INSTALLATION - CLEARANCES
5
C) Clearance between grill and combustible wall
above the counter top surface
1. The grill must have a minimum of 15” [375mm] right,
left, and rear clearance from any combustible wall
above the non-combustible counter top surface.
D) Clearance between the grill and combustible or
non-combustible construction below the counter
top surface .
1. “0” clearance is required below the counter top to non-
combustible construction.
2. 4” (100) mm clearance is required below the countertop
to combustible construction to the rear.
3. 1” (25) mm clearance is required below the countertop
to combustible construction to the left and right sides.
4. 3/8” (9.5mm) clearance is required below the
countertop to a combustible front wall of the enclosure
provided the front wall of the enclosure is less than 1”
(25) mm thick.