User guide

Each switch must be assigned a unique Ethernet IP address during conguration. Once
the default Ethernet IP address on the 4Gb SAN Switch has been changed, you may
install additional 4Gb SAN Switches in the enclosure.
See the appropriate HP BladeSystem Enclosure Setup and Installation Guide for help
identify ing your specic enclosure setup, available connections and power requirements.
Electrical considerations
The 4Gb SAN Switc
h requires 35 watts, provided by the enclosure. N o other power
requirement or p rovision exists.
Environmental considerations
Ensure proper cooling and ventilation by verifying the following:
Theairventsontheenclosurearenotblockedorrestricted.
The ambient air temperature at the front of the enclosure does not exceed 35°C
(95°F) while the switch is op erating.
IMPORTANT:
Thedustcoversthatshipwithyour4GbSANswitch
must
be inserted into any ports
where SFPs a re not installed, to help contain air ow in the BladeSystem chassis.
Brocade 4Gb SAN Switch for HP c-Class BladeSystem
23