MODEL RD1, RD2 and RD3
RADIATION DAMPER
INSTALLATION INSTRUCTIONS
For Use In 1, 2 or 3 Hour Rated Floor-Ceiling and Roof-Ceiling Designs.
Horizontal Mount Only.
For Use With The Following Fan Models:
Damper Fan Models
RD1 Broan L100, L100C, L100EX, L100MG, L150, L150C, L150EX,
L150MG, L200, L200C, L200EX, L200MG, L250, L250C, L250EX,
L250MG, L300, L300C, L300EX, L300KMG, L300MG
ABC / Chelsea / Powerline NCF100, NCF150, NCF200, NCF250,
NCF300
Acme 992900, 992901, 992902, 992903, 992904, 992949,
992950, 992951, 992952, 992953, VQ100, VQ150, VQ200,
VQ250, VQ300
American Cool Air CFL10A1151, CFL15A1151, CFL20A1151,
CFL25A1151, CFL30A1151
Breidert / Jenco FF100, FF100-230V, FF100-277V, FF150, FF150-
230V, FF150-277V, FF200, FF200-230V, FF200-277V, FF250,
FF250-230V, FF250-277V, FF300, FF300-230V, FF300-277V
Carnes VCDD010C, VCDD010CF, VCDD010CP, VCDD015C,
VCDD015CF, VCDD015CP, VCDD020C, VCDD020CF, VCDD020CP,
VCDD025C, VCDD025CF, VCDD025CP, VCDD030C, VCDD030CF,
VCDD030CP
PennBarry ZQ105, ZQ155, ZQ205, ZQ255, ZQ305, ZQ105T,
ZQ155T, ZQ205T, ZQ255T, ZQ305T
Twin City T100, T100C, T100EX, T150, T150C, T150EX, T200,
T200C, T200EX, T250, T250C, T250EX, T300, T300C, T300EX
US Fan UVQ100, UVQ150, UVQ200, UVQ250, UVQ300
RD2 Broan L400, L400C, L400EX, L400K, L500, L500C, L500EX,
L500K, L700, L700C, L700EX
ABC / Chelsea / Powerline 992905, 992906, 992907, 992954,
992955, 992956, NCF400, NCF500, NCF700
Acme VQ400, VQ500, VQ700
American Cool Air CFL40A1151, CFL50A1151, CFL70A1151
Breidert / Jenco FF400, FF400-230V, FF400-277V, FF500, FF500-
230V, FF500-277V, FF700, FF700-230V, FF700-277V
Carnes VCDD040C, VCDD040CF, VCDD040CP, VCDD050C,
VCDD050CF, VCDD050CP, VCDD070C, VCDD070CF, VCDD070CP
PennBarry ZQ405, ZQ505, ZQ705
Twin City T400, T400C, T400EX, T500, T500C, T500EX, T700,
T700C, T700EX
US Fan UVQ400, UVQ500, UVQ700
RD3 Broan L900, L900C, L900EX, L1500, L1500C, L1500EX
ABC / Chelsea / Powerline NCF900, NCF1500
Acme 992908, 992909, 992957, 992958, VQ900, VQ1500
American Cool Air CFL90A1151, CFL150A1151
Breidert / Jenco FF900, FF900-230V, FF900-277V, FF1500,
FF1500-230V, FF1500-277V
Carnes VCDD090C, VCDD090CF, VCDD090CP, VCDD150C,
VCDD150CF, VCDD150CP
PennBarry ZQ905, ZQ1505
Twin City T900, T900C, T900EX, T1500, T1500C, T1500EX
US Fan UVQ900, UVQ1500
1. Plan installation so that ceiling penetration is located within ceiling tiles
or panels without necessitating cuts in any ceiling suspension main
runners or cross tees. If required, a maximum of one runner or cross
tee may be cut to accommodate desired damper location. Cut ends must
be supported by a minimum 12 steel wire gauge (3mm) vertical hanger
wire.
2. Position radiation damper on the inlet side of the fan so that the arrow in
the damper will point UP in the finished installation. Attach the damper
to the fan using #8 (M4) sheet metal screws (provided). There must be a
minimum of two connections on each of two opposite sides. Care must
be taken to ensure that the fasteners do not interfere with the closing of
the damper curtain. For best results, use mounting holes provided. Use
of a plastic grille requires that a minimum 5/8” (16mm) wide ceiling
support ange of steel (not provided) be attached to the radiation
damper around the inlet face, using #8 (M4) sheet metal screws or
1/4” (6mm) diameter bolts with nuts. There must be a minimum of two
connections on each of the four sides. Care must be taken to ensure that
the fasteners do not interfere with the closing of the damper curtain.
3. Mount fan/damper assembly to the deck or ceiling structure above or
adjacent to the assembly. If the assembly is hung from the structure
above, a minimum 12 steel wire gauge (3mm) hanger wire must be
used. There must be a minimum of two wires on each of two opposite
sides. If the assembly is directly mounted to the adjacent structure, use
#8 (M4) sheet metal screws or 1/4” (6mm) diameter bolts with nuts to
FAN
CEILING
SUPPORT
FLANGE
5/8” (16 mm)
MINIMUM
PLASTIC
GRILLE
METAL
GRILLE
GRILLE
SCREW
CEILING
DAMPER
MOUNTING
BRACKET
WIRE
If fan has a plastic grille -
a 5/8” (16mm) minimum wide
ceiling support ange of steel
must be used.
If fan has a metal grille -
no ange is required.
ITEM PART NO. DESCRIPTION
1 99523579 Fusible Link
2 99260485 Sheet Metal Nut
3 99170245 Damper Screw
4 99150573 Grille Screw
For replacement parts
telephone
1-800-558-1711.
CLASSIFIED
SEE DETAILS ON UL
CLASSIFICATION
MARKING ON
ENCLOSED PRODUCT
99042780G
mechanically fasten it to the structure. Position fan/damper assembly
so that the inlet face of the radiation damper is flush with the finished
surface of the ceiling. Ceiling opening must be no larger than the inlet
opening of the damper.
4. Attach the grille supplied with the fan over the inlet face of the radiation
damper using #8 (M4) sheet metal screws (provided). There must be a
minimum of one screw on each of two opposite sides. For best results,
use mounting holes provided.