Installation Guide

DT100W
DELAY-OFF TIMER
INCLUDED
Wall Control
Instruction Sheet
Note: Wall plate not included – Use Broan Part No. S97012925 (or equivalent)
CONTROL SPECIFICATIONS
cULus Listed
120 VAC 60 Hz Line Power
9A Max. Total Load (Fan + Lamp)
When used in combination with fan/light fixtures that are switched
together, the device is rated for the following lamps: 600W Incandescent,
150W LED, 150W CFL, or 400VA Inductive Ballasted Fluorescent Lamps
Typical Wire Sizes: 12AWG (MAX) or 14AWG solid or stranded copper
wire
Operating temperature: 32-122°F (0-50°C)
SAFETY
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS,
OBSERVE THE FOLLOWING:
1. Before installing the wall control, switch power off at the service panel
and lock the service disconnecting means to prevent power from being
switched on accidentally. When the service disconnecting means cannot
be locked, securely fasten a prominent warning device, such as a tag,
to the service panel. CAUTION: Risk of Electric Shock - More than one
disconnect switch may be required to de-energize the equipment before
servicing.
2. All electrical work must be done in accordance with local codes,
ordinances, or National Electrical Code, as applicable, including fire-rated
construction codes and standards. FOR SAFETY, THIS PRODUCT MUST
BE GROUNDED. If you are unfamiliar with methods of installing electrical
wiring, secure the services of a qualified electrician.
3. Use copper wire only.
4. WARNING: This device shall not be used in combination with a wall switch
controlling a receptacle.
5. Install only in a UL Listed junction box sized 2.0 x 3.0 x 3.0 in.
(50.8 x 76.2 x 76.2 mm) or larger, with a minimum volume of 18.0 in
3
(295 CM
3
).
6. This control requires a neutral wire for operation.
7. When cutting or drilling into wall or ceiling, do not damage electrical
wiring or other hidden utilities.
8. To prevent serious injury from electrical shock or damage to electrical
components - DO NOT WIRE HOT!
9. Note: When power is applied, the Model DT100W may require
approximately 30 seconds to boot up and be ready to function.
Warranty is void if miswired.
WHT
WHT
WHT
WHT
WHT
WHT
FAN/LIGHT
BLK
BLK
BLK
BLK
BLU
BLU
M
L
RED
RED
RED
SPEED
CONTROL
FAN/LIGHT
CONTROL
120 VAC
LINE IN
GRD
GRD
GRD
WHT
WHT
WHT
FAN
BLK
BLK
BLK
BLU
M
RED
FAN/LIGHT
CONTROL
120 VAC
LINE IN
GRD
GRD
CAP OFF
OR USE
FOR
CONTROLLING
EXISTING
LIGHT
FIXTURE
CONTROLLING
A FAN/LIGHT
CONTROLLING
A FAN
USED WITH SPEED CONTROL
NOTE: If this Fan/Light Control with Off-
Delay is used with a speed control, the
speed control must be connected between
theFan/Light Control and the Fan/Light unit.
For Warranty Statement, Service Parts, Technical Support, or to
Register your product, please visit our website or call:
In the United States - Broan.com 800-637-1453 or NuTone.com
888-336-6151. In Canada - Broan.ca or NuTone.ca 877-896-1119
30
45 15
0
FAN
OFF
FAN
ON
25-min run
time to
satisfy
pre-determined
ventilation
time
30
45 15
0
FAN
OFF
FAN
ON
10-min. run time
while bathroom
is in use
FAN
ON
FAN
ON
FAN
OFF
5-min. run time
to satisfy
pre-determined
ventilation time
10-min. run time
after bathroom usage
to satisfy pre-determined
delay time
HOUR OF OPERATION WITH NO OCCUPANCY
Homeowner wants the fan
to ventilate the bathroom
25 minutes out of every
hour with a 10-minute
delay-off after every time
the bathroom is used.
VENTILATION dial
is set at 25 minutes,
meaning that the fan
will run for 25 minutes
per hour to fully
ventilate the room.
DELAY dial is set at
10minutes, meaning
that the fan will run for
10 minutes after every
occupancy.
The control will determine when the fan needs to start by using the
following formula:
- 60 minutes – VENTILATION setting (25 minutes) = starting
ventilation time (35 minutes). Meaning that 35 minutes into
an hour with no occupancy, the fan will start and run for the
remaining 25 minutes.
- 35 minutes into the hour, the control will start the fan to satisfy
the VENTILATION requirement of 25 minutes.
HOUR OF OPERATION WITH 10-MIN. OF OCCUPANCY
Homeowner
wants the fan
to ventilate
the bathroom
25minutes out
of every hour
with a 10-minute
delay after
every time the
bathroom is
used.
VENTILATION
dial is set at
25 minutes,
meaning that
the fan will
run for 25
minutes per
hour to fully
ventilate the room.
DELAY dial is set at 10 minutes, meaning that the fan will run for
10minutes after every occupancy.
10 minutes into the hour, the bathroom is occupied, and the fan is used
for 10 minutes. The control documents the 10 minutes of usage.
