COMMERCIAL SINGLE PACKAGE ROOFTOP UNITS GAS HEATING/ELECTRIC COOLING UNITS 580F, 579F, 581A/B DuraPac and DuraPac Plus Series Sizes 036-300 3 to 25 Tons 48-910df 581A210-300 SIZES 036-073 50-1242f 50-1214df 579F180-216 581A155,180 580F180,210 SIZES 090-151 a48-8207 580F240 579F240-300 Standard efficiency units (580F072, 090, 120, 150 and 579F180-300) are available. Standard efficiency units (580F036-060, 073, 091,103,121,151, and 180-300) that meet ASHRAE 90.
TABLE OF CONTENTS The unsightly appearance of flue stacks is eliminated and the effects of wind on heating operations are diminished by the induced draft combustion system. The inducer fan draws hot combustion gas through the heat exchanger at the optimum rate for the most effective heat transfer. The heat exchanger operates under negative pressure, preventing flue gas leakage into the indoor supply air.
FEATURES/BENEFITS (cont) Accessory upgrade kits allow for control by differential dry-bulb temperature (outdoor vs return), outdoor air enthalpy changeover, or more precise differential enthalpy control. Units can be equipped with different economizer options to meet specific controls applications. The factory-installed or field-installed EconoMi$er IV and EconoMi$er2 are available.
FEATURES/BENEFITS (cont) Reheat mode will operate when outdoor temperatures diminish and the need for latent capacity is required for sole humidity control. Hot Gas Reheat mode will provide neutral air for maximum dehumidification operation. EXCLUSIVE HOT GAS REHEAT DEHUMIDIFICATION PACKAGE (581A181-300) — The hot gas reheat dehumidification package is a result of recent advances by Bryant in controlling comfort levels.
MODEL NUMBER NOMENCLATURE 580F036-150 (Standard and Medium Efficiency) 3 to 121/2 Tons 580F E V 060 120 N 580F – Packaged Rooftop Standard Efficiency Factory-Installed Options Code Voltage Designation J – 208/230-1-60 P – 208/230-3-60 E – 460-3-60 T – 575-3-60 Gas Heat Options A – Standard N – Low NOx Unit S – Stainless Steel Heat Exchanger Fuel Control Type/Heat Exchanger V – Natural Gas/Direct Spark Ignition N – Low NOx Natural Gas/Direct Spark Ignition/Stainless Steel Heat Exchanger Nominal Ton
MODEL NUMBER NOMENCLATURE — 579F180-300 579F E V 180 230 –– C B Fan Drive Option (Standard Motor) B – Standard Low-Medium Fan Drive Static Capability D – Alternate High Fan Drive Static Capability 579F – Single-Package Standard-Efficiency Gas/Electric Unit Voltage Designation E – 460-3-60 P – 208/230-3-60 T – 575-3-60 Factory-Installed Outdoor-Air and Other Upgrade Options C – EconoMi$er IV H – Manual Outdoor-Air Damper Fuel and Control Type V – Natural Gas/Electric Relight Pilot Design Series C
MODEL NUMBER NOMENCLATURE 581A155, 180, 181 — 13 to 15 Tons 581A E V 180 230 –– C B Fan Drive Position (Standard Motor) B – Standard Low-Medium Fan Drive Static Capability D – Alternate High Fan Drive Static Capability 581A – Single Package High Efficiency Gas/Electric Unit Voltage Designation E – 460-3-60 P – 208/230-3-60 T – 575-3-60 Factory-Installed Outdoor-Air and Other Upgrade Options C – EconoMi$er IV H – Manual Outdoor-Air Damper Fuel and Control Type V – Natural Gas/Electric Relight Pilo
ARI* CAPACITY RATINGS — 580F036-151 UNIT 580F NOMINAL TONS STANDARD CFM 036 048 060 3 4 5 1200 1600 2000 NET COOLING CAPACITY (Btuh) 72,000 71,000 85,000 Belt Drive Direct Drive 4.0 5.3 6.7 10.0 10.0 10.0 9.7 9.7 9.7 SOUND RATING (dB) 81 81 81 EER 8.0 7.0 9.6 9.0 10.1 8.9 SOUND RATING (dB) 81 80 87 88,000 8.7 10.1 82 10.5 100,000 117,000 114,000 144,000 9.9 13.0 11.3 16.0 10.1 9.0 10.1 9.0 82 88 84 87 10.4 9.40 11.0 9.20 14.3 9.5 86 9.
ARI* CAPACITY RATINGS (cont) HEATING CAPACITIES AND EFFICIENCIES (Standard Efficiency Units) — 580F036-151 (cont) 208/230/460-3-60 — SINGLE-STAGE GAS HEAT — LOW NOx UNIT 580F 036060N 036090N 048060N 048090N 048120N 060060N 060090N 060120N INPUT CAPACITY 60,000 90,000 60,000 90,000 120,000 60,000 90,000 120,000 OUTPUT CAPACITY 49,000 73,000 49,000 73,000 98,000 47,000 73,000 98,000 TEMPERATURE RISE (°F) 20-50 30-60 20-50 30-60 40-70 20-50 30-60 40-70 MINIMUM HEATING AIRFLOW (CFM) 910 1130 910 1130 1300 9
ARI* CAPACITY RATINGS — 581B036-150 UNIT 581B 036 048 060 072 090 102 120 150 NOMINAL TONS 3 4 5 6 71/2 81/2 10 121/2 COOLING (Btuh) 36,000 46,000 61,000 73,000 90,000 103,000 120,000 138,000 TOTAL kW 3.21 4.25 5.55 6.70 8.18 8.90 10.91 14.40 SEER† EER 13.0 13.0 13.0 — — — — — 11.20 11.05 11.00 11.00 11.00 11.60 11.00 9.6 SOUND RATING dB 76 76 80 80 82 82 84 86 IPLV ** ** ** ** 11.6 12.8 11.4 10.
ARI* CAPACITY RATINGS (cont) HEATING CAPACITIES AND EFFICIENCIES — 581B036-150(cont) 208/230/460-3-60 — SINGLE-STAGE GAS HEAT — LOW NOx UNIT 581B INPUT CAPACITY OUTPUT CAPACITY TEMPERATURE RISE (°F) MINIMUM HEATING AIRFLOW (CFM) 036060N 036090N 048060N 048090N 048120N 060060N 060090N 060120N 60,000 90,000 60,000 90,000 120,000 60,000 90,000 120,000 50,000 74,000 50,000 74,000 101,000 50,000 74,000 101,000 20-50 30-60 20-50 30-60 40-70 20-50 30-60 40-70 930 1150 930 1150 1340 930 1150 1340 EFFICIEN
ARI* CAPACITY RATINGS — 579F180-300 LOW HEAT UNITS UNIT 579F NOMINAL TONS 180 216 240 300 15 18 20 25 NET COOLING CAPACITY (Btuh) 174,000 188,000 220,000 268,000 TOTAL WATTS EER 20,128 21,619 25,513 31,068 8.6 8.7 8.6 8.6 SOUND RATING (dB) 88 88 94 94 IPLV 9.3 9.5 8.7 9.2 HIGH HEAT UNITS dB db EER IPLV wb UNIT 579F NOMINAL TONS 180 216 240 300 15 18 20 25 — — — — — NET COOLING CAPACITY (Btuh) 174,000 186,000 218,000 268,000 TOTAL WATTS EER 20,154 21,798 25,719 31,600 8.6 8.5 8.5 8.
ARI* CAPACITY RATINGS — 580F180-300 UNIT SIZE 580F (Low Heat) 180 210 240 300 UNIT SIZE 580F (High Heat) 180 210 240 300 Bels db EER IPLV wb — — — — — NOMINAL TONS NET COOLING CAPACITY (Btuh) TOTAL WATTS EER 15 18 20 25 176,000 202,000 236,000 278,000 17,064 21,166 24,832 28,535 9.5 9.7 9.5 9.7 NOMINAL TONS NET COOLING CAPACITY (Btuh) TOTAL WATTS EER 15 18 20 25 176,000 202,000 236,000 277,000 17,179 21,301 24,832 29,067 9.5 9.7 9.5 9.
ARI* CAPACITY RATINGS — 581A155,180 LOW HEAT UNITS UNIT 581A NOMINAL TONS 155230 180275 13 15 NET COOLING CAPACITY (Btuh) 134,000 180,000 TOTAL WATTS EER 12,209 17,064 10.60 10.50 SOUND RATING (dB) 88 88 IPLV 11.4 11.4 HIGH HEAT UNITS dB db EER IPLV wb UNIT 581A NOMINAL TONS 155300 180360 13 15 — — — — — NET COOLING CAPACITY (Btuh) 134,000 180,000 TOTAL WATTS EER 12,218 17,179 10.60 10.50 SOUND RATING (dB) 88 88 IPLV 11.4 11.
ARI* CAPACITY RATINGS — 581A210-300 UNIT 581A 210 240 300** db EER IPLV wb — — — — NOMINAL TONS 18 20 25 CFM 5,500 6,000 7,500 NET COOLING CAPACITY (Btuh) 200,000 234,000 278,000 TOTAL kW 18.5 21.7 27.8 EER 10.8 10.8 10.0 SOUND RATING (dB) 81.7 81.7 84.6 IPLV† 12.0 11.9 10.9 3. Ratings are based on: Cooling Standard: 80 F db, 67 F wb indoor entering-air temperature and 95 F db air entering outdoor unit.
OPTIONS AND ACCESSORIES 581B036-150 AND 580F036-151 ITEM 100% Open Two-Position Damper 25% Open Two-Position Damper Condenser Coil Grille Condenser Coil Hail Guard Assembly Convenience Outlet (Load Side) Copper Fins Indoor and Outdoor Coil Copper Fins Outdoor Coil E-Coat Outdoor Coil (Aluminum) E-Coat Outdoor Coil (Copper) EconoMi$er IV with Controller EconoMi$er2 (without controller) Electronic Programmable Thermostat Enthalpy or Differential Enthalpy Sensor Fan/Filter Status Flue Discharge Deflector Flue
OPTIONS AND ACCESSORIES (cont) 579F180-300, 580F180-300, AND 581A155-181 ITEM 25% Open Two-Position Damper Barometric Relief Damper (not for use with Horizontal Adapter Curb) Condenser Coil Hail Guard Assembly (180-240) Convenience Outlet (Load Side) Copper Fins Indoor and Outdoor Coil Copper Fins Outdoor Coil E-Coat Outdoor Coil (Aluminum) E-Coat Outdoor Coil (Copper) EconoMi$er IV with Controller EconoMi$er2 (without Controller) Electronic Programmable Thermostat Enthalpy or Differential Enthalpy Sensor F
OPTIONS AND ACCESSORIES (cont) 581A210-300 ITEM EconoMi$er IV Power Exhaust Barometric Relief Hail Guard Horizontal Kit Return Smoke Detector Supply Smoke Detector Return and Supply Smoke Detector Non-Fused Disconnect Non-Powered Convenience Outlet Outdoor Air Enthalpy Sensor Return Air Enthalpy Sensor Return Air Temperature Sensor Return Air CO2 Sensor Indoor Air Quality (CO2) Room Sensor Hot Gas Reheat Non-Powered Convenience Outlet Pre-Coat Condenser E-Coat Condenser Coil Copper Condenser Coil Copper Eva
OPTIONS AND ACCESSORIES (cont) Two-Position Damper package is available as an accessory. Both 25% or 100% outdoor air dampers are available. Head Pressure Control (Motormaster) accessory package maintains condensing temperature between 90 F and 110 F at outdoor ambient temperatures down to –20 F by condenser-fan speed modulation or condenser-fan cycling and wind baffles. Unit-Mounted, Non-Fused Disconnect Switch provides unit power shutoff.
580F036-151 PHYSICAL DATA — 580F036-073 UNIT SIZE 580F NOMINAL CAPACITY (tons) OPERATING WEIGHT (lb) Unit Al/Al* Al/Cu* Cu/Cu* EconoMi$er IV EconoMi$er2 Roof Curb† COMPRESSOR Type Quantity No. Cylinders (per Circuit) Oil (oz) REFRIGERANT TYPE Expansion Device Operating Charge (lb-oz) Circuit 1 (first stage) Circuit 2 (second stage) CONDENSER FAN Nominal Cfm Quantity...Diameter (in.) Motor Hp...Rpm Watts Input (Total) CONDENSER COIL Rows...Fins/in. Total Face Area (sq ft) EVAPORATOR FAN Quantity...Size (in.
