Dimensions Guide

INSTALLATION PLANNING - MODELS 2730 & 2736
DIMENSIONS
NOTE: Dimensions shown are for reference only. Before cutting
out countertop, refer to instructions packed with downdraft and
cooktop.
ELECTRICAL
The unit has a 2 ft. power cord with a 3-pronged plug. Plan to
provide a grounded outlet within reach of this cord. Outlet may
also be wall-mounted, with access hole in cabinet. If local codes
call for hard-wiring, see installation instructions.
DOWNDRAFT
TYPICAL INSTALLATION
COOK TOP
CHIMNEY TOP
COUNTER
TOP
GEAR
MOTOR
COVER
BLOWER
BOX
3-1/4" X 10"
DUCT CONNECTOR
AIR
VENT
120 VAC
GOUNDED
OUTLET
CABINET
FRONT
DUCTWORK
This downdraft blower system is designed for use with 3-1/4" x 10"
rectangular, or 6" round duct. The blower discharge can be
positioned in one of 3 directions with 7-1/2" movement side to
side.
Cooktop depth can vary greatly from one to another. This may
cause the fit of these two appliances to be rather tight.
Pay special attention to the 4 areas of potential interference
highlighted above. The back of the downdraft cut-out will be 1-3/
4" from the cooktop and 2" of FLAT countertop is needed behind
cooktop.
Refer to the cooktop installation instructions for dimensions of
cooktop, countertop cut-out, and cabinet requirements. The 2730
and 2736 can be installed in most standard 30" and 36" wide
cabinets.
FRONT TO BACK
INSIDE CABINET DEPTH
DOWNDRAFT
B
A
COUNTER TOP
2"
1 3/4 "
COOKTOP
The system will operate most efficiently when the ductwork does
not exceed 40 feet of equivalent duct. The chart above, shows
equivalent feet of elbows and transitions. The number of feet of
straight 3-1/4" x 10" or 6" duct plus the equivalent feet of elbows
or transitions to be used should equal 40 feet or less.
The equivalent feet of various roof and wall caps has been taken
into consideration. Do not include them in this calculation.
3-1/4" x 10" TO
6" RD.
TRANSITION
2 FT.
3-1/4" X 10"
90
o
ELBOW
8 FT.
6" RD.
ELBOW
6 FT.
RIGHT
DISCHARGE
LEFT
DISCHARGE
DOWN
DISCHARGE
(as shipped)