The fan continues to run for 10 minutes after the control is switched off
to satisfy the pre-determined DELAY time of 10 minutes.
20 minutes of VENTILATION time is subtracted from the pre-determined
25 minutes, leaving 5 more minutes of VENTILATION time for the hour.
With 5 minutes left in the hour, the control will start the fan to satisfy the
VENTILATION requirement of 25 minutes.
INSTALLATION
NOTE: This control requires a 120 VAC source (hot and neutral) in the switch
box to operate the wall control.
1. Turn off the power and lockout the service panel before wiring the
control.
2. Install the wall control in at least a 3” deep switch box for #14 AWG wire
or at least a 3 ½” deep switch box for #12 AWG wire. The control can be
installed in either a metal outlet box or a plastic outlet box.
3. Attach the incoming power line and ventilator power line to switch box.
It may be necessary to use two side knockouts for some applications.
Use proper connectors. Provide 6” leads inside box and ventilation
product.
4. Make electrical connections following the diagrams provided. Use wire
nuts. Make sure both the control and the ventilator are properly grounded.
5. Tuck wires in and fasten control to switch box using attached screws.
Verify wall control orientation before installation. Note “TOP” direction
shown on the wall control label.
6. Attach switch plate (not included) using color-matched oval head
screws.
NOTE: The control’s off-delay is adjustable from 5 to 60 minutes but has
been pre-set to approximately 30 minutes. This is the recommended setting
for a properly-sized fan/ventilator to fully exhaust and restore the outdoor air
quality. See DELAY-OFF / VENTILATION ADJUSTMENT” to change settings
for a specific application.
COVER PLATE REMOVAL AND
INSTALLATION
Removal: Grasp sides of the
cover and pull straight outward.
Installation: Align tabs on the
cover with holes in metal panel
and push straight inward.
OPERATING INSTRUCTIONS
The Delay-Off timer will control the connected ventilator and light. To
turn on the ventilator and light, press the top button. Press the bottom
button to turn off the light and to start the delay-off timer for the ventilator.
The ventilator stays on for the user-adjustable DELAY time. Pressing the
bottom button again will turn off the ventilator immediately, regardless of
the DELAY or VENTILATION setting. CAUTION: This setting is not a power
disconnection and should never be used as a disconnecting means for
service, maintenance, or cleaning.
NOTE: When fan is “ON”, Indicator Light on Switch will be “ON”.
The VENTILATION time ranges from 0 to 60 minutes. This setting is
how long, each hour, the ventilator will operate. When in VENTILATION
mode, the ventilator will run for the specified time every hour, including
manual usage. For more information, please see the examples below.
The DELAY time ranges from 0 to 60 minutes. This setting is how long,
after each occupation, the ventilator will operate. When in DELAY mode,
the ventilator will run for the specified time after the light is turned off.
For more information, please see the examples below.
DELAY-OFF / VENTILATION ADJUSTMENT
1. Remove the cover plate.
2. Locate DELAY and VENTILATION adjustment dials (recessed in the
lower portion of control). The settings are indicated by the flat edges of
the dials.
3. Use a screwdriver to rotate the dial clockwise (CW) to increase the
DELAY and VENTILATION time and counter-clockwise (CCW) to
decrease the DELAY and VENTILATION time.
4. When dials are set to the desired settings, replace the cover plate.
DETERMINING VENTIALTION TIME
This control provides a pre-set VENTILATION time for meeting continuous
ventilation codes. After the initial VENTILATION time is set by manually
turning the fan ON, the control will provide continuous activation cycles
every hour.
To calculate the applicable VENTILATION time setting, use the following
formula: VENTILATION time = (required CFM
1
÷ ventilator CFM) x 60
1
from ASHRAE 62.2 formula/table (based on square footage and number of bedrooms)
MODÈLE DT100W
MINUTERIE D’ARRÊT
COMPRIS
Commande murale
Feuillet d’instructions
N.B. : Plaque murale non comprise – Utiliser la pièce S97012925 de Broan
(ou une pièce équivalente)
CARACTÉRISTIQUES
Certification cULus
Alimentation électrique : 120 VCA, 60 Hz
Charge totale maximale : 9 A (ventilateur et lampe)
Lorsqu’utilisé avec un ventilateur luminaire branché sur un même
interrupteur, le produit est compatible avec les lampes à incandescence
de 600 W, à DEL de 150 W, fluocompactes de 150 W ou fluorescentes
à ballast inductif de 400 VA
Calibre de fil habituel : Fil de cuivre massif ou toronné de 12 AWG
(maximum) ou 14 AWG
Température de fonctionnement : 0 à 50 °C (32 à 122 °F)
SÉCURITÉ
MESURE DE SÉCURITÉ POUR RÉDUIRE LE RISQUE D’INCENDIE,
D’ÉLECTROCUTION ET DE BLESSURE :
1. Avant d’installer la commande murale, couper le courant au panneau
d’alimentation et en verrouiller l’accès afin d’éviter une remise en marche
accidentelle. Si le panneau ne peut être verrouillé, y fixer solidement
un dispositif d’avertissement bien visible (p. ex. une étiquette).
