Technical data

Brocade 300 Power Supply Specifications (Continued)TABLE 5
Specification Value
Input voltage 85 - 264 VAC, universal
Input line frequency 47 - 63 Hz
BTU rating 277 BTU/hr
Inrush current 21.5 Amps at 240 Vac Cold Start
Environmental requirements
The following table lists the acceptable environment for both operating and nonoperating (such as
during transportation or storage) conditions.
Environmental Requirements TABLE 6
Condition Acceptable Range During Operation Acceptable Range During Non-
Operation
Ambient Temperature -10° to +40° C (14° to 104° F) -25° to 70° C (-13° to 158° F)
Humidity 10% to 85% RH noncondensing, at 40°C, with
maximum gradient of 10% per hour
10% to 90% RH noncondensing, at 70°
C
Altitude 0 to 3 km (9,842 ft) above sea level 0 to 12 km (39,370 ft) above sea level
Shock 20 G, 6 ms duration, half sine wave 33 G, 11 ms duration, half sine
Vibration 0.5 G, 5-500 Hz 2.0 G, 5-500 Hz
Air flow High speed: 39.1 CMH (23 CFM)
Low speed: 30.6 CMH (18 CFM)
None required
NOTE
The -10° to 40° Celsius range applies to the ambient air temperature at the air intake vents on the non-
port side of the switch. The temperature inside the switch can be up to 80° Celsius during switch
operation. If the internal temperature range exceeds the operating ranges of the components, the LEDs,
error messages, and Fabric Watch alerts indicate a problem. Enter the tempShow or Fabric Watch
commands to view temperature status.
Environmental requirements
Brocade 300 Hardware Reference Manual 35