check if the “Emergency Stop” switch is working OK.
Check its wiring also.
Enter “Configuration Mode” in controller and verify the
configuration of “EMERGENCY STOP” polarity.
4 The controller generates
unnecessary “Shutdown Alarms” or
“Warning Alarms”
Check the respective switch/sensor and wiring.
Enter “Configuration Mode” in the controller and verify the
respective threshold configuration.
5 The engine runs, but the controller
shows genset to be “OFF”.
Check if the MPU signal (if used), and main alternator
voltage signal (R/L1 phase) are received by the controller
terminals.
Check if the LOP and LLOP are working OK. Also check
their wiring to the controller.
6 The controller displays incorrect PF
value or kW or load current.
Check wiring of the respective alternator phase voltage
and the CT to the controller.
Check the CT ratio (if kW or current reading is faulty).
7 The controller displays incorrect
Mains voltage or incorrect main
alternator voltage.
Check the wiring of the respective phase to the controller.
8 Controller displays incorrect
reading for any of LOP, Fuel Level,
Temperature sensors.
Check respective sensor and its wiring.
Enter “configuration mode” in the controller and verify the
calibration for the respective sensor in configuration.
9 The controller displays incorrect
engine RPM.
Check the MPU connection and configuration (if enabled).
Check wiring of the main alternator’s R-phase and neutral
to the controller.