PHYSICAL DATA — 580F036-073 (cont) Liquid Propane Std 074 115 150 060N 090N 120N Alt 074 115 150 Thermostat Heat Anticipator Setting (amps) 208/230 v and 575 Stage 1 Stage 2 460 v Stage 1 Stage 2 Gas Input (Btuh) Standard Units (Stage 1/Stage 2) 074 115 150*** 060N††† 090N††† 120N††† Low NOx Units Efficiency (Steady State) (%) Temperature Rise Range Manifold Pressure (in. wg) Natural Gas Liquid Propane Gas Valve Quantity Gas Valve Pressure Range Psig in. wg Field Gas Connection Size (in.
580F036-151 PHYSICAL DATA — 580F090,120,150 UNITS UNIT SIZE 580F NOMINAL CAPACITY (tons) OPERATING WEIGHT (lb) Unit Al/Al* Al/Cu* Cu/Cu* Economizer EconoMi$er IV Roof Curb† COMPRESSOR Type Quantity No. Cylinders (per Circuit) Oil (oz) REFRIGERANT TYPE Expansion Device Operating Charge (lb-oz) Circuit 1 (first stage) Circuit 2 (second stage) CONDENSER COIL Rows...Fins/in. Total Face Area (sq ft) CONDENSER FAN Nominal Cfm Quantity...Diameter (in.) Motor Hp...Rpm Watts Input (Total) EVAPORATOR COIL Rows...
PHYSICAL DATA — 580F090,120,150 UNITS (cont) Liquid Propane Std Alt Thermostat Heat Anticipator Setting (amps) 208/230 v and 575 Stage 1 Stage 2 460 v Stage 1 Stage 2 Gas Input (Btuh) Stage 1 Stage 2 Efficiency (Steady State) (%) Temperature Rise Range Manifold Pressure (in. wg) Natural Gas Liquid Propane Gas Valve Quantity Gas Valve Pressure Range Psig in. wg Field Gas Connection Size (in.) HIGH-PRESSURE SWITCH (psig) Standard Compressor Internal Relief (Differential) Cutout Reset (Auto.
580F036-151 PHYSICAL DATA — 580F091,103,121,151 UNITS ASHRAE 90.1 COMPLIANT UNITS UNIT SIZE 580F NOMINAL CAPACITY (tons) OPERATING WEIGHT (lb) Unit Al/Al* Al/Cu* Cu/Cu* EconoMi$er IV EconoMi$er2 Roof Curb† COMPRESSOR Type Quantity No. Cylinders (per Circuit) Oil (oz) (each compressor) REFRIGERANT TYPE Expansion Device Operating Charge (lb-oz) Circuit 1 (first stage) Circuit 2 (second stage) CONDENSER FAN Nominal Cfm Quantity...Diameter (in.) Motor Hp...Rpm Watts Input (Total) CONDENSER COIL Rows...Fins/in.
PHYSICAL DATA — 580F091,103,121,151 UNITS (cont) UNIT SIZE 580F FURNACE SECTION Rollout Switch Cutout Temp (F)** Burner Orifice Diameter (in. ...drill size) Natural Gas Liquid Propane Std Alt Thermostat Heat Anticipator Setting (amps) 208/230 v and 575 Stage 1 Stage 2 460 v Stage 1 Stage 2 Gas Input (Btuh) Stage 1 Stage 2 Efficiency (Steady State) (%) Temperature Rise Range Manifold Pressure (in. wg) Natural Gas Liquid Propane Gas Valve Quantity Gas Valve Pressure Range Psig in.
580F036-151 BASE UNIT DIMENSIONS — 580F036-072 a48-8195 26
BASE UNIT DIMENSIONS — 580F073 580F036-151 a48-8196 27
580F036-151 BASE UNIT DIMENSIONS — 580F090,120,150 a48-8197 28
BASE UNIT DIMENSIONS — 580F091,103,121,151 580F036-151 a48-8198 29
580F036-151 ACCESSORY DIMENSIONS — 580F ROOF CURB ACCESSORY CRRFCURB001A01 CRRFCURB002A01 A UNIT SIZE B C 1′ -2″ [356] 2′ -0″ [610] CONNECTOR PKG. ACCY. D ALT DRAIN HOLE 580F 036-073 CRBTMPWR001A01 CRBTMPWR002A01 CRBTMPWR003A01 CRBTMPWR004A01 1′ -911/16″ [551] 1′ -4″ [406] 13/4″ [44.5] GAS 3/ ″ 4 [19] NPT 2″ [12.7] NPT 3/ ″ [19] NPT 4 1/ POWER CONTROL ACCESSORY POWER 3/ ″ [19] NPT 4 11/4″ [31.7] 3/ ″ [19] NPT 4 11/4″ [31.7] 1/ ″ 2 [12.7] NPT 1/ ″ 2 [12.7] NPT NOTES: 1.
ACCESSORY DIMENSIONS — 580F (cont) B C D ALT DRAIN HOLE CRBTMPWR001A01 CRBTMPWR002A01 CRBTMPWR003A01 CRBTMPWR004A01 2′ -87/ 16″ [827] 1′ -1015/ 16″ [583] GAS 3/ ″ 4 [19] NPT 13/4″ [44.5] 1/ ″ 2 [12.7] NPT 3/ ″ 4 [19] NPT POWER CONTROL ACCESSORY POWER 4″ [19] NPT 11/4″ [31.7] 3/ 3/ 4″ 1/ ″ 2 [19] NPT [12.7] NPT 11/4″ [31.7] 1/ ″ 2 [12.7] NPT ROOF CURB ACCESSORY CRRFCURB003A01 CRRFCURB004A01 “A” UNIT SIZE 1′ -2″ [356] 2′ -0″ [610] 580F 090-151 NOTES: 1.
580F036-151 SELECTION PROCEDURE (with 580F060 example) IV DETERMINE FAN SPEED AND POWER REQUIREMENTS AT DESIGN CONDITIONS. Before entering the Fan Performance tables, calculate the total static pressure required based on unit components. From the given and the Accessory/FIOP Static Pressure table on page 70 find: External static pressure 0.60 in. wg EconoMi$er IV static pressure 0.12 in. wg Total Static 0.72 in.
PERFORMANCE DATA 580F048 (4 TONS) 580F036 (3 TONS) Temp (F) Air Entering Condenser (Edb) 75 85 95 105 115 72 42.8 20.0 2.91 40.8 19.4 3.14 38.7 18.6 3.35 36.5 17.8 3.55 34.3 17.0 3.76 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW Air Entering Evaporator — Cfm/BF 900/0.11 1200/0.14 1500/0.17 Air Entering Evaporator — Ewb (F) 67 62 72 67 62 72 67 62 38.9 35.0 44.8 40.8 37.0 45.8 41.9 38.2 24.5 28.7 21.8 27.5 32.8 23.0 30.0 36.0 2.81 2.70 2.99 2.88 2.78 3.02 2.92 2.82 36.9 33.3 42.5 38.7 35.0 43.
580F036-151 PERFORMANCE DATA (cont) COOLING CAPACITIES (cont) 580F090 (71/2 TONS) Temp (F) Air Entering Condenser (Edb) 75 85 95 105 115 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 72 105.8 52.6 7.28 101.8 51.6 7.82 97.0 50.2 8.36 91.0 48.2 8.80 85.2 46.4 9.30 Air Entering Evaporator — Cfm/BF 2800/0.09 3000/0.10 Air Entering Evaporator — Ewb (F) 67 62 72 67 98.2 90.0 106.4 99.0 67.8 81.6 53.6 69.8 6.98 6.68 7.32 7.04 93.6 85.2 102.6 94.4 66.4 79.6 52.8 68.6 7.50 7.18 7.86 7.54 88.4 80.0 97.
PERFORMANCE DATA (cont) 580F120 (10 TONS) Temp (F) Air Entering Condenser (Edb) 72 135.8 66.8 9.76 130.0 64.3 10.41 124.1 62.2 11.13 118.1 60.4 11.93 115.0 59.4 12.26 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 75 85 95 105 115 62 112.0 97.4 9.10 104.0 93.8 9.74 96.7 90.0 10.40 87.9 85.2 11.10 84.2 83.4 11.40 Air Entering Evaporator — Cfm/BF 4000/0.125 Air Entering Evaporator — Ewb (F) 72 67 62 142.4 130.6 119.8 73.2 93.4 112.7 10.00 9.61 9.27 136.0 125.0 114.5 71.1 91.7 110.2 10.67 10.28 9.
580F036-151 PERFORMANCE DATA (cont) COOLING CAPACITIES (cont) 580F151 (121/2 TONS) Temp (F) Air Entering Condenser (Edb) TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 75 85 95 105 115 125 3750/0.08 72 164.6 81.3 10.24 159.9 79.7 11.38 154.2 77.9 12.59 147.8 75.4 13.84 139.7 72.5 15.03 130.5 69.8 16.32 67 152.0 101.9 9.96 147.1 99.9 11.05 141.5 98.0 12.26 134.2 95.2 13.48 120.4 89.8 14.70 107.0 84.4 15.91 62 139.9 121.7 9.71 133.6 119.1 10.82 124.4 114.8 11.95 114.0 109.5 13.12 102.8 102.
PERFORMANCE DATA (cont) 580F036 (3 TONS) — STANDARD MOTOR (DIRECT DRIVE) Low Speed Airflow 208 V (Cfm) ESP Bhp Watts ESP 900 0.49 0.21 253 0.50 1000 0.42 0.23 270 0.43 1100 0.37 0.24 287 0.38 1200 0.33 0.26 304 0.33 1300 0.27 0.27 321 0.28 1400 0.20 0.29 338 0.23 1500 0.16 0.30 355 0.18 Bhp ESP — — High Speed 230, 460, 575 V Bhp Watts 0.23 277 0.25 292 0.26 307 0.27 323 0.29 338 0.30 354 0.31 369 LEGEND Brake Horsepower Input to Fan External Static Pressure (in. wg) ESP 0.51 0.43 0.39 0.34 0.28 0.25 0.
580F036-151 PERFORMANCE DATA (cont) FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 580F048 (4 TONS) — STANDARD MOTOR (DIRECT DRIVE) Low Speed Airflow 208 V (Cfm) ESP Bhp Watts ESP 1200 0.68 0.41 458 0.74 1300 0.61 0.42 471 0.67 1400 0.53 0.45 503 0.59 1500 0.45 0.47 536 0.51 1600 0.36 0.49 557 0.42 1700 0.26 0.52 584 0.32 1800 0.15 0.54 610 0.22 1900 0.04 0.56 629 0.11 2000 — — — — High Speed 230, 460, 575 V Bhp Watts 0.45 506 0.46 521 0.49 556 0.52 593 0.54 616 0.57 646 0.60 674 0.
PERFORMANCE DATA (cont) 580F060 (5 TONS) — STANDARD MOTOR (DIRECT DRIVE) Low Speed Airflow 208 V 230,460,575 V (Cfm) ESP Bhp Watts ESP Bhp Watts 1500 0.69 0.67 750 1.01 0.71 791 1600 0.49 0.70 780 0.85 0.74 824 1700 0.29 0.73 810 0.70 0.77 857 1800 0.09 0.75 839 0.54 0.80 891 1900 — — — 0.39 0.83 924 2000 — — — 0.23 0.86 957 2100 — — — 0.08 0.89 990 2200 — — — — — — 2300 — — — — — — 2400 — — — — — — 2500 — — — — — — Bhp ESP ESP 1.00 0.85 0.70 0.55 0.40 0.25 0.10 — — — — 208 V Bhp 0.70 0.74 0.77 0.81 0.
580F036-151 PERFORMANCE DATA (cont) FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 580F060 (5 TONS) — THREE-PHASE, ALTERNATE MOTOR (BELT DRIVE)* External Static Pressure (in. wg) Airflow 0.2 0.4 0.6 (Cfm) Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm 1500 802 0.42 370 912 0.55 489 1006 0.70 624 1088 1600 840 0.49 432 947 0.63 557 1038 0.78 696 1119 1700 878 0.57 502 982 0.71 632 1071 0.87 776 1151 1800 917 0.65 581 1017 0.81 716 1105 0.97 864 1183 1900 956 0.75 668 1053 0.91 808 1139 1.
