User Guide

6
STALE AIR EXHAUST DUCTWORK:
Install registers in areas where contaminants and humidity are
produced: Kitchen, bathrooms, laundry room, etc.
Install registers on an interior wall, 6 to 12 inches away from the
ceiling OR in the ceiling.
Install the kitchen register at least 4 feet away from the range.
Bathroom fans and range hoods can be used to better exhaust stale
air.
Homes with more than one level require at least one exhaust register
at the highest level.
FRESH AIR DISTRIBUTION DUCTWORK:
Install registers in bedrooms, dining room, living room and basement.
Install registers in the ceiling OR high on the walls with the airflow
directed towards the ceiling.
If a register must be installed in the floor, direct the air flow up the
wall.
2.2.1 FULLY DUCTED SYSTEM
2.2 INSTALLING THE DUCTWORK AND THE REGISTERS
Never install a stale air exhaust register in a room where there is a combustion device, such as a gas furnace, a
gas water heater or a fireplace.
WARNING
!
VH0118
DO NOT CONNECT TO THE SUPPLY SIDE
OF THE FURNACE/AHU
VJ0136
STALE AIR EXHAUST DUCTWORK:
Same as for Fully Ducted System, described on point 2.2.1.
FRESH AIR DISTRIBUTION:
Connect the fresh air distribution duct of the unit to the furnace/AHU
return duct at least 10 feet away from the furnace/AHU (A+B)*.
* This 10-ft. distance applies only in areas where the outside temperature
falls below the freezing point (32°F).
NOTE: The furnace/AHU blower operation can be synchronized with
the unit (see Section 3.3). It is recommended, but not essential that the
furnace/AHU blower runs when the unit is in operation.
2.2.2 EXHAUST DUCTED SYSTEM
When performing duct connection to the furnace/AHU, installation must be done in accordance with all applicable
codes and standards. Please refer to your local building code.
WARNING
!
A+B= MIN. 10’
VH0119
For this type of installation, you must perform steps in
section 2.2.4 to make sure that the pressure in the return
duct of the furnace/AHU allows the unit to operate properly.
CAUTION