Installation Guide

1
2
3
4
English
MODEL RD1, RD2 and RD3
RADIATION DAMPER
INSTALLATION INSTRUCTIONS
For Use In 1, 2 or 3 Hour Rated Floor-Ceiling and Roof-Ceiling Designs
Horizontal Mount Only
For Use With The Following Fan Models:
Damper Fan Models
RD1 Broan
L100, L100C, L100EX, L100MG, L150, L150C, L150EX,
L150MG, L200, L200C, L200EX, L200MG, L250, L250C, L250EX,
L250MG, L300, L300C, L300EX, L300KMG, L300MG
ABC / Chelsea / Powerline
NCF100, NCF150, NCF200, NCF250,
NCF300
Acme
992900, 992901, 992902, 992903, 992904, 992949, 992950,
992951, 992952, 992953, VQ100, VQ150, VQ200, VQ250, VQ300
American Cool Air
CFL10A1151, CFL15A1151, CFL20A1151,
CFL25A1151, CFL30A1151
Breidert / Jenco
FF100, FF100-230V, FF100-277V, FF150, FF150-
230V, FF150-277V, FF200, FF200-230V, FF200-277V, FF250, FF250-
230V, FF250-277V, FF300, FF300-230V, FF300-277V
Carnes
VCDD010C, VCDD010CF, VCDD010CP, VCDD015C,
VCDD015CF, VCDD015CP, VCDD020C, VCDD020CF, VCDD020CP,
VCDD025C, VCDD025CF, VCDD025CP, VCDD030C, VCDD030CF,
VCDD030CP
Twin City
T100, T100C, T100EX, T150, T150C, T150EX, T200,
T200C, T200EX, T250, T250C, T250EX, T300, T300C, T300EX
US Fan
UVQ100, UVQ150, UVQ200, UVQ250, UVQ300
RD2 Broan
L400, L400C, L400EX, L400K, L500, L500C, L500EX, L500K,
L700, L700C, L700EX
ABC / Chelsea / Powerline
992905, 992906, 992907, 992954,
992955, 992956, NCF400, NCF500, NCF700
Acme
VQ400, VQ500, VQ700
American Cool Air
CFL40A1151, CFL50A1151, CFL70A1151
Breidert / Jenco
FF400, FF400-230V, FF400-277V, FF500, FF500-
230V, FF500-277V, FF700, FF700-230V, FF700-277V
Carnes
VCDD040C, VCDD040CF, VCDD040CP, VCDD050C,
VCDD050CF, VCDD050CP, VCDD070C, VCDD070CF, VCDD070CP
Twin City
T400, T400C, T400EX, T500, T500C, T500EX, T700,
T700C, T700EX
US Fan
UVQ400, UVQ500, UVQ700
RD3 Broan
L900, L900C, L900EX, L1500, L1500C, L1500EX
ABC / Chelsea / Powerline
NCF900, NCF1500
Acme
992908, 992909, 992957, 992958, VQ900, VQ1500
American Cool Air
CFL90A1151, CFL150A1151
Breidert / Jenco
FF900, FF900-230V, FF900-277V, FF1500, FF1500-
230V, FF1500-277V
Carnes
VCDD090C, VCDD090CF, VCDD090CP, VCDD150C,
VCDD150CF, VCDD150CP
Twin City
T900, T900C, T900EX, T1500, T1500C, T1500EX
US Fan
UVQ900, UVQ1500
1. Plan installation so that ceiling penetration is located within ceiling tiles or pan-
els without necessitating cuts in any ceiling suspension main runners or cross
tees. If required, a maximum of one runner or cross tee may be cut to accom-
modate desired damper location. Cut ends must be supported by a minimum
12 steel wire gauge (3mm) vertical hanger wire.
2. Position radiation damper on the inlet side of the fan so that the arrow in the
damper will point
UP in the finished installation. Attach the damper to the fan
using #8 (M4) sheet metal screws (provided). There must be a minimum of two
connections on each of two opposite sides. Care must be taken to ensure that
the fasteners do not interfere with the closing of the damper curtain. For best
results, use mounting holes provided. Use of a
plastic grille requires that a
minimum 5/8” (16mm) wide ceiling support flange of steel (not provided)
be attached to the radiation damper around the inlet face, using #8 (M4)
sheet metal screws or 1/4” (6mm) diameter bolts with nuts. There must be a
minimum of two connections on each of the four sides. Care must be taken to
ensure that the fasteners do not interfere with the closing of the damper cur-
tain.
3. Mount fan/damper assembly to the deck or ceiling structure above or adjacent
to the assembly. If the assembly is hung from the structure above, a minimum
12 steel wire gauge (3mm) hanger wire must be used. There must be a mini-
mum of two wires on each of two opposite sides. If the assembly is directly
mounted to the adjacent structure, use #8 (M4) sheet metal screws or 1/4”
FAN
CEILING
SUPPORT
FLANGE
5/8” (16 mm)
MINIMUM
PLASTIC
GRILLE
METAL
GRILLE
GRILLE
SCREW
CEILING
DAMPER
MOUNTING
BRACKET
WIRE
If fan has a plastic grille -
a 5/8 (16mm) minimum wide
ceiling support flange of steel
must be used.
If fan has a metal grille -
no flange is required.
ITEM PART NO. DESCRIPTION
1 99523579 Fusible Link
2 99260485 Sheet Metal Nut
3 99170245 Damper Screw
4 99150573 Grille Screw
For replacement parts
telephone
1-800-558-1711.
CLASSIFIED
SEE DETAILS ON UL
CLASSIFICATION
MARKING ON
ENCLOSED PRODUCT
99042780F
(6mm) diameter bolts with nuts to mechanically fasten it to the structure. Posi-
tion fan/damper assembly so that the inlet face of the radiation damper is flush
with the finished surface of the ceiling. Ceiling opening must be no larger
than the inlet opening of the damper.
4. Attach the grille supplied with the fan over the inlet face of the radiation damper
using #8 (M4) sheet metal screws (provided). There must be a minimum of
one screw on each of two opposite sides. For best results, use mounting holes
provided.

Summary of content (6 pages)