PERFORMANCE DATA (cont) 580F072,073 (6 TONS) — STANDARD MOTOR (BELT DRIVE)* Airflow (Cfm) 1800 1900 2000 2100 2200 2300 2400 2500 2600 2700 2800 2900 3000 Rpm 967 1007 1048 1090 1131 1173 1215 1258 1300 1343 1386 1429 — 0.2 Bhp 0.65 0.75 0.85 0.97 1.09 1.23 1.38 1.54 1.71 1.90 2.09 2.31 — Watts 579 663 757 859 970 1091 1223 1365 1518 1683 1860 2050 — Rpm 1077 1115 1153 1191 1230 1269 1309 1349 1389 1430 1471 — — 0.4 Bhp 0.81 0.91 1.03 1.15 1.29 1.43 1.59 1.76 1.94 2.14 2.
580F036-151 PERFORMANCE DATA (cont) FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 580F090,091 (71/2 TONS) — STANDARD MOTOR (BELT DRIVE)* Airflow (Cfm) 2250 2300 2400 2500 2550 2600 2700 2800 2900 3000 3100 3200 3300 3400 3500 3600 3700 3750 Rpm 513 521 535 551 558 566 582 597 613 629 645 662 678 694 711 727 744 752 0.2 Bhp 0.54 0.57 0.63 0.69 0.72 0.76 0.83 0.90 0.98 1.07 1.16 1.26 1.36 1.47 1.59 1.71 1.84 1.
PERFORMANCE DATA (cont) 580F090,091 (71/2 TONS) — ALTERNATE MOTOR (BELT DRIVE)* Airflow (Cfm) 2250 2300 2400 2500 2550 2600 2700 2800 2900 3000 3100 3200 3300 3400 3500 3600 3700 3750 Rpm 513 521 535 551 558 566 582 597 613 629 645 662 678 694 711 727 744 752 0.2 Bhp 0.54 0.57 0.63 0.69 0.72 0.76 0.83 0.90 0.98 1.07 1.16 1.26 1.36 1.47 1.59 1.71 1.84 1.
580F036-151 PERFORMANCE DATA (cont) FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 580F090,091 (71/2 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* Airflow (Cfm) 2250 2300 2400 2500 2550 2600 2700 2800 2900 3000 3100 3200 3300 3400 3500 3600 3700 3750 Rpm 513 521 535 551 558 566 582 597 613 629 645 662 678 694 711 727 744 752 0.2 Bhp 0.54 0.57 0.63 0.69 0.72 0.76 0.83 0.90 0.98 1.07 1.16 1.26 1.36 1.47 1.59 1.71 1.84 1.
PERFORMANCE DATA (cont) 580F103 (81/2 TONS) — STANDARD MOTOR (BELT DRIVE)* Airflow (Cfm) 2550 2600 2700 2800 2900 3000 3100 3200 3300 3400 3500 3600 3700 3750 3800 3900 4000 4100 4200 4250 Rpm 558 566 582 597 613 629 645 662 678 694 711 727 744 752 761 777 794 — — — 0.2 Bhp 0.72 0.76 0.83 0.90 0.98 1.07 1.16 1.26 1.36 1.47 1.59 1.71 1.84 1.91 1.98 2.12 2.
580F036-151 PERFORMANCE DATA (cont) FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 580F103 (81/2 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* Airflow (Cfm) 2550 2600 2700 2800 2900 3000 3100 3200 3300 3400 3500 3600 3700 3750 3800 3900 4000 4100 4200 4250 Rpm 558 566 582 597 613 629 645 662 678 694 711 727 744 752 761 777 794 811 828 837 0.2 Bhp 0.72 0.76 0.83 0.90 0.98 1.07 1.16 1.26 1.36 1.47 1.59 1.71 1.84 1.91 1.98 2.12 2.27 2.42 2.59 2.
PERFORMANCE DATA (cont) 580F120 (10 TONS) — STANDARD MOTOR (BELT DRIVE)* Airflow (Cfm) 3000 3100 3200 3300 3400 3500 3600 3700 3800 3900 4000 4100 4200 4300 4400 4500 4600 4700 4800 4900 5000 Rpm 726 746 766 786 806 826 846 866 886 907 927 948 968 989 1009 1030 1051 — — — — 0.2 Bhp 0.75 0.81 0.88 0.95 1.03 1.11 1.20 1.29 1.38 1.48 1.58 1.69 1.81 1.93 2.06 2.19 2.
580F036-151 PERFORMANCE DATA (cont) FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 580F120 (10 TONS) — ALTERNATE MOTOR (BELT DRIVE)* Airflow (Cfm) 3000 3100 3200 3300 3400 3500 3600 3700 3800 3900 4000 4100 4200 4300 4400 4500 4600 4700 4800 4900 5000 Rpm 726 746 766 786 806 826 846 866 886 907 927 948 968 989 1009 1030 1051 1071 1092 1113 — 0.2 Bhp 0.75 0.81 0.88 0.95 1.03 1.11 1.20 1.29 1.38 1.48 1.58 1.69 1.81 1.93 2.06 2.19 2.32 2.47 2.62 2.
PERFORMANCE DATA (cont) 580F120 (10 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* External Static Pressure (in. wg) 0.6 Watts Rpm Bhp Watts Rpm 822 853 1.14 997 910 883 870 1.21 1062 926 947 887 1.29 1131 942 1016 905 1.37 1204 958 1088 922 1.46 1280 975 1163 940 1.55 1360 991 1243 958 1.65 1444 1008 1327 975 1.75 1532 1025 1415 994 1.85 1625 1043 1507 1012 1.96 1722 1060 1603 1030 2.08 1823 1078 1704 1049 2.20 1928 1095 1809 1067 2.32 2038 1113 1920 1086 2.45 2153 1131 2034 1105 2.59 2272 1149 2154 1124 2.
580F036-151 PERFORMANCE DATA (cont) FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 580F121 (10 TONS) — STANDARD MOTOR (BELT DRIVE)* Airflow (Cfm) 3000 3100 3200 3300 3400 3500 3600 3700 3800 3900 4000 4100 4200 4300 4400 4500 4600 4700 4800 4900 5000 Rpm 592 607 623 638 653 669 685 700 716 732 748 764 780 796 812 828 — — — — — 0.2 Bhp 0.77 0.83 0.90 0.98 1.06 1.15 1.23 1.33 1.43 1.53 1.64 1.76 1.88 2.00 2.13 2.
PERFORMANCE DATA (cont) 580F121 (10 TONS) — ALTERNATE MOTOR (BELT DRIVE)* Airflow (Cfm) 3000 3100 3200 3300 3400 3500 3600 3700 3800 3900 4000 4100 4200 4300 4400 4500 4600 4700 4800 4900 5000 Rpm 592 607 623 638 653 669 685 700 716 732 748 764 780 796 812 828 845 861 877 894 — 0.2 Bhp 0.77 0.83 0.90 0.98 1.06 1.15 1.23 1.33 1.43 1.53 1.64 1.76 1.88 2.00 2.13 2.27 2.42 2.57 2.72 2.
580F036-151 PERFORMANCE DATA (cont) FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 580F121 (10 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* External Static Pressure (in. wg) 0.6 Watts Rpm Bhp Watts Rpm 817 719 1.10 961 775 881 731 1.17 1030 787 949 744 1.26 1103 798 1020 757 1.34 1179 810 1095 770 1.44 1260 822 1175 783 1.53 1344 835 1258 796 1.63 1432 847 1346 810 1.74 1524 860 1438 823 1.85 1621 873 1534 837 1.96 1722 886 1635 851 2.08 1828 899 1741 865 2.21 1939 912 1851 879 2.34 2054 925 1966 894 2.
PERFORMANCE DATA (cont) 580F150,151 (121/2 TONS) — STANDARD MOTOR (BELT DRIVE)* Airflow (Cfm) 3700 3800 3900 4000 4100 4200 4300 4400 4500 4600 4700 4800 4900 5000 5100 5200 5300 5400 5500 5600 5700 5800 5900 6000 6100 6200 6300 Rpm 728 744 760 777 793 810 826 843 860 876 893 910 927 944 961 978 995 — — — — — — — — — — 0.2 Bhp 1.36 1.46 1.57 1.68 1.79 1.92 2.04 2.18 2.32 2.46 2.62 2.77 2.94 3.11 3.29 3.48 3.
580F036-151 PERFORMANCE DATA (cont) FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 580F150,151 (121/2 TONS) — ALTERNATE MOTOR (BELT DRIVE)* Airflow (Cfm) 3700 3800 3900 4000 4100 4200 4300 4400 4500 4600 4700 4800 4900 5000 5100 5200 5300 5400 5500 5600 5700 5800 5900 6000 6100 6200 6300 Rpm 728 744 760 777 793 810 826 843 860 876 893 910 927 944 961 978 995 1012 1029 1046 1063 1080 1098 1115 — — — 0.2 Bhp 1.36 1.46 1.57 1.68 1.79 1.92 2.04 2.18 2.32 2.46 2.62 2.77 2.94 3.11 3.29 3.48 3.67 3.87 4.
PERFORMANCE DATA (cont) 580F036 (3 TONS) — STANDARD MOTOR (DIRECT DRIVE) Low Speed Airflow 208 V (Cfm) ESP Bhp Watts ESP 900 0.54 0.21 253 0.57 1000 0.49 0.23 270 0.51 1100 0.43 0.24 287 0.45 1200 0.39 0.26 304 0.40 1300 0.33 0.27 321 0.35 1400 0.26 0.29 338 0.28 1500 0.21 0.30 355 0.23 Bhp ESP — — High Speed 230, 460, 575 V Bhp Watts 0.23 277 0.25 292 0.26 307 0.27 323 0.29 338 0.30 354 0.31 369 LEGEND Brake Horsepower Input to Fan External Static Pressure (in. wg) ESP 0.55 0.52 0.46 0.38 0.35 0.29 0.
580F036-151 PERFORMANCE DATA (cont) FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 580F048 (4 TONS) — STANDARD MOTOR (DIRECT DRIVE) Low Speed Airflow 208 V (Cfm) ESP Bhp Watts ESP 1200 0.75 0.41 458 0.81 1300 0.68 0.42 471 0.74 1400 0.60 0.45 503 0.66 1500 0.51 0.47 536 0.58 1600 0.42 0.49 557 0.49 1700 0.32 0.52 584 0.39 1800 0.21 0.54 610 0.29 1900 0.09 0.56 629 0.18 2000 — — — 0.06 Bhp ESP — — High Speed 230, 460, 575 V Bhp Watts 0.45 506 0.46 521 0.49 556 0.52 593 0.54 616 0.57 646 0.60 674 0.
PERFORMANCE DATA (cont) 580F060 (5 TONS) — STANDARD MOTOR (DIRECT DRIVE) Low Speed Airflow 208V 230, 460, 575 V (Cfm) ESP Bhp Watts ESP Bhp Watts 1500 0.74 0.67 750 1.06 0.71 791 1600 0.54 0.70 780 0.90 0.74 824 1700 0.34 0.73 810 0.75 0.77 857 1800 0.14 0.75 839 0.59 0.80 891 1900 — — — 0.44 0.83 924 2000 — — — 0.28 0.86 957 2100 — — — 0.13 0.89 990 2200 — — — — — — 2300 — — — — — — 2400 — — — — — — 2500 — — — — — — Bhp ESP — — ESP 1.07 0.92 0.77 0.62 0.47 0.32 0.17 0.02 — — — 208 V Bhp 0.70 0.74 0.
0F036-151 PERFORMANCE DATA (cont) FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 580F060 (5 TONS) — THREE-PHASE, ALTERNATE MOTOR (BELT DRIVE)* External Static Pressure (in. wg) Airflow 0.2 0.4 0.6 (Cfm) Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm 1500 790 0.40 353 896 0.53 470 990 0.67 599 1074 1600 828 0.46 413 930 0.60 535 1021 0.75 669 1103 1700 866 0.54 479 964 0.68 607 1053 0.84 746 1133 1800 905 0.62 553 1000 0.77 687 1085 0.94 831 1164 1900 944 0.71 635 1036 0.87 775 1119 1.
