Instruction manual

BriskHeat
®
Corporation. All rights reserved
26
Centipede 2
®
Module System
Instructions
Alarm Setup
User can set-up alarm contacts to remain in alarm position and heaters
powered off until the user manually clears the alarm.
Getting There
Main Menu Global Program Reset Default Setting
Alarm Latch Set-up
Touch the Latch parameter to toggle ON/OFF. See page 14 for
definitions.
Hi Temperature Latch
Lo-Temperature Latch
Open RTD Latch
Short RTD Latch
Saves changes
Exits out of Alarm setup menu without saving. Return to
Options / Set-up menu.
To Unlatch: Go to either the Alarm Setup screen or the Edit a Single Zone
screen. Change Unlatch One-Shot toggle to ON and then touch to
unlatch.
BriskHeat
®
Corporation. All rights reserved
7
Centipede 2
®
Module System
Instructions
Understanding the Centipede 2
®
Touchscreen Interface (C2MOD-OI)
A
B
C
D
E
F
G
A. Touchscreen Display: Used for programming and viewing status of
Centipede 2
®
modules (PN: C2MOD-C).
B. Status LED: See page 11 for an explanation.
C RJ45 Module Connections (Strings 1 through 4): Connect up to
four separate strings of Centipede 2 modules (PN: C2MOD-C) utilizing
CAT5 communication cables. Connect up to 64 modules per string
(128 total modules).
D. RS-232 External Communication Port: See page 30 for installation
instructions. See page 24 for set-up instructions.
E. Ethernet and USB Port: Currently inactive.
F. Input Power Connector and Switch: Power cord connection point
and main power switch for touchscreen operator interface.
G. Dry Contact Alarm Relay Connection: NO or NC (Normally Open or
Normally Closed). See page 31 for installation instructions.