Technical data
2-2 Brocade SilkWorm 4100 Hardware Reference Manual
Publication Number: 53-0000563-02
Items Included with the SilkWorm 4100
2
If installing the switch in a cabinet:
• The cabinet must be a standard EIA cabinet.
• Plan a cabinet space that is 1 rack unit high (1.75 inches; 4.44 cm), 19 inches (48.3 cm) wide,
and at least 24 inches (61cm) deep.
• Ground all equipment in the cabinet through a reliable branch circuit connection and maintain
ground at all times. Do not rely on a secondary connection to a branch circuit, such as a power
strip.
• Ensure that airflow and temperature requirements are met on an ongoing basis, particularly if
the switch is installed in a closed or multirack assembly.
• Verify that the additional weight of the switch does not exceed the cabinet’s weight limits or
unbalance the cabinet in any way.
• Secure the cabinet to ensure stability in case of unexpected movement.
For additional installation, electrical, environmental, and other considerations, refer to the SilkWorm
Switch Safety Guide.
Items Included with the SilkWorm 4100
The following items are included with the standard shipment of the SilkWorm 4100:
• The SilkWorm 4100 switch, containing three fan assemblies and two power supplies
• The Fixed Rack Mount Kit, with installation instructions
• One accessory kit, containing the following items:
- The SilkWorm 4100 QuickStart Guide
- The Brocade Documentation CD-ROM
- 32 SFP (small-form-factor pluggable) transceivers (optional)
- Rubber mounting feet (to be used when setting up the SilkWorm 4100 as a standalone unit)
- Two grounded 6-ft. (approximately 1.83 meters) power cords.
- The power plug type is NEMA5-15
- Power plug current/voltage rating: 15A/125V
- Cordage type: SVT
- Current rating/wire gauge: 10A/ 18AWG
- Connector at system end of cordset: IEC 60320/ C13
- One serial cable, 10-ft. (approximately 3 meters) long, which can be converted from a DB-
9 serial cable to an RJ-45-style serial cable by removing the adapter on the end of the cable