Installation Guide

37
12. Install the 15 Amp fuse into the fuse holder at top of the
control box.
13. Install the roof.
14. Restore utility power to the generator.
15. Push the ON/OFF Switch on the side of the generator to
the “ON” (I) position.
16. Set the generator mode to AUTO.
Replacing the Battery
1. Push the ON/OFF Switch on the side of the generator to
the “OFF” (0) position.
2. Remove utility power to the generator to de-energize the
battery charger.
3. Remove the roof.
4. Remove the 15 Amp fuse from the fuse holder at top of
the control box.
5. Remove the front panel.
6. Disconnect the negative (-) cable at the battery.
7. Disconnect the positive ( + ) cable at the battery.
8. Remove the battery and install replacement battery.
 DON'T POLLUTE. CONSERVE RESOURCES.
RETURN USED BATTERY TO RECYCLING
COLLECTION CENTER.
9. Connect the positive ( + ) cable at the battery.
10. Connect the negative ( - ) cable at the battery.
11. Install the front panel.
12. Install the 15 Amp fuse into the fuse holder at top of the
control box.
13. Install the roof.
14. Restore utility power to the generator.
15. Push the ON/OFF Switch on the side of the generator to
the “ON” (I) position.
16. Set the generator mode to AUTO.
Charging the Battery
If it is necessary to charge the battery, proceed as follows:
1. Push the ON/OFF Switch on the side of the generator to
the “OFF” (0) position.
2. Remove utility power to the generator to de-energize the
battery charger.
3. Remove the roof.
4. Remove the 15 Amp fuse from the fuse holder at top of
the control box.
5. Remove the front panel.
6. Disconnect the negative (-) cable at the battery.
NOTICE Failure to disconnect negative battery cable
could result in equipment failure.DO NOT attempt to
jump start the generator.Damage to equipment resulting
from failure to follow this instruction will void engine and
generator warranty.
7. Charge battery with the battery charger at 2 Amps until
the battery holds 12 Volts. DO NOT exceed 13.7 volts
when charging the battery.
NOTICE DO NOT use a battery booster to quick charge a
low battery.
8. Connect the negative (-) cable at the battery.
9. Install the front panel.
10. Install the 15 Amp fuse into the fuse holder at top of the
control box.
11. Install the roof.
12. Restore utility power to the generator.
13. Push the ON/OFF Switch on the side of the generator to
the “ON” (I) position.
14. Set the generator mode to AUTO.
Not for