Operating Guide
INSTALLATION - ENCLOSURES
8
GRILL ENCLOSURE WITHOUT AN LP GAS
CYLINDER
• Ventilation totaling a minimum free area of 10 square
inches (65 square cm) is provided at the top of the grill
through the side trim and rear trim of the grill
• Ventilation totaling a minimum free area of 5 square
inches (13 square cm) is provided at the bottom of the
grill through the bottom trim of the grill
• Ventilation totaling a minimum free area of 10 square
inches (33 square cm) is required at the bottom of the
enclosure
• Position the bottom edge of vent 1” (25mm) or less
from the floor level and within 5” (127mm) of the bottom
of the enclosure
• Be careful not to obstruct these vents
GRILL ENCLOSURE DIMENSIONS
420 / 490
590
XL
A
MIN
30 5/16” [770mm]
36 11/16” [932mm]
44” [1118mm]
MAX
30 15/32” [774mm]
36 27/32” [936mm]
44 5/32” [1122mm]
B
MIN
31 3/8" [797mm]
37 3/4" [959mm]
45 1/8" [1146mm]
C
MIN
27” [686mm] with surface mount GFCI receptacle
GRILL ENCLOSURE WITH AN LP GAS
CYLINDER
• A remote LP gas cylinder enclosure is required for
installations that use an LP gas cylinder
• Construct enclosure with four sides, a top and a bottom
with minimum inside dimensions of:
o height – 20” (50cm)
o width – 15” (38.5cm)
o depth – 14” (36cm)
• Enclosure must not allow space for a spare tank to be
stored inside the enclosure
• Ventilation totaling a minimum free area of 20 square
inches (130 square cm) is required at the top on the
exposed exterior wall of the enclosure. (As per ANSI
Standard Z21.58/CSA 1.6)
• Ventilation totaling a minimum free area of 10 square
inches (65 square cm) is required at the bottom on the
exposed exterior wall of the enclosure. (As per ANSI
Standard Z21.58/CSA 1.6)
• Position the top vent(s) within 5” (127mm) of the top of
the enclosure
• Position the bottom vent 1” (25mm) or less from the
floor level and within 5” (127mm) of the bottom of the
enclosure
• The remote LP gas cylinder enclosure must isolate the
LP gas cylinder from the burner compartment, so that it
provides shielding from radiation, be a flame barrier
and provide protection from foreign material such as
hot drippings
DANGER
Failure to build a remote LP gas cylinder enclosure for
a single 20 lb. LP gas cylinder only, following the
requirements for ventilation, cylinder retention and
separation of the LP gas cylinder from a heat source,
listed in the ANSI Standard for Outdoor Cooking Gas
Appliances, Z21.58/CSA 1.6, could be dangerous, and
result in a fire or an explosion causing serious bodily
injury or death and damage to property.