PERFORMANCE DATA (cont) 580F072,073 (6 TONS) — STANDARD MOTOR (BELT DRIVE)* Airflow (Cfm) 1800 1900 2000 2100 2200 2300 2400 2500 2600 2700 2800 2900 3000 Rpm 919 960 1001 1043 1085 1127 1169 1212 1255 1298 1341 1384 — 0.2 Bhp 0.63 0.73 0.84 0.96 1.09 1.23 1.38 1.55 1.73 1.93 2.14 2.36 — Watts 561 648 744 850 966 1092 1229 1378 1539 1713 1899 2099 — Rpm 1010 1047 1085 1123 1162 1201 1241 1281 1322 1363 1404 — — 0.4 Bhp 0.75 0.85 0.96 1.09 1.22 1.37 1.53 1.70 1.89 2.09 2.
580F036-151 PERFORMANCE DATA (cont) FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 580F090,091 (71/2 TONS) — STANDARD MOTOR (BELT DRIVE)* Airflow (Cfm) 2250 2300 2400 2500 2550 2600 2700 2800 2900 3000 3100 3200 3300 3400 3500 3600 3700 3750 Rpm 505 513 527 543 550 558 574 589 605 621 637 654 670 686 703 720 736 745 0.2 Bhp 0.52 0.55 0.60 0.66 0.69 0.73 0.80 0.87 0.95 1.03 1.12 1.22 1.32 1.42 1.54 1.66 1.78 1.
PERFORMANCE DATA (cont) 580F090,091 (71/2 TONS) — ALTERNATE MOTOR (BELT DRIVE)* Airflow (Cfm) 2250 2300 2400 2500 2550 2600 2700 2800 2900 3000 3100 3200 3300 3400 3500 3600 3700 3750 Rpm 505 513 527 543 550 558 574 589 605 621 637 654 670 686 703 720 736 745 0.2 Bhp 0.52 0.55 0.60 0.66 0.69 0.73 0.80 0.87 0.95 1.03 1.12 1.22 1.32 1.42 1.54 1.66 1.78 1.
580F036-151 PERFORMANCE DATA (cont) FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 580F090,091 (71/2 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* Airflow (Cfm) 2250 2300 2400 2500 2550 2600 2700 2800 2900 3000 3100 3200 3300 3400 3500 3600 3700 3750 Rpm 505 513 527 543 550 558 574 589 605 621 637 654 670 686 703 720 736 745 0.2 Bhp 0.52 0.55 0.60 0.66 0.69 0.73 0.80 0.87 0.95 1.03 1.12 1.22 1.32 1.42 1.54 1.66 1.78 1.
PERFORMANCE DATA (cont) 580F103 (81/2 TONS) — STANDARD MOTOR (BELT DRIVE)* Airflow (Cfm) 2550 2600 2700 2800 2900 3000 3100 3200 3300 3400 3500 3600 3700 3750 3800 3900 4000 4100 4200 4250 Rpm 550 558 574 589 605 621 637 654 670 686 703 720 736 745 753 770 787 804 — — 0.2 Bhp 0.69 0.73 0.80 0.87 0.95 1.03 1.12 1.22 1.32 1.42 1.54 1.66 1.78 1.85 1.91 2.05 2.20 2.
580F036-151 PERFORMANCE DATA (cont) FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 580F103 (81/2 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* Airflow (Cfm) 2550 2600 2700 2800 2900 3000 3100 3200 3300 3400 3500 3600 3700 3750 3800 3900 4000 4100 4200 4250 Rpm 550 558 574 589 605 621 637 654 670 686 703 720 736 745 753 770 787 804 821 829 0.2 Bhp 0.69 0.73 0.80 0.87 0.95 1.03 1.12 1.22 1.32 1.42 1.54 1.66 1.78 1.85 1.91 2.05 2.20 2.35 2.51 2.
PERFORMANCE DATA (cont) 580F120,121 (10 TONS) — STANDARD MOTOR (BELT DRIVE)* External Static Pressure (in. wg) 0.6 Watts Rpm Bhp Watts Rpm 765 696 1.03 904 757 825 706 1.10 968 766 888 717 1.18 1035 776 955 728 1.26 1106 786 1026 739 1.35 1181 797 1100 750 1.43 1259 807 1179 762 1.53 1341 817 1261 773 1.63 1428 828 1347 785 1.73 1518 839 1438 797 1.84 1613 850 1533 809 1.95 1712 861 1632 821 2.07 1816 873 1736 833 2.19 1924 — 1845 846 2.
580F036-151 PERFORMANCE DATA (cont) FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 580F120,121 (10 TONS) — ALTERNATE MOTOR (BELT DRIVE)* External Static Pressure (in. wg) 0.6 Watts Rpm Bhp Watts Rpm 765 696 1.03 904 757 825 706 1.10 968 766 888 717 1.18 1035 776 955 728 1.26 1106 786 1026 739 1.35 1181 797 1100 750 1.43 1259 807 1179 762 1.53 1341 817 1261 773 1.63 1428 828 1347 785 1.73 1518 839 1438 797 1.84 1613 850 1533 809 1.95 1712 861 1632 821 2.07 1816 873 1736 833 2.19 1924 884 1845 846 2.
PERFORMANCE DATA (cont) 580F120,121 (10 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* External Static Pressure (in. wg) 0.6 Watts Rpm Bhp Watts Rpm 765 696 1.03 904 757 825 706 1.10 968 766 888 717 1.18 1035 776 955 728 1.26 1106 786 1026 739 1.35 1181 797 1100 750 1.43 1259 807 1179 762 1.53 1341 817 1261 773 1.63 1428 828 1347 785 1.73 1518 839 1438 797 1.84 1613 850 1533 809 1.95 1712 861 1632 821 2.07 1816 873 1736 833 2.19 1924 884 1845 846 2.32 2037 896 1958 858 2.45 2154 908 2077 871 2.
580F036-151 PERFORMANCE DATA (cont) FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 580F150,151 (121/2 TONS) — STANDARD MOTOR (BELT DRIVE)* Airflow (Cfm) 3700 3800 3900 4000 4100 4200 4300 4400 4500 4600 4700 4800 4900 5000 5100 5200 5300 5400 5500 5600 5700 5800 5900 6000 6100 6200 6300 Rpm 676 690 705 719 734 748 763 778 792 807 822 837 852 867 882 897 912 927 943 958 — — — — — — — 0.2 Bhp 1.19 1.27 1.36 1.45 1.55 1.66 1.76 1.88 1.99 2.12 2.25 2.38 2.52 2.66 2.81 2.97 3.13 3.30 3.47 3.
PERFORMANCE DATA (cont) 580F150,151 (121/2 TONS) — ALTERNATE MOTOR (BELT DRIVE)* AIRFLOW (Cfm) 3700 3800 3900 4000 4100 4200 4300 4400 4500 4600 4700 4800 4900 5000 5100 5200 5300 5400 5500 5600 5700 5800 5900 6000 6100 6200 6300 Rpm 676 690 705 719 734 748 763 778 792 807 822 837 852 867 882 897 912 927 943 958 973 988 1004 1019 1034 1050 1065 0.2 Bhp 1.19 1.27 1.36 1.45 1.55 1.66 1.76 1.88 1.99 2.12 2.25 2.38 2.52 2.66 2.81 2.97 3.13 3.30 3.47 3.65 3.83 4.03 4.22 4.43 4.64 4.86 5.
580F036-151 PERFORMANCE DATA (cont) GENERAL NOTES FOR FAN PERFORMANCE DATA TABLES 1. Values include losses for filters, unit casing, and wet coils. See this page for accessory/FIOP static pressure information. 2. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
PERFORMANCE DATA (cont) UNIT 580F 0 1045 1455 1175 1455 1300 1685 1460 1685 036† 036** 048† 048** 060† 060** 072,073†† 072,073** 1/ 2 1 973 1392 1094 1392 1233 1608 1382 1608 1009 1423 1135 1423 1266 1647 1421 1647 11/2 937 1360 1054 1360 1200 1570 1343 1570 2 901 1328 1013 1328 1166 1531 1304 1531 MOTOR PULLEY TURNS OPEN 21/2 3 31/2 865 829 793 1297 1265 1233 973 932 892 1297 1265 1233 1133 1100 1066 1493 1454 1416 1265 1226 1187 1493 1454 1416 *Approximate fan rpm shown.
2500 5000 2000 3000 3-6 Ton 2000 7.5-12.5 Ton FLOW (cfm) FLOW (cfm) 4000 1000 1500 1000 500 0 0 0.1 0.2 0.3 0.4 0.5 0 a48-6308 STATIC PRESSURE (in. wg) 0 VERTICAL POWER EXHAUST PERFORMANCE 0.1 0.2 0.3 0.4 STATIC PRESSURE (in. wg) 0.5 a48-6309 2500 2500 Flow in cubic feet per minute (cfm) FLOW IN CUBIC FEET PER MINUTE (cfm) HORIZONTAL POWER EXHAUST PERFORMANCE 2000 3-6 Ton 1500 7 1/2 - 12 1/2 Ton 1000 500 0 0.15 0.05 0.25 a48-6202 STATIC PRESSURE (in.
PERFORMANCE DATA (cont) UNIT 580F EVAPORATOR-FAN MOTOR Standard 036 Alternate High Static Standard 048 Alternate High Static Standard 060 Alternate High Static Standard 072,073 High Static Standard, Alternate 090,091 High Static Standard 103 High Static Standard 120,121 Alternate High Static Standard 150, 151 Alternate UNIT VOLTAGE 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460
580F036-151 PERFORMANCE DATA (cont) POWER EXHAUST OPTIONS POWER EXHAUST PART NO. CRPWREXH030A01 CRPWREXH021A01 CRPWREXH022A01 CRPWREXH023A01 VERTICAL — MOUNTED IN ECONOMIZER HOOD APPLICATION USAGE Power Exhaust System (208/230-1-60) 036-073 Power Exhaust System (460-3-60) 036-073 Power Exhaust System (208/230-1-60) 090-151 Power Exhaust System (460-3-60) 090-151 POWER OUTPUT (Hp per fan) 0.23 0.24 0.47 0.37 NO. FANS 2 2 2 2 POWER EXHAUST PART NO.
ELECTRICAL DATA NOMINAL V-PH-Hz IFM TYPE STD 208/230-1-60 ALT STD 208/230-3-60 ALT HIGH 036 (3 Ton) STD 460-3-60 ALT HIGH ALT 575-3-60 HIGH STD 208/230-1-60 ALT STD 208/230-3-60 ALT HIGH 048 (4 Ton) STD 460-3-60 ALT HIGH ALT 575-3-60 HIGH CONV OUTLET NO YES NO YES NO YES NO YES NO YES NO YES NO YES NO YES NO YES NO YES NO YES NO YES NO YES NO YES NO YES NO YES NO YES NO YES NO YES NO YES VOLTAGE RANGE COMPRESSOR (each) Max Qty RLA LRA Qty FLA 187 254 1 16.2 96 1 1.
580F036-151 ELECTRICAL DATA (cont) UNIT SIZE 580F NOMINAL V-PH-Hz IFM TYPE STD 208/230-1-60 ALT STD 208/230-3-60 ALT HIGH 060 (5 Ton) STD 460-3-60 ALT HIGH ALT 575-3-60 HIGH STD 208/230-3-60 HIGH 072 (6 Ton) STD 460-3-60 HIGH STD 575-3-60 HIGH STD 208/230-3-60 HIGH 073 (6 Ton) STD 460-3-60 HIGH STD 575-3-60 HIGH STD 208/230-3-60 ALT HIGH STD 090 (71/2 Ton) 460-3-60 ALT HIGH STD 575-3-60 ALT HIGH STD 208/230-3-60 ALT HIGH STD 091 (71/2 Ton) 460-3-60 ALT HIGH STD 575-3-60 ALT HIGH C
ELECTRICAL DATA (cont) NOMINAL V-PH-Hz IFM TYPE STD 208/230-3-60 HIGH 103 (81/2 Ton) STD 460-3-60 HIGH STD 575-3-60 HIGH STD 208/230-3-60 ALT HIGH STD 120 (10 Ton) 460-3-60 ALT HIGH STD 575-3-60 ALT HIGH STD 208/230-3-60 ALT HIGH STD 121 (10 Ton) 460-3-60 ALT HIGH STD 575-3-60 ALT HIGH CONV OUTLET NO YES NO YES NO YES NO YES NO YES NO YES NO YES NO YES NO YES NO YES NO YES NO YES NO YES NO YES NO YES NO YES NO YES NO YES NO YES NO YES NO YES NO YES NO YES NO YES VOLTAGE RANGE COMPRESSOR
580F036-151 ELECTRICAL DATA (cont) UNIT SIZE 580F NOMINAL V-PH-Hz IFM TYPE STD 208/230-3-60 HIGH 150 (121/2 Ton) STD 460-3-60 HIGH STD 575-3-60 HIGH STD 208/230-3-60 HIGH 151 (121/2 Ton) STD 460-3-60 HIGH STD 575-3-60 HIGH CONV OUTLET NO YES NO YES NO YES NO YES NO YES NO YES NO YES NO YES NO YES NO YES NO YES NO YES VOLTAGE RANGE COMPRESSOR (each) Max Qty RLA LRA Qty FLA 187 254 2 23 146 2 1.4 — — — — — — — — — COMBUSTION FAN MOTOR FLA IFM FLA 10.6 0.6 15.0 4.8 414 508 2 10.
