Heat Pump User Manual

53
PERFORMANCE DATA — 548F (cont)
ELECTRIC HEATING CAPACITIES — 548F090-120
*Two heater packages required to provide kW indicated.
NOTES:
1. The rated heater voltage is 240, 480, and 575 v. If power distribution voltage varies from rated heater voltage, heater kW will vary accordingly.
2. To determine heater kW at voltages other than those shown in table, use the following formula:
Heater kW new = Heater kW rated x (unit power distribution voltage/rated heater voltage)
2
As an example:
For a 16 kW heater rated at 240 v with a power distribution voltage of 215 v
kW new = 16 kW (215/240)
2
kW new = 12.8 kW (rating at 215 v)
UNIT
548F
UNIT VOLTAGE
(60 Hz)
ACCESSORY
kW
ELECTRIC HEATER
PART NUMBER
CRHEATER---A00
SINGLE POINT BOX
PACKAGE NO.
CRSINGLE---A00
090
208/230/240
(3 phase)
7.8/ 9.6/10.4
12.0/14.7/16.0
18.6/22.8/24.8
24.0/29.4/32.0
31.8/39.0/42.4*
017
010
011
012
012 and 017
007
007
009
009
013
460/480
(3 phase)
12.8/13.9
15.2/16.5
25.6/27.8
30.4/33.0
38.4/41.7*
016
013
014
015
014 and 016
006
006
008
008
010
575
(3 phase)
17.0
34.0
018
019
006
006
120
208/230/240
(3 phase)
7.8/ 9.6/10.4
12.0/14.7/16.0
24.0/29.4/32.0
31.8/39.0/42.4*
37.6/46.2/50.0*
017
010
012
012 and 017
010 and 012
012
012
015
017
017
460/480
(3 phase)
15.2/16.5
25.6/27.8
30.4/33.0
38.4/41.7*
45.9/50.0*
013
014
015
014 and 016
013 and 015
011
014
014
016
016
575
(3 phase)
17.0
34.0
51.0*
018
019
018 and 019
011
014
016
548F