Operating Guide

INSTALLATION - ENCLOSURES
8
GRILL ENCLOSURE WITHOUT AN LP GAS
CYLINDER
Ventilation totaling a minimum free area of 10 square
inches (65 square cm) is provided at the top of the grill
through the side trim and rear trim of the grill
Ventilation totaling a minimum free area of 5 square
inches (13 square cm) is provided at the bottom of the
grill through the bottom trim of the grill
Ventilation totaling a minimum free area of 10 square
inches (33 square cm) is required at the bottom of the
enclosure
Position the bottom edge of vent 1” (25mm) or less
from the floor level and within 5” (127mm) of the bottom
of the enclosure
Be careful not to obstruct these vents
GRILL ENCLOSURE DIMENSIONS
420 / 490
590
XL
A
MIN
30 5/16” [770mm]
36 11/16” [932mm]
44” [1118mm]
MAX
30 15/32” [774mm]
36 27/32” [936mm]
44 5/32” [1122mm]
B
MIN
31 3/8" [797mm]
37 3/4" [959mm]
45 1/8" [1146mm]
C
MIN
27” [686mm] with surface mount GFCI receptacle
GRILL ENCLOSURE WITH AN LP GAS
CYLINDER
A remote LP gas cylinder enclosure is required for
installations that use an LP gas cylinder
Construct enclosure with four sides, a top and a bottom
with minimum inside dimensions of:
o height 20” (50cm)
o width – 15” (38.5cm)
o depth 14” (36cm)
Enclosure must not allow space for a spare tank to be
stored inside the enclosure
Ventilation totaling a minimum free area of 20 square
inches (130 square cm) is required at the top on the
exposed exterior wall of the enclosure. (As per ANSI
Standard Z21.58/CSA 1.6)
Ventilation totaling a minimum free area of 10 square
inches (65 square cm) is required at the bottom on the
exposed exterior wall of the enclosure. (As per ANSI
Standard Z21.58/CSA 1.6)
Position the top vent(s) within 5” (127mm) of the top of
the enclosure
Position the bottom vent 1” (25mm) or less from the
floor level and within 5” (127mm) of the bottom of the
enclosure
The remote LP gas cylinder enclosure must isolate the
LP gas cylinder from the burner compartment, so that it
provides shielding from radiation, be a flame barrier
and provide protection from foreign material such as
hot drippings
DANGER
Failure to build a remote LP gas cylinder enclosure for
a single 20 lb. LP gas cylinder only, following the
requirements for ventilation, cylinder retention and
separation of the LP gas cylinder from a heat source,
listed in the ANSI Standard for Outdoor Cooking Gas
Appliances, Z21.58/CSA 1.6, could be dangerous, and
result in a fire or an explosion causing serious bodily
injury or death and damage to property.