Installation

21
B6LC and
B1600705
UNITS
Outdoor Air -40°F Outdoor Air -22°F Outdoor Air -4°F Outdoor Air 14°F Outdoor Air 32°F
Desired Air Temperature Desired Air Temperature Desired Air Temperature Desired Air Temperature Desired Air Temperature
Supply
Air
(CFM)
Supply
Air
(L/s)
55°F 68°F 73°F 55°F 68°F 73°F 55°F 68°F 73°F 55°F 68°F 73°F 55°F 68°F 73°F
kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
700 330 7.4 10.4 11.5 5.6 8.6 9.7 3.9 6.8 8.0 2.1 5.1 6.2 0.3 3.3 4.4
650 307 6.6 9.4 10.5 5.0 7.8 8.9 3.4 6.2 7.3 1.8 4.6 5.6 0.2 3.0 4.0
600 283 5.9 8.5 9.4 4.5 7.0 8.0 3.0 5.6 6.5 1.6 4.1 5.1 0.1 2.7 3.7
550 259 5.2 7.6 8.5 3.9 6.3 7.2 2.6 5.0 5.9 1.3 3.7 4.6 0.1 2.4 3.3
500 236 4.0 6.1 7.0 3.0 5.1 5.9 1.9 4.0 4.9 0.9 3.0 3.8 - 1.9 2.7
450 212 3.0 4.9 5.6 2.1 4.0 4.8 1.3 3.2 3.9 0.4 2.3 3.1 - 1.5 2.2
400 189 2.2 3.9 4.6 1.5 3.2 3.9 0.9 2.5 3.2 0.2 1.9 2.5 - 1.2 1.8
Although the B6LC, B1600705 and B12LC models have good efficiencies, the supply air could be colder than the ambient room air. It is possible to eliminate the
discomfort associated with this temperature difference by installing an electric duct heater. This will temper the air before it is distributed throughout the building.
The tables below gives the heating requirements at different temperatures and airflows.
NOTE:
The data does not reflect a reduction in effectiveness due to frosting.
Based on the standard air at: 1.2 Kg/m3 and Cp = 1.0 KJ/Kg°C
13.35 lb/ft3 and Cp = .24 Btu/lbm°F
Appendix G
MAKE-UP HEAT REQUIREMENTS
B6LC AND B1600705