CIRCUIT BREAKER VOLTS CB 24 V CB1 (150,151 Std) 460-3-60 MFG. PT. NO. POTTER & BRUMFIELD W2BX-1024-3.2 Heinemann Airpax CF3-Z228-41 219-3-2600-486 580F036-151 TYPICAL WIRING SCHEMATICS — 580F036-151 (580F090, 460-3-60 Shown) MUST TRIP AMPS 3.2 8.
580F036-151 TYPICAL WIRING SCHEMATICS — 580F036-151 (cont) a48-7910 IAQ LA POT OAT RAT — — — — — LEGEND Indoor Air Quality Low Ambient Lockout Device Potentiometer Outdoor-Air Temperature Return-Air Temperature NOTE: Potentiometer Defaults Settings: Power Exhaust Middle Minimum Pos. Fully Closed DCV Max. Middle DCV Set Middle Enthalpy C Setting ECONOMIZER NOTES: 1. 620 ohm, 1 watt 5% resister should be removed only when using differential enthalpy or dry bulb. 2.
TYPICAL WIRING SCHEMATICS — 580F (cont) C2 FOR 008-014 UNITS RED YEL BLU LINE SIDE GRA C H3 H1 H2 H4 TRAN4 BLU GRA 11 21 RED YEL 13 23 23 240V X4 X2 X1 X3 RED SECONDARY 120V H1 YEL BLU H3 H2 X2 X3 GRA 208-230-1 ONLY H4 TRAN4 RED GRA X4 600V H2 H1 X1 BLK WHT SECONDARY 120V TRAN4 X4 X2 GROUND FAULT INTERRUPTER CONVENIENCE OUTLET GFI - CO X1 X3 GRN-YEL GRN-YEL SECONDARY 120V SWITCH BLK FUSE TEST RESET a48-7462 15 AMP Convenience Outlet (Optional) — Sizes 580
580F036-151 TYPICAL PIPING AND WIRING — 580F036-151 48-983 Vertical Discharge Ducting NO.1 CONVENIENCE OUTLET a48-6307 NO.
PHYSICAL DATA — 581B036-072 036 3 048 4 060 5 072 6 530 580 576 548 50 30 115 540 590 586 558 50 30 115 560 610 606 578 50 30 115 635 685 681 653 50 30 115 1 42 1 53 1 50 1 60 5-8 9-0 10-2 15-8 10- 0 17-0 12-8 21-0 Scroll R-22 1...22 3500 1/ ...825 4 180 1...17 14.6 Propeller 1...22 1...22 3500 4100 1/ ...825 1/ ...1100 4 4 180 320 3/ -in. OD Enhanced Copper Tubes, Aluminum Lanced Fins 8 2...17 16.5 2...17 16.5 1...22 4100 1/ ...1100 4 320 2...17 16.5 1...17 1...17 1...17 1...17 3.
PHYSICAL DATA — 581B036-072 (cont) UNIT SIZE 581B FURNACE SECTION Rollout Switch Cutout Temp (F)† Burner Orifice Diameter (in. ...
PHYSICAL DATA — 581B090-150 UNIT SIZE 581B NOMINAL CAPACITY (tons) 102 81/2 120 10 150 121/2 870 945 941 899 143 1015 1077 1072 1044 143 1035 1110 1106 1068 143 1050 1125 1121 1083 143 2 53 2 50 2 50 2 60 Scroll R-22 7-10 8- 2 9- 8 8-13 9-10 10-10 9-8 9-5 13-0 13-6 16-0 16-8 16-8 17-8 15-3 16-6 Propeller 2...22 2...22 6500 7000 1/ ...1100 1/ ...1100 4 4 650 650 3/ -in. OD Enhanced Copper Tubes, Aluminum Lanced Fins 8 2...22 6500 1/ ...1100 4 650 2...22 7000 1/ ...1100 4 650 2...
PHYSICAL DATA — 581B090-150 (cont) UNIT SIZE 581B FURNACE SECTION Rollout Switch Cutout Temp (F)† Burner Orifice Diameter (in. ...drill size)** Natural Gas — Std Liquid Propane — Alt†† 090 581B036-150 Stage 2 195 195 195 195 .120...31 .120...31 .120...31 .096...41 .096...41 .096...41 .120...31 .120...31 .129...30 .096...41 .096...41 .102...38 .120...31 .129...30 Lo Med Hi .14 .14 .14 .14 .20 .20 90,000 120,000 180,000 125,000 180,000 224,000 82 82 82 20-50 35-65 45-75 .14 .14 .14 .20 .20 .
BASE UNIT DIMENSIONS — 581B036-072 581B036-150 a48-8199 87
090 102 120 150 UNIT 581B STD UNIT WEIGHT Lb Kg 870 395 1015 460 1035 469 1050 476 ECONOMI$ER IV WEIGHT Lb Kg 75 34.1 75 34.1 75 34.1 75 34.1 VERT. ECON IV W/P.E. WEIGHT Lb Kg 145 65.9 145 65.9 145 65.9 145 65.9 (A) CORNER WEIGHT Lb Kg 189 86 223 101 225 102 228 103 (B) CORNER WEIGHT Lb Kg 161 73 188 85 192 87 195 88 (C) CORNER WEIGHT Lb Kg 239 109 279 126 285 129 289 131 (D) CORNER WEIGHT Lb Kg 280 127 327 148 333 151 338 153 ft-in. 2-07/8 1-27/8 1-27/8 1-27/8 “H” mm 632 378 378 378 ft-in.
ACCESSORY DIMENSIONS — 581B036-072 581B036-150 a48-8201 89
581B036-150 ACCESSORY DIMENSIONS — 581B090-150 a48-8202 90
SELECTION PROCEDURE (With 581B048 Example) = 48,900 Btuh – 897 Watts Btuh ) Watts 3061 Btuh (3.413 = 48,900 Btuh Net capacity = 45,839 Btuh – Net sensible capacity = 37,481 Btuh – 3061 Btuh = 34,420 Btuh 91 581B036-150 IV DETERMINE FAN SPEED AND POWER REQUIREMENTS AT DESIGN CONDITIONS. Before entering the Fan Performance tables, calculate the total static pressure required based on unit components. From the given and the Pressure Drop tables (page 128), find: External static pressure .75 in.
PERFORMANCE DATA COOLING CAPACITIES, STANDARD UNITS 581B036 (3 TONS) Temp (F) Air Ent Condenser (Edb) TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 75 85 95 581B036-150 105 115 125 900/0.14 72 41.9 20.4 2.19 40.7 19.9 2.46 39.3 19.5 2.75 37.7 18.8 3.06 36.0 18.3 3.41 34.2 17.6 3.78 67 38.7 25.2 2.16 37.5 24.7 2.42 36.1 24.1 2.71 34.6 23.5 3.02 33.0 22.9 3.36 31.3 22.2 3.73 62 35.7 29.7 2.12 34.5 29.2 2.39 33.1 28.4 2.66 31.7 27.8 2.98 29.7 26.7 3.31 27.8 25.8 3.
PERFORMANCE DATA (cont) COOLING CAPACITIES, STANDARD UNITS (cont) 581B072 (6 TONS) Temp (F) Air Ent Condenser (Edb) 75 85 95 105 125 72 86.7 43.0 4.58 84.1 42.0 5.10 81.3 41.0 5.65 77.9 39.7 6.22 74.7 38.7 6.84 70.3 37.2 7.43 67 80.7 53.7 4.46 78.2 52.6 4.97 75.3 51.4 5.52 72.0 50.2 6.08 68.4 48.8 6.68 63.6 47.0 7.25 62 74.4 63.8 4.33 72.0 62.7 4.85 69.2 61.4 5.39 66.1 60.0 5.94 61.8 58.1 6.49 57.2 55.8 7.03 72 88.8 45.0 4.63 86.4 44.5 5.16 83.4 43.4 5.71 80.0 42.2 6.29 75.9 40.8 6.87 71.8 39.5 7.
PERFORMANCE DATA (cont) COOLING CAPACITIES, STANDARD UNITS (cont) 581B120 (10 TONS) Temp (F) Air Ent Condenser (Edb) 75 85 95 581B036-150 105 115 125 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 72 141.2 66.7 7.37 138.9 66.3 8.32 135.1 65.2 9.35 129.8 63.6 10.47 124.3 61.9 11.68 118.5 60.0 13.02 Air Entering Evaporator — Cfm/BF 3200/0.03 4000/0.04 Air Entering Evaporator — Ewb 67 62 72 67 130.4 118.1 145.2 134.0 84.4 101.5 71.3 93.1 7.23 7.13 7.46 7.31 126.6 113.6 142.6 130.6 83.6 99.
PERFORMANCE DATA (cont) COOLING CAPACITIES — UNITS WITH PERFECT HUMIDITY™ ADAPTIVE DEHUMIDIFICATION SYSTEM OPTION 581B036 (3 TONS) — SUBCOOLING MODE Temp (F) Air Ent Condenser (Edb) 75 85 95 105 115 125 72 41.3 17.5 2.19 38.6 15.2 2.46 35.9 13.0 2.74 33.8 10.9 3.05 31.8 9.0 3.40 28.7 6.9 3.78 67 37.3 22.4 2.14 34.4 20.1 2.40 31.4 17.9 2.68 29.7 15.8 3.00 28.0 13.7 3.36 26.3 12.2 3.73 62 34.3 26.7 2.10 31.6 25.1 2.37 28.8 23.3 2.63 27.4 21.0 2.97 25.5 18.4 3.31 23.4 17.3 3.
PERFORMANCE DATA (cont) COOLING CAPACITIES — UNITS WITH PERFECT HUMIDITY™ ADAPTIVE DEHUMIDIFICATION SYSTEM OPTION (cont) 581B048 (4 TONS) — SUBCOOLING MODE Temp (F) Air Ent Condenser (Edb) 75 85 581B036-150 95 105 115 125 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 1200/0.17 72 52.9 22.7 2.87 49.2 19.8 3.26 45.8 17.2 3.71 41.6 13.5 4.20 37.2 9.9 4.73 32.4 7.2 5.29 67 47.5 28.4 2.86 43.8 25.5 3.25 40.1 22.5 3.68 37.0 19.5 4.17 33.2 16.4 4.68 28.1 12.9 5.23 62 41.5 33.4 2.82 37.1 30.4 3.
PERFORMANCE DATA (cont) COOLING CAPACITIES — UNITS WITH PERFECT HUMIDITY™ ADAPTIVE DEHUMIDIFICATION SYSTEM OPTION (cont) 581B060 (5 TONS) — SUBCOOLING MODE Temp (F) Air Ent Condenser (Edb) 75 85 95 115 125 72 69.9 29.0 3.61 65.9 25.3 4.05 61.9 21.6 4.53 57.7 18.1 5.05 53.4 14.7 5.60 48.7 10.9 6.26 67 62.7 36.9 3.55 59.1 34.0 3.97 55.2 31.1 4.43 51.1 27.8 4.93 47.2 24.6 5.49 42.0 19.6 6.12 62 56.2 43.9 3.51 51.7 41.9 3.91 47.7 40.0 4.35 44.9 35.7 4.84 42.0 31.5 5.40 36.9 28.0 6.02 72 74.7 31.7 3.64 70.
PERFORMANCE DATA (cont) COOLING CAPACITIES — UNITS WITH PERFECT HUMIDITY™ ADAPTIVE DEHUMIDIFICATION SYSTEM OPTION (cont) 581B072 (6 TONS) — SUBCOOLING MODE Temp (F) Air Ent Condenser (Edb) 75 85 581B036-150 95 105 115 125 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 1800/0.05 72 82.6 36.0 4.60 78.2 31.4 5.16 73.8 27.0 5.75 68.4 22.3 6.37 63.4 18.1 7.04 55.5 15.3 7.80 67 75.6 44.8 4.52 71.6 41.2 5.03 67.4 37.6 5.60 62.6 33.5 6.22 57.8 29.5 6.89 49.6 24.0 7.61 62 68.5 55.4 4.36 64.5 51.
