Edit a Single Zone
Basic Navigation
Touch the desired field to program. See below for detailed instructions.
Saves parameters to selected module.
Exits out of Single Zone edit menu without saving. Returns to
Single Zone view.
Parameter Definitions
Set Point: Target temperature. Range: 0 to 325°C.
Low Alarm: Low-temperature limit. Module will go into alarm condition
if sensor detects temperature below this temperature.
High Alarm: High-temperature limit. Module will go into alarm condition
if sensor detects temperature above this temperature.
Unlatch One-Shot: Toggle to ON to unlatch a latched zone. See Alarm
Latch Setup on page 27 for more details.
Zone Enable: Toggle for turning on and off modules. Default is ON.
BriskHeat
®
Corporation. All rights reserved
19
Centipede 2
®
Module System
Instructions
OPTIONS / SETUP
A. General: General Options. Set O/I name, scroll rate, and date/time.
See page 21.
B. Network: Modbus settings. See page 24.
C. Password Management: See page 25.
D. Detect Zones: See page 26.
E. Alarm Setup: See page 27.
F. Alarm Log: Lists recent alarm logs. See page 28.