ATTENTION : Risque d’électrocution – Il est parfois nécessaire de
déclencher plusieurs disjoncteurs pour mettre l’appareil hors tension
avant l’entretien.
2. Tous les travaux électriques doivent être faits conformément aux codes et
règlements locaux applicables, y compris ceux concernant la protection
contre les incendies. POUR DES RAISONS DE SÉCURITÉ, CE PRODUIT
DOIT ÊTRE MIS À LA TERRE. En cas de doute quant au branchement
des fils, recourir aux services d’un électricien.
3. Utiliser des fils de cuivre seulement.
4. ATTENTION : Ce produit ne doit pas être utilisé en combinaison avec un
interrupteur mural contrôlant une prise de courant.
5. Installer le produit uniquement dans une boîte de jonction certifiée par
UL faisant 50,8 x 76,2 x 76,2 mm (2,0 x 3,0 x 3,0 po) ou plus et ayant
un volume d’au moins 295 cm³ (18,0 po³).
6. Il faut brancher un fil neutre sur la commande pour faire fonctionner ce
produit.
INSTALLATION
N.B. : Il faut acheminer un courant de 120 VCA (phase et neutre) à la boîte
de jonction pour faire fonctionner la commande murale.
1. Couper le courant et verrouiller l’accès au panneau d’alimentation avant
de commencer le branchement de la commande.
2. Installer la commande murale dans une boîte de jonction d’une
profondeur d’au moins 7,6 cm (3 po) pour fils de calibre 14 AWG
ou d’au moins 8,9 cm (3 ½ po) pour fils de calibre 12 AWG. La boîte
électrique peut être en métal ou en plastique.
3. Brancher le fil d’alimentation et le fil du ventilateur sur la boîte de
jonction. Dans certains cas, il faudra utiliser deux entrées défonçables.
Utiliser des serre-fils adaptés. Laisser une longueur de 15 cm (6 po) à
tous les fils dans la boîte de jonction.
4. Brancher les fils tel qu’indiqué sur les schémas fournis. Utiliser des
capuchons de connexion. Mettre correctement à la terre la commande
murale et le ventilateur.
5. Pousser les fils dans la boîte de jonction et y fixer la commande avec
les vis fournies. Vérifier que la commande est dans le bon sens avant de
l’installer (indication du haut de la commande sur son étiquette).
6. Fixer la plaque d’interrupteur (non comprise) avec des vis à tête ovale
de couleur assortie.
N.B. : La minuterie se règle de 5 à 60 minutes, mais est préréglée par défaut
à environ 30 minutes, comme il s’agit de la durée recommandée pour
qu’un ventilateur de taille appropriée expulse complètement l’air d’une
pièce et en rétablisse la qualité. Consulter la section « RÉGLAGE DE LA
DURÉE DU DÉLAI ET DE LA VENTILATION » pour régler la durée selon
une application donnée.
7. S’il faut couper ou percer dans un mur ou un plafond, prendre garde
de ne pas endommager les fils électriques et les autres installations qui
pourraient être dissimulées.
8. Pour éviter les dommages aux composants électriques et les blessures
graves causées par l’électrocution, NE PAS BRANCHER DES FILS SOUS
TENSION.
9. N.B. : Une fois le courant rétabli, il faut environ 30 secondes au produit
DT100W avant d’être prêt à l’emploi.
Garantie nulle en cas de mauvais branchement.
VENTILATEUR/LAMPE
BLANC
BLANC
BLANC
BLEU
NOIR
NOIR
ROUGE
BLANC
TERRE
BLANC
ROUGE
BLEU
TERRE
NOIR
COMMANDE
VENTILATEUR/LAMPE
ALIMENTATION
120 VCA
BLANC
BLANC
BLANC
BLANC
BLANC
BLANC
VENTILATEUR/LAMPE
NOIR
NOIR
NOIR
NOIR
BLEU
BLEU
M
L
ROUGE
ROUGE
ROUGE
COMMANDE
DE VITESE
COMMANDE
VENTILATEUR/LAMPE
ALIMENTATION
120 VCA
TERRE
TERRE
TERRE
Lorem ipsum
BLANC
BLANC
BLANC
VENTILATEUR
NOIR
NOIR
NOIR
BLEU
M
ROUGE
COMMANDE
VENTILATEUR/LAMPE
ALIMENTATION
120 VCA
TERRE
TERRE
CAPUCHON
INSTALLÉ
OU NON
POUR
CONTRÔLE
DE LA
LAMPE
EXISTANTE
BRANCHEMENT AVEC
VENTILATEUR/LAMPE
BRANCHEMENT
AVEC VENTILATEUR
UTILISATION AVEC UNE
COMMANDE DE VITESSE
N.B. : Si la commande de ventilateur/
lampe avec minuterie est utilisée avec une
commande de vitesse, cette dernière doit être
branchée entre la commande de ventilateur/
lampe et le ventilateur/lampe.
RETRAIT ET INSTALLATION DE LA
PLAQUE-COUVERCLE
Retrait : Tenir les côtés de la plaque
et tirer vers le bas en ligne droite.
Installation : Aligner les languettes
de la plaque et les trous du panneau
de métal et pousser en ligne droite.