PERFORMANCE DATA (cont) COOLING CAPACITIES — UNITS WITH PERFECT HUMIDITY™ ADAPTIVE DEHUMIDIFICATION SYSTEM OPTION (cont) 581B090 (71/2 TONS) — SUBCOOLING MODE TEMP (F) AIR ENT CONDENSER (Edb) 75 85 95 105 115 125 72 98.4 44.5 5.05 94.2 39.7 5.74 89.9 34.8 6.42 84.6 30.0 7.26 79.2 25.2 8.10 72.8 20.1 9.10 67 91.1 55.4 4.96 85.8 51.3 5.65 80.5 47.2 6.33 75.3 42.5 7.16 70.1 37.8 7.99 64.5 33.4 8.94 62 81.1 67.0 4.87 76.9 62.7 5.55 72.6 58.3 6.22 68.0 53.9 7.05 63.3 49.4 7.87 57.2 44.1 8.
PERFORMANCE DATA (cont) COOLING CAPACITIES — UNITS WITH PERFECT HUMIDITY™ ADAPTIVE DEHUMIDIFICATION SYSTEM OPTION (cont) 581B102 (81/2 TONS) — SUBCOOLING MODE Temp (F) Air Ent Condenser (Edb) 75 85 581B036-150 95 105 115 125 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 2550/0.08 72 114.1 49.8 5.57 107.3 42.2 6.32 101.9 35.4 7.06 94.5 29.7 7.99 86.4 24.0 8.91 78.6 18.3 9.81 67 104.1 64.2 5.46 98.4 58.3 6.30 92.4 51.9 7.13 85.4 45.7 8.00 75.0 38.7 8.83 65.5 32.0 9.65 62 97.8 81.2 5.44 92.
PERFORMANCE DATA (cont) COOLING CAPACITIES — UNITS WITH PERFECT HUMIDITY™ ADAPTIVE DEHUMIDIFICATION SYSTEM OPTION (cont) 581B120 (10 TONS) — SUBCOOLING MODE Temp (F) Air Ent Condenser (Edb) 75 85 95 105 115 125 72 134.3 60.0 7.03 127.6 51.5 7.96 120.9 43.0 8.88 112.0 36.1 10.0 103.0 29.2 11.2 94.1 22.3 12.35 67 122.5 76.1 6.84 115.4 68.8 7.86 108.3 61.5 8.87 99.9 54.1 10.0 91.5 46.7 11.1 83.1 39.3 12.15 62 111.4 93.7 6.72 104.6 87.2 7.59 97.8 80.6 8.46 90.4 73.8 9.6 83.1 66.9 10.8 75.7 60.1 11.
PERFORMANCE DATA (cont) COOLING CAPACITIES — UNITS WITH PERFECT HUMIDITY™ ADAPTIVE DEHUMIDIFICATION SYSTEM OPTION (cont) 581B150 (121/2 TONS) — SUBCOOLING MODE Temp (F) Air Ent Condenser (Edb) 75 85 581B036-150 95 105 115 125 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 3750/0.08 72 156.3 66.6 9.28 147.6 58.7 10.29 138.9 50.8 11.29 129.1 42.1 12.59 119.2 33.5 13.90 109.4 24.8 15.20 67 144.2 87.6 8.98 136.2 80.0 9.93 128.2 72.3 10.87 117.8 63.5 12.14 107.3 54.8 13.40 96.9 46.0 14.
PERFORMANCE DATA (cont) FAN PERFORMANCE — VERTICAL DISCHARGE UNITS 581B036 (3 TONS) — STANDARD MOTOR (BELT DRIVE)* 0.8 Bhp 0.37 0.43 0.50 0.57 0.65 0.74 0.84 Watts 368 430 498 572 651 738 831 Rpm 947 972 999 1025 1053 1081 1110 1.0 Bhp 0.44 0.51 0.59 0.67 0.76 0.86 0.96 Watts 437 509 587 670 760 856 960 581B036 (3 TONS) — STANDARD MOTOR (BELT DRIVE)* (cont) External Static Pressure (in. wg) Airflow 1.2 1.4 1.6 (Cfm) Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm 900 1016 0.51 505 1080 0.57 572 1139 0.
PERFORMANCE DATA (cont) FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 581B048 (4 TONS) — STANDARD MOTOR (BELT DRIVE)* External Static Pressure (in. wg) 0.6 Watts Rpm Bhp Watts Rpm 367 871 0.47 471 952 426 901 0.54 540 981 491 931 0.62 616 1010 564 963 0.70 699 1040 643 994 0.79 790 1070 730 1027 0.89 888 1101 826 1060 1.00 994 1133 930 1093 1.11 1109 — 1043 — — — — 0.8 Bhp 0.57 0.65 0.74 0.84 0.94 1.05 1.16 — — Watts 572 651 738 831 932 1040 1157 — — Rpm 1025 1053 1081 1110 1140 1170 — — — 1.
PERFORMANCE DATA (cont) FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) Rpm 1158 1190 1223 1257 1291 — — — — — — 0.8 Bhp 0.80 0.90 1.00 1.12 1.24 — — — — — — Watts 715 800 892 993 1101 — — — — — — Rpm 1238 1269 1302 1334 — — — — — — — 1.0 Bhp 0.94 1.04 1.15 1.27 — — — — — — — Watts 831 922 1022 1130 — — — — — — — 581B060 (5 TONS) — STANDARD MOTOR (BELT DRIVE)* — SINGLE-PHASE UNITS (cont) External Static Pressure (in. wg) Airflow 1.2 1.4 1.
PERFORMANCE DATA (cont) FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 581B060 (5 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* Airflow (Cfm) 581B036-150 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500 Rpm 848 887 927 967 1007 1048 1090 1131 1173 1215 1258 0.2 Bhp 0.42 0.49 0.57 0.65 0.75 0.85 0.97 1.09 1.23 1.38 1.54 Watts 371 433 502 579 663 757 859 970 1091 1223 1365 Rpm 968 1004 1040 1077 1115 1153 1191 1230 1269 1309 1349 0.4 Bhp 0.55 0.63 0.71 0.81 0.91 1.03 1.15 1.29 1.43 1.59 1.
PERFORMANCE DATA (cont) FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 581B072 (6 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* 0.8 Bhp 1.13 1.25 1.38 1.52 1.67 1.84 2.01 2.19 2.38 2.59 2.81 — — Watts 1002 1111 1228 1353 1487 1630 1782 1945 2117 2301 2495 — — Rpm 1333 1366 1399 1433 1467 1501 1537 1572 1608 1645 — — — 1.0 Bhp 1.28 1.42 1.56 1.71 1.87 2.04 2.23 2.42 2.62 2.
PERFORMANCE DATA (cont) FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 581B090 (71/2 TONS) — STANDARD MOTOR (BELT DRIVE)* External Static Pressure (in. wg) 581B036-150 Airflow (Cfm) 2250 2300 2400 2500 2550 2600 2700 2800 2900 3000 3100 3200 3300 3400 3500 3600 3700 3750 Rpm 0.2 Bhp Watts 513 521 535 551 558 566 582 597 613 629 645 662 678 694 711 727 744 752 0.54 0.57 0.63 0.69 0.72 0.76 0.83 0.90 0.98 1.07 1.16 1.26 1.36 1.47 1.59 1.71 1.84 1.
PERFORMANCE DATA (cont) FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 581B090 (71/2 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* External Static Pressure (in. wg) Airflow (Cfm) 0.2 Bhp Watts Rpm 0.4 Bhp Watts Rpm 0.6 Bhp Watts Rpm 0.8 Bhp Watts Rpm 1.0 Bhp Watts 513 521 535 551 558 566 582 597 613 629 645 662 678 694 711 727 744 752 0.54 0.57 0.63 0.69 0.72 0.76 0.83 0.90 0.98 1.07 1.16 1.26 1.36 1.47 1.59 1.71 1.84 1.
PERFORMANCE DATA (cont) FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 581B102 (81/2 TONS) — STANDARD MOTOR (BELT DRIVE)* External Static Pressure (in. wg) 581B036-150 Airflow (Cfm) 2500 2600 2700 2800 2900 3000 3100 3200 3300 3400 3500 3600 3700 3800 3900 4000 4100 4200 4300 Rpm 0.2 Bhp Watts 541 556 571 586 601 616 632 648 663 679 695 711 728 744 760 777 793 810 826 0.50 0.55 0.60 0.66 0.72 0.79 0.85 0.93 1.00 1.09 1.17 1.26 1.36 1.46 1.57 1.68 1.79 1.92 2.
PERFORMANCE DATA (cont) FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 581B102 (81/2 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* External Static Pressure (in. wg) Airflow (Cfm) 0.2 Bhp Watts Rpm 0.4 Bhp Watts Rpm 0.6 Bhp Watts Rpm 0.8 Bhp Watts Rpm 1.0 Bhp Watts 541 556 571 586 601 616 632 648 663 679 695 711 728 744 760 777 793 810 826 0.50 0.55 0.60 0.66 0.72 0.79 0.85 0.93 1.00 1.09 1.17 1.26 1.36 1.46 1.57 1.68 1.79 1.92 2.
PERFORMANCE DATA (cont) FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 581B120 (10 TONS) — STANDARD MOTOR (BELT DRIVE)* External Static Pressure (in. wg) 581B036-150 Airflow (Cfm) 3000 3100 3200 3300 3400 3500 3600 3700 3800 3900 4000 4100 4200 4300 4400 4500 4600 4700 4800 4900 5000 Rpm 0.2 Bhp Watts 616 632 648 663 679 695 711 728 744 760 777 793 810 826 843 860 876 893 910 927 944 0.79 0.85 0.93 1.00 1.09 1.17 1.26 1.36 1.46 1.57 1.68 1.79 1.92 2.04 2.18 2.32 2.46 2.62 2.77 2.94 3.
PERFORMANCE DATA (cont) FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 581B120 (10 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* External Static Pressure (in. wg) Airflow (Cfm) Watts 616 632 648 663 679 695 711 728 744 760 777 793 810 826 843 860 876 893 910 927 944 0.79 0.85 0.93 1.00 1.09 1.17 1.26 1.36 1.46 1.57 1.68 1.79 1.92 2.04 2.18 2.32 2.46 2.62 2.77 2.94 3.11 732 796 864 936 1012 1092 1177 1266 1361 1460 1563 1672 1786 1906 2031 2161 2297 2439 2587 2741 2901 Rpm 0.4 Bhp Watts Rpm 0.
PERFORMANCE DATA (cont) FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 581B150 (121/2 TONS) — STANDARD MOTOR (BELT DRIVE)* External Static Pressure (in. wg) 581B036-150 Airflow (Cfm) 3700 3800 3900 4000 4100 4200 4300 4400 4500 4600 4700 4800 4900 5000 5100 5200 5300 5400 5500 5600 5700 5800 5900 6000 6100 6200 6300 Rpm 0.2 Bhp Watts 728 744 760 777 793 810 826 843 860 876 893 910 927 944 961 978 995 1012 1029 1046 1063 1080 1098 1115 — — — 1.36 1.46 1.57 1.68 1.79 1.92 2.04 2.18 2.32 2.46 2.
PERFORMANCE DATA (cont) FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS 581B036 (3 TONS) — STANDARD MOTOR (BELT DRIVE)* 0.8 Bhp 0.42 0.47 0.52 0.58 0.65 0.72 0.80 Watts 417 466 519 579 644 716 795 Rpm 948 971 995 1020 1044 1070 1096 1.0 Bhp 0.53 0.58 0.64 0.71 0.78 0.86 0.95 Watts 526 580 639 705 777 855 941 581B036 (3 TONS) — STANDARD MOTOR (BELT DRIVE)* (cont) External Static Pressure (in. wg) Airflow 1.2 1.4 1.6 (Cfm) Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm 900 1019 0.64 640 1084 0.76 760 1146 0.
