12kW
¹
Standby Generator
Lubrication
Oil Capacity (L / qt) 1.3 / 1.37
Lubrication System Full Pressure
Recommended Oil 5W30 Full Synthetic
Alternator Specs
Manufacturer Mecc Alte
Type Self-Excited, 4-Lead
Voltage Regulator Automatic
Insulation Class H
Controller Features
Generator Sensing Single phase voltage monitoring
LCD Display Displays multi-line text and graphics
Fault Display Provides additional data regarding fault
Exercise Cycle
Default: Start and run for 16 seconds;
Abort exercise below 40° F (internal
temperature)
Power Save Mode Reduces power consumption
Engine
Engine Brand Vanguard
Engine Speed (RPM) 3600
Engine Fuel
Liquid Propane Vapor (LPV) or
Natural Gas (NG)
Engine Cylinder Configuration OHV
Number of Cylinders 2
Displacement (L / Ci) 0.627 / 38.26
Compression Ratio 8.3:1
Governor Type Electronic
Frequency Regulation +/- 0.3 Hz (0.5%)
Valves OHV with Hardened Seats
Ignition System
Fixed Timing Magnetron®
Electric Ignition
Starter Motor Rating Voltage 12 Volt
Battery Required
12 Volt, Group BCI 24,
500 CCA Minimum
Peak Motor Starting kVA 37
Operations
Engine Specifications
Fuel Consumption
2
Full Load 1/2 Load No Load
BTU / hr
NG - 133,000
LPV - 175,000
NG - 87,000
LPV - 102,000
NG - 54,000
LPV - 44,000
ft
3
/ hr
NG - 133
LPV - 70
NG - 87
LPV - 41
NG - 54
LPV - 18
m
3
/ hr
NG - 3.8
LPV - 2.0
NG - 2.5
LPV - 1.2
NG - 1.6
LPV - 0.5
g
/ hr LPV - 2.0 LPV - 1.2 LPV - 0.5
Sound Rating At 7 Meters
64 dBA
4
3
Unlike some other standby generator manufacturers,
our warranty covers parts, labor AND travel for the
full length of the warranty with no start-up costs!
1
This generator is certified in accordance with UL (Underwriters Laboratories) 2200 (stationary engine generator assemblies) and CSA (Canadian Standards Association) standard C22.2 No. 100-14 (motors and generators).
2
Fuel consumption rates are estimated based on normal operating conditions at ½ load. Generator operation may be greatly affected by elevation and the cycling operation of multiple electrical appliances – fuel flow rates may vary
depending on these factors.
3
See operator’s manual or BRIGGSandSTRATTON.com for complete warranty details.
4
Lowest no-load measurement per ISO 3744. Sound level measurement at other locations around generator may be different depending upon installation configuration.