Spec Sheet

HEAT RECOVERY VENTILATOR/
ENERGY RECOVERY VENTILATOR
FOR LIGHT COMMERCIAL APPLICATIONS
High CFM ventilation for small business owners concerned about
indoor air quality (excess moisture, smoke, odors and cleanliness).
Suitable for installation above a suspended ceiling, mechanical room
or suspended from a ceiling, this model delivers year-round comfort
and sensible heat recovery with virtually no cross leakage. On this unit,
the heat exchange efficiency can reach up to 60%.
Only 24.5” high for false ceiling installation
• Defrost system
• Two-speed control
Low voltage remote switch
REPAIRS AND MAINTENANCE
All parts of the B12LC such as the large access door and the entire
motor sub-assembly can be removed for ease of maintenance.
Furthermore, the electronic circuit board reduces electro-mechanical
parts, minimizing repair time to a minimum.
ORDERING EXAMPLE
B12LC 
VB0240
Available at:
Control
Built-in electronic circuit board ready to receive the VT1W main wall
control.
Heat recovery cores/Energy recovery cores
Dimensions: 12” x 12” x 13.125”
Exchange surface: 200 ft²
Weight: HRV Polypropylene: 9.2 lb.; Aluminum 13.9 lb.
ERV Polymerised paper: 11.2 lb.
Type: plate to plate core
Quantity: 3
Material: HRV polypropylene or aluminum
ERV polymerised paper
Warranty: HRV 15 years; ERV 5 years
VK0103A
15"
[381]
CORE
REVERSED DOOR OPTION
A MINIMUM OF 15" [381] CLEARANCE FROM ANY OBSTRUCTION IS REQUIRED
FOR REMOVAL OF CORES, FANS, ETC.
THE ACCESS DOOR CAN BE REMOVED FROM CABINET
WITH ONLY 2" [51] OF CLEARANCE.
ACCESS DOOR
Options
• Medium e ciency air supply  lters
Recirculation or exhaust defrost
Requirements and Standards
Complies with the CSA C22.2, no. 113 Standard applicable to ventilators
Complies with UL Standard 1812 - ducted Heat Recovery Ventilators
and Energy Recovery Ventilators
Warranty
The B12LC unit is fully protected by a 2-year warranty on parts, the
best in the industry, and the heat recovery cores are covered by a
15-year warranty and the energy recovery cores are protected by a 5-year
warranty.
PACKAGE
C Corrosion resistant 
W White prepaint
When ordered‚ the recirculation defrost damper module is factory
installed.
Not recommended with aluminum cores.
Nt recommended fr ERV.
Not for all configurations; please contact a sales representative for
more details.
FROST CONTROL
D Recirculation defrost
E Exhaust only
ACCESS DOOR
S Standard
R Reversed (right hand  ow)
LOW SPEED
N Normal low speed
BROAN B12LC
Part no. B12LC
767 to 1026 cfm (0.4 in. w.g.)
CORE MATERIAL
P
Polypropylene
core
A Aluminum core
H
Polymerised
paper ERV HM
N
OUTDOOR TEMPERATURE DEFROST CYCLE (IN MINUTES)
°C °F
DEFROST/OPERATION
WARMER THAN -5 WARMER THAN 23 NO DEFROST
-5 TO -15 23 TO 5 12/60
-15 TO -30 5 TO -21 12/24
-30 & LESS -21 & LESS 12/12