PERFORMANCE DATA (cont) FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 581B048 (4 TONS) — STANDARD MOTOR (BELT DRIVE)* External Static Pressure (in. wg) 0.6 Watts Rpm Bhp Watts Rpm 343 859 0.46 458 944 394 886 0.52 517 969 452 913 0.58 581 996 515 941 0.66 653 1023 586 970 0.73 731 1050 663 999 0.82 817 1078 749 1029 0.91 910 1106 842 1059 1.02 1012 1135 944 1090 1.13 1122 — 0.8 Bhp 0.58 0.65 0.72 0.80 0.88 0.98 1.08 1.
PERFORMANCE DATA (cont) FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 0.8 Bhp 0.72 0.80 0.90 1.00 1.11 1.23 — — — — — Watts 640 714 796 886 986 1095 — — — — — Rpm 1169 1195 1221 1250 1279 — — — — — — 1.0 Bhp 0.85 0.93 1.03 1.14 1.25 — — — — — — Watts 753 829 914 1008 1111 — — — — — — 581B060 (5 TONS) — STANDARD MOTOR (BELT DRIVE)* — SINGLE-PHASE UNITS (cont) External Static Pressure (in. wg) Airflow 1.2 1.4 1.6 (Cfm) Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm — 1500 1247 0.98 873 1320 1.
PERFORMANCE DATA (cont) FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 581B060 (5 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* Airflow (Cfm) 581B036-150 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500 Rpm 800 839 879 919 960 1001 1043 1085 1127 1169 1212 0.2 Bhp 0.39 0.46 0.54 0.63 0.73 0.84 0.96 1.09 1.23 1.38 1.55 Watts 350 412 483 561 648 744 850 966 1092 1229 1378 Rpm 904 938 974 1010 1047 1085 1123 1162 1201 1241 1281 0.4 Bhp 0.49 0.57 0.65 0.75 0.85 0.96 1.09 1.22 1.37 1.53 1.
PERFORMANCE DATA (cont) FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 581B072 (6 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* Airflow (Cfm) Watts 569 652 744 844 954 1074 1204 1345 1497 1660 1835 2023 2224 Rpm 1010 1046 1083 1120 1158 1196 1234 1273 1312 1352 1392 1432 1472 0.4 Bhp 0.80 0.91 1.02 1.14 1.27 1.41 1.57 1.73 1.91 2.10 2.31 2.53 2.76 External Static Pressure (in. wg) 0.6 Watts Rpm Bhp Watts Rpm 715 1098 0.98 869 1178 805 1131 1.09 965 1210 903 1166 1.21 1070 1242 1010 1200 1.
PERFORMANCE DATA (cont) FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 581B090 (71/2 TONS) — STANDARD MOTOR (BELT DRIVE)* External Static Pressure (in. wg) 0.6 Watts Rpm Bhp Watts Rpm 681 657 0.97 901 722 708 663 1.00 931 727 766 674 1.07 993 738 828 686 1.14 1060 748 860 692 1.17 1095 754 894 698 1.21 1131 759 964 710 1.29 1207 770 1039 723 1.38 1287 782 1119 736 1.47 1372 794 1204 749 1.57 1463 806 1293 762 1.67 1558 818 1388 776 1.78 1658 831 1488 789 1.89 1764 843 1593 803 2.01 1876 856 1705 817 2.
PERFORMANCE DATA (cont) FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 581B090 (71/2 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* 0.8 Bhp 1.22 1.26 1.33 1.41 1.45 1.49 1.58 1.67 1.76 1.87 1.97 2.09 2.21 2.33 2.46 2.60 2.75 2.82 Watts 1142 1174 1241 1312 1349 1388 1469 1554 1644 1740 1840 1946 2057 2174 2297 2425 2560 2630 Rpm 782 787 796 806 811 816 826 837 848 859 871 882 894 907 919 932 944 951 1.0 Bhp 1.50 1.54 1.62 1.70 1.74 1.78 1.88 1.97 2.07 2.18 2.29 2.41 2.54 2.67 2.81 2.95 3.10 3.
PERFORMANCE DATA (cont) FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 581B102 (81/2 TONS) — STANDARD MOTOR (BELT DRIVE)* External Static Pressure (in. wg) 0.6 Watts Rpm Bhp Watts Rpm 576 682 0.78 732 753 621 692 0.84 783 761 670 702 0.90 837 770 721 712 0.96 894 780 775 722 1.02 954 789 832 732 1.09 1017 799 893 743 1.16 1083 808 957 754 1.24 1153 818 1024 765 1.31 1225 829 1095 777 1.40 1302 839 1169 788 1.48 1381 850 1246 800 1.57 1465 860 1328 811 1.66 1552 871 1414 823 1.76 1644 882 1503 835 1.
PERFORMANCE DATA (cont) FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 581B102 (81/2 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* 0.8 Bhp 0.96 1.02 1.08 1.15 1.22 1.29 1.37 1.45 1.53 1.62 1.71 1.81 1.91 2.01 2.12 2.23 2.35 2.47 2.60 Watts 892 948 1008 1070 1136 1204 1276 1351 1429 1511 1597 1686 1779 1876 1977 2082 2192 2305 2423 Rpm 817 825 834 842 851 860 869 878 888 897 907 917 927 938 948 959 970 981 992 1.0 Bhp 1.13 1.20 1.27 1.34 1.42 1.50 1.58 1.66 1.75 1.85 1.95 2.05 2.15 2.26 2.38 2.50 2.62 2.
PERFORMANCE DATA (cont) FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 581B120 (10 TONS) — STANDARD MOTOR (BELT DRIVE)* 581B036-150 Airflow (Cfm) 3000 3100 3200 3300 3400 3500 3600 3700 3800 3900 4000 4100 4200 4300 4400 4500 4600 4700 4800 4900 5000 Rpm 579 592 606 620 634 648 662 676 690 705 719 734 748 763 778 792 807 822 837 852 867 0.2 Bhp 0.70 0.76 0.82 0.88 0.95 1.03 1.10 1.19 1.27 1.36 1.45 1.55 1.66 1.76 1.88 1.99 2.12 2.25 2.38 2.52 2.
PERFORMANCE DATA (cont) FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 581B120 (10 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* 0.8 Bhp 1.29 1.37 1.45 1.53 1.62 1.71 1.81 1.91 2.01 2.12 2.23 2.35 2.47 2.60 2.73 2.87 3.01 3.15 3.31 3.46 3.63 Watts 1204 1276 1351 1429 1511 1597 1686 1779 1876 1977 2082 2192 2305 2423 2546 2673 2805 2942 3083 3230 3383 Rpm 860 869 878 888 897 907 917 927 938 948 959 970 981 992 1004 1015 1027 1038 1050 1062 1074 1.0 Bhp 1.50 1.58 1.66 1.75 1.85 1.95 2.05 2.15 2.26 2.38 2.
PERFORMANCE DATA (cont) FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 581B150 (121/2 TONS) — STANDARD MOTOR (BELT DRIVE)* External Static Pressure (in. wg) 0.6 Watts Rpm Bhp Watts Rpm 1328 811 1.66 1552 871 1414 823 1.76 1644 882 1503 835 1.86 1739 894 1597 848 1.97 1838 905 1695 860 2.08 1942 917 1797 872 2.20 2050 928 1903 885 2.32 2162 940 2014 898 2.44 2279 952 2130 910 2.57 2401 964 2250 923 2.71 2527 976 2375 936 2.85 2658 989 2505 949 3.00 2794 1001 2640 963 3.15 2935 1014 2781 976 3.
PERFORMANCE DATA (cont) FAN RPM AT MOTOR PULLEY SETTING WITH STANDARD MOTOR* — 581B036-150 UNIT 581B 0 1/ 036 048 060 072 090,102 120 150 1044 1185 1460 1585 1085 1080 1130 1008 1144 1425 1538 1060 1060 1112 2 1 11/2 2 971 1102 1389 1492 1035 1035 1087 935 1061 1354 1445 1010 1015 1062 898 1019 1318 1399 985 990 1037 MOTOR PULLEY TURNS OPEN 2 1 /2 3 3 1 /2 4 862 978 1283 1352 960 970 1212 826 936 1248 1305 935 950 987 789 895 1212 1259 910 925 962 753 853 1177 1212 890 905 937 4 1 /2 5 5
PERFORMANCE DATA (cont) OUTDOOR SOUND POWER (TOTAL UNIT) UNIT 581B 036,048 060,072 090,102 120 150 dB SOUND RATING (dB) 76 80 82 84 86 OCTAVE BANDS 63 125 250 500 1000 2000 4000 8000 55.9 59.1 62.2 64.6 63.7 66.0 68.9 69.3 71.1 69.9 64.0 68.7 71.5 73.3 72.5 66.2 71.9 74.7 76.9 78.2 68.4 74.0 76.2 77.6 81.1 64.5 68.9 72.9 73.7 77.3 61.7 65.7 68.7 70.6 73.3 57.3 59.0 61.5 63.7 66.
PERFORMANCE DATA (cont) 0.35 0.25 0.2 0.15 581B036-150 Coil Pressure Drop (in. wg) 0.3 0.1 0.05 0 0 1000 3 ton 2000 3000 Airflow (cfm) 4 & 5 ton 6 ton 4000 5000 a48-7640 7.5 ton 8.5, 10 & 12.
PERFORMANCE DATA (cont) 2500 5000 2000 3000 3-6 Ton 2000 7.5-12.5 Ton FLOW (cfm) FLOW (cfm) 4000 1000 1500 1000 500 0 0 0.1 0.2 0.3 0.4 0.5 0 a48-6308 STATIC PRESSURE (in. wg) 0 VERTICAL POWER EXHAUST PERFORMANCE 0.1 a48-6309 0.2 0.3 0.4 0.5 STATIC PRESSURE (in. wg) Flow in cubic feet per minute (cfm) FLOW IN CUBIC FEET PER MINUTE (cfm) 2500 2500 2000 3-6 Ton 1500 7 1/2 - 12 1/2 Ton 1000 500 0 0.15 0.05 0.25 a48-6202 STATIC PRESSURE (in.
PERFORMANCE DATA (cont) EVAPORATOR-FAN MOTOR PERFORMANCE — STANDARD MOTOR UNIT 581B 036 048 072 090,102 120 150 UNIT PHASE Single MAXIMUM CONTINUOUS BHP* 1.20 MAXIMUM OPERATING WATTS* 1000 Three 1.20 1000 Single 1.20 1000 Three 1.20 1000 Single 1.30 1650 Three 2.40 2120 Three 2.40 2120 Three 2.90 2615 Three 3.70 3775 Three 5.25 4400 MAXIMUM AMP DRAW 4.9 4.9 2.2 2.2 4.9 4.9 2.2 2.2 10.1 6.7 3.0 3.0 6.7 3.0 3.0 8.6 3.9 3.9 12.2 5.5 5.5 17.3 8.5 8.
PERFORMANCE DATA (cont) 581B036-150 POWER EXHAUST OPTIONS POWER EXHAUST PART NO. CRPWREXH030A01 CRPWREXH021A01 CRPWREXH022A01 CRPWREXH023A01 VERTICAL — MOUNTED IN ECONOMIZER HOOD APPLICATION USAGE Power Exhaust System (208/230-1-60) 036-072* Power Exhaust System (460-3-60) 036-072 Power Exhaust System (208/230-1-60) 090-150* Power Exhaust System (460-3-60) 090-150 POWER OUTPUT (Hp per fan) 0.23 0.24 0.47 0.37 NO. FANS 2 2 2 2 POWER EXHAUST| PART NO.
