Installation Guide

22
4 2Wire-Start 18AWG[1mm
2
] twisted pair
conductors, 300V minimum,
90°C Cu wire.
5 2Wire-Start 18AWG[1mm
2
] twisted pair
conductors, 300V minimum,
90°C Cu wire.
Refer to Transfer switch
manual to verify if this
function is available.
Contact Close for
Genset Start.(Only for
transferswitch that
provides this option)
Mains monitoring must be
disabled in the controller.
6 E-Stop 18AWG[1mm
2
] twisted pair
conductors, 300V minimum,
90°C Cu wire.
E-Stop Switch
7 E-Stop 18AWG[1mm
2
] twisted pair
conductors, 300V minimum,
90°C Cu wire.
E-Stop Switch
Contact Open to Shutdown
Genset
8 Not Used
9 12VDC 18AWG[1mm
2
] twisted pair
conductors, 300V minimum,
90°C Cu wire.
10 (B) 18AWG[1mm
2
] twisted pair
conductors, 300V minimum,
90°C Cu wire.
11 (A) 18AWG[1mm
2
] twisted pair
conductors, 300V minimum,
90°C Cu wire.
12 GND 18AWG[1mm
2
] twisted pair
conductors, 300V minimum,
90°C Cu wire.
Refer to the Amplify
Gateway Manual.
Comm to WIFI module
13 12VDC 18AWG[1mm
2
] twisted pair
conductors, 300V minimum,
90°C Cu wire.
14 (B) 18AWG[1mm
2
] twisted pair
conductors, 300V minimum,
90°C Cu wire.
15 (A) 18AWG[1mm
2
] twisted pair
conductors, 300V minimum,
90°C Cu wire.
16 GND 18AWG[1mm
2
] twisted pair
conductors, 300V minimum,
90°C Cu wire.
Refer to the InfoHub™
Premium Manual.
Comm to Cellular module
25 Utility 14AWG [2.5mm
2
] 300V
minimum, 90°C Cu Wire
Transfer switch Utility
26 Utility 14AWG [2.5mm
2
] 300V
minimum, 90°C Cu Wire
Transfer switch Utility
Voltage Sensing for Genset
Start. Use either this signal
or 2-wire start signal for
Genset Start Signal.
For power output connection (L1, L2, Neutral (N), and Ground), refer to the National Electric and local codes.
For communication wires use #18 AWG [1mm
2
] twisted pair conductors, no greater than 500 ft in length, 300 volt wire.
When connecting to the terminal block, fasten only one wire to each connector screw.
Torque terminal block screws to 4.4 in-lb [0.49 Newton meter].
Torque circuit breaker connections to 45 in-lb [5 Newton meter].
Transfer switch connection. In terminal group (E) pin 1, 2 and 3 get connected to a Briggs & Stratton
®
basic transfer
switch (refer to the transfer switch installation manual).