ELECTRICAL DATA 581B036-150 UNITS UNIT SIZE 581B NOMINAL V-PH-Hz IFM TYPE 208/230-1-60 STD STD 208/230-3-60 HIGH 036 (3 Tons) STD 460-3-60 HIGH STD 575-3-60 HIGH 208/230-1-60 STD STD 208/230-3-60 HIGH 048 (4 Tons) STD 460-3-60 HIGH STD 575-3-60 HIGH 208/230-1-60 STD PH STD 208/230-3-60 HIGH 060 (5 Tons) STD 460-3-60 HIGH STD 575-3-60 HIGH PH STD 208/230-3-60 HIGH STD 072 (6 Tons) 460-3-60 HIGH STD 575-3-60 HIGH PH STD 208/230-3-60 HIGH STD 090 (71/2 Tons) 460-3-60 HIGH STD 575-3-60
ELECTRICAL DATA (cont) 581B036-150 UNITS UNIT SIZE 581B NOMINAL V-PH-Hz CONV OUTLET IFM TYPE NO YES NO YES NO YES NO YES NO YES NO YES NO YES NO YES NO YES NO YES NO YES NO YES NO YES NO YES NO YES NO YES NO YES NO YES STD 208/230-3-60 HIGH STD 102 (81/2 Tons) 460-3-60 HIGH STD 575-3-60 HIGH 581B036-150 PH STD 208/230-3-60 HIGH STD 120 (10 Tons) 460-3-60 HIGH STD 575-3-60 HIGH PH 150 (121/2 Tons) 208/230-3-60 STD 460-3-60 STD ST 575-3-60 PH CONV FLA HACR IFM LRA MCA MOCP NEC OFM PH RLA UL
TYPICAL WIRING SCHEMATICS — 581B 581B036-150 a48-8233 SIZES 036-150 (581B090, 460-3-60 Shown) 135
581B036-150 TYPICAL WIRING SCHEMATICS — 581B (cont) a48-7910 IAQ LA POT OAT RAT — — — — — LEGEND Indoor Air Quality Low Ambient Lockout Device Potentiometer Outdoor-Air Temperature Return-Air Temperature NOTE: Potentiometer Defaults Settings: Power Exhaust Middle Minimum Pos. Fully Closed DCV Max. Middle DCV Set Middle Enthalpy C Setting ECONOMIZER NOTES: 1. 620 ohm, 1 watt 5% resister should be removed only when using differential enthalpy or dry bulb. 2.
TYPICAL WIRING SCHEMATICS — 581B (cont) 460V C2 FOR 008-014 UNITS RED YEL BLU LINE SIDE GRA C H3 H1 H2 H4 TRAN4 BLU GRA 11 21 RED YEL 13 23 23 240V X4 X2 X1 X3 RED H1 H3 H2 X2 X3 GRA 208-230-1 ONLY H4 581B036-150 SECONDARY 120V YEL BLU TRAN4 RED GRA X4 600V H2 H1 X1 BLK WHT SECONDARY 120V TRAN4 X4 X2 GROUND FAULT INTERRUPTER CONVENIENCE OUTLET GFI - CO X1 X3 GRN-YEL GRN-YEL SECONDARY 120V SWITCH BLK FUSE TEST RESET a48-7462 15 AMP Convenience Outlet (Opti
581B036-150 TYPICAL PIPING AND WIRING — 581B036-150 48-983 Vertical Discharge Ducting NO.1 CONVENIENCE OUTLET a48-6307 NO.
GUIDE SPECIFICATIONS — 580F036-151 AND 581B036-150 PACKAGED ROOFTOP ELECTRIC COOLING UNIT WITH GAS HEAT — CONSTANT VOLUME APPLICATION HVAC GUIDE SPECIFICATIONS SIZE RANGE: 3 TO 121/2 TONS, NOMINAL (COOLING) 60,000 TO 250,000 BTUH, NOMINAL (INPUT HEATING) BRYANT MODEL NUMBERS: 580F, 581B 581B036-121 UNITS ARE ENERGY STAR QUALIFIED PART 1 — GENERAL 1.
580F036-150 AND 581B036-150 GUIDE SPECIFICATIONS — 580F036-151 AND 581B036-150 (cont) F. Heating Section: 1. Induced-draft combustion type with energy saving direct-spark ignition system and redundant main gas valve. 2. Heat Exchanger: a. The standard heat exchanger shall be of the tubular-section type constructed of a minimum of 20-gage steel coated with a nominal 1.2 mil aluminum-silicone alloy for corrosion resistance. b.
GUIDE SPECIFICATIONS — 580F036-151 AND 581B036-150 (cont) J. L. M. * 141 580F036-151 AND 581B036-150 K. f. EconoMi$er IV and EconoMi$er2 shall be equipped with a barometric relief damper capable of relieving up to 100% return air. g. Designed to close damper(s) during loss-ofpower situations with spring return built into motor. h. Dry bulb outdoor-air temperature sensor shall be provided as standard. Outdoor air sensor set point is adjustable and shall range from 40 to 100 F.
GUIDE SPECIFICATIONS — 580F036-151 AND 581B036-150 (cont) 3. 580F036-150 AND 581B036-150 * * * 4. 5. 6. 7. * 8. 9. * 10. * 11. * 12. 13. t. Remote Minimum Position Control — A fieldinstalled accessory remote potentiometer allows the outdoor air damper to be opened or closed beyond the minimum position in the occupied mode for modified ventilation.
GUIDE SPECIFICATIONS — 580F036-151 AND 581B036-150 (cont) 143 580F036-151 AND 581B036-150 both temperature and humidity in the space are not satisfied. 2) Hot gas reheat mode shall mix a portion of the hot gas from the discharge of the compressor with the hot liquid refrigerant leaving the condenser coil to create a two-phase heat transfer in the system, resulting in a neutral leaving-air temperature when only humidity in the space is not satisfied. b.
PHYSICAL DATA — 579F180-300 180 208/230, 460 v 15 1650 90 200 UNIT 579F NOMINAL CAPACITY (tons) OPERATING WEIGHT (lb) Economizer Roof Curb COMPRESSOR Quantity...Model (Ckt 1, Ckt 2) 0TFQ004-012 579F180-300 Maximum Continuous Bhp Pulley Center Line Distance (in.) Speed Change per Full Turn of Movable Pulley Flange (rpm) Movable Pulley Maximum Full Turns From Closed Position Factory Speed Factory Speed Setting (rpm) Fan Shaft Diameter at Pulley (in.
PHYSICAL DATA — 579F180-300 (cont) UNIT 579F FURNACE SECTION Rollout Switch Cutout Temp (F)† Burner Orifice Diameter (in. ...drill size) Natural Gas Thermostat Heat Anticipator Setting (amps) 208/230, 575 Stage 1 Stage 2 460 v Stage 1 Stage 2 Gas Input Stage 1 Stage 2 Efficiency (Steady State) (%) Temperature Rise Range Manifold Pressure (in. wg) Natural Gas Gas Valve Quantity Field Gas Connection Size (in.-FPT) 180 216 240 300 190 190 190 190 0.1285...30/0.136...29 0.1285...30/0.136...29 0.1285.
180 216 UNIT 579F CORNER B Lb Kg 386 175 410 186 CORNER C Lb Kg 403 183 461 209 CORNER DIM A DIM B DIM C D Lb Kg ft-in. mm ft-in. mm ft-in. mm 438 199 3-5 1041 3-5 1041 1-10 559 472 214 3-3 991 3-7 1092 1-8 508 Center of Gravity. 4. Direction of airflow. 5. Ductwork to be attached to accessory roof curb only. 6. Minimum clearance: • Rear: 7′ -0″ (2134) for coil removal. This dimension can be reduced to 4′ -0″ (1219) if conditions permit coil removal from the top.
240 300 CORNER B Lb Kg 406 184 428 194 CORNER C Lb Kg 476 216 526 239 CORNER DIM A DIM B DIM C D Lb Kg ft-in. mm ft-in. mm ft-in. mm 525 238 3-2 965 3-5 1041 1-8 508 574 260 3-2 965 3-5 1041 1-8 508 4. Direction of airflow. 5. Ductwork to be attached to accessory roof curb only. 6. Minimum clearance: • Rear: 7′ -0″ (2134) for coil removal. This dimension can be reduced to 4′ -0″ (1219) if conditions permit coil removal from the top.
CRRFCURB010A00 CRRFCURB011A00 CRRFCURB012A00 PKG. NO. REF.
ACCESSORY DIMENSIONS — 579F180-300 (cont) a48-7458 2" X 1/4 SUPPORT TYP. STITCH WELDED 3 1/2" FULLY INSULATED SUPPLY PLENUM 1" INSULATION 1 1/2 # DENSITY, STICK PINNED & GLUED 14 3/4" 23" 6" a48-7457 12" WIDE STANDING SEAM PANELS a48-7459 ACCESSORY PACKAGE NO.
ACCESSORY DIMENSIONS (cont) LEGEND K.O.
SELECTION PROCEDURE (With 579F180 Example) IV DETERMINE FAN SPEED AND POWER REQUIREMENTS AT DESIGN CONDITIONS. Before entering the Fan Performance tables, calculate the total static pressure required based on unit components. From the given and the Accessory/FIOP Static Pressure table on page 164 find: I DETERMINE COOLING AND HEATING REQUIREMENTS AT DESIGN CONDITIONS. Given: Required Cooling Capacity . . . . . . . . . . . . . 170,000 Btuh Sensible Heat Capacity . . . . . . . . . . . . . . . .
PERFORMANCE DATA — 579F COOLING CAPACITIES 579F180 (15 Tons) Temp (F) Air Entering Condenser (Edb) TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 75 85 95 105 115 117 120 Evaporator Air Quantity — Cfm 4500 54/0.48 — — — 159 159 13.7 154 154 15.3 149 149 16.9 144 144 18.6 143 143 18.9 141 141 19.5 58/0.32 168 152 12.4 164 148 13.8 159 142 15.4 154 137 17.0 145 142 18.6 143 142 19.0 141 141 19.5 62/0.22 177 142 12.6 171 139 14.1 165 136 15.5 158 133 17.1 152 130 18.
PERFORMANCE DATA — 579F (cont) COOLING CAPACITIES (cont) 579F180 (15 Tons) (cont) Temp (F) Air Entering Condenser (Edb) TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 75 85 95 105 115 117 120 — — — — — — — — 80/0.03 256 70 14.2 249 68 16.3 237 65 17.3 228 62 19.0 217 59 20.9 — — — — — — 3. The SHC is based on 80 F edb temperature of air entering evaporator coil. Below 80 F edb, subtract (corr factor x cfm) from SHC. Above 80 F edb, add (corr factor x cfm) to SHC.
PERFORMANCE DATA — 579F (cont) COOLING CAPACITIES (cont) 579F216 (18 Tons) Temp (F) Air Entering Condenser (Edb) TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 75 85 95 105 115 117 120 Evaporator Air Quantity — Cfm 5400 54/0.49 194 194 13.6 189 189 15.1 183 183 16.8 177 177 18.6 171 171 20.5 170 170 20.9 168 168 21.5 58/0.31 198 178 13.7 192 176 15.2 184 181 16.8 178 178 18.6 171 171 20.5 170 170 20.9 168 168 21.5 62/0.20 206 169 13.9 200 166 15.4 193 162 17.1 185 159 18.
PERFORMANCE DATA — 579F (cont) COOLING CAPACITIES (cont) 579F216 (18 Tons) (cont) Temp (F) Air Entering Condenser (Edb) TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 75 85 95 105 115 117 120 — — — — — — — — 80/0.05 — — — — — — — — — — — — — — — — — — — — — 3. The SHC is based on 80 F edb temperature of air entering evaporator coil. Below 80 F edb, subtract (corr factor x cfm) from SHC. Above 80 F edb, add (corr factor x cfm) to SHC.
PERFORMANCE DATA — 579F (cont) COOLING CAPACITIES (cont) 579F240 (20 Tons) Temp (F) Air Entering Condenser (Edb) TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 75 85 95 105 115 117 120 Evaporator Air Quantity — Cfm 6,000 54/0.48 217 217 15.1 212 212 16.9 206 206 18.9 199 199 20.8 192 192 23.0 191 191 23.5 189 189 24.2 58/0.31 222 199 15.2 217 194 17.2 208 197 18.8 202 190 20.9 194 192 22.9 191 191 23.5 189 189 24.2 62/0.21 232 189 15.4 226 185 17.3 217 181 19.0 209 177 21.
PERFORMANCE DATA — 579F (cont) COOLING CAPACITIES (cont) 579F240 (20 Tons) (cont) Temp (F) Air Entering Condenser (Edb) TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 75 85 95 105 115 117 120 — — — — — — — — 80/0.04 — — — — — — — — — — — — — — — — — — — — — 3. The SHC is based on 80 F edb temperature of air entering evaporator coil. Below 80 F edb, subtract (corr factor x cfm) from SHC. Above 80 F edb, add (corr factor x cfm) to SHC.
PERFORMANCE DATA — 579F (cont) COOLING CAPACITIES (cont) 579F300 (25 Tons) Temp (F) Air Entering Condenser (Edb) TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 75 85 95 105 115 117 120 Evaporator Air Quantity — Cfm 7,000 54/0.44 — — — 249 249 21.3 244 244 23.6 237 237 25.9 229 229 28.6 228 228 29.1 226 226 30.0 58/0.26 256 243 19.3 251 238 21.3 245 230 23.5 238 233 25.9 231 225 28.6 230 225 29.1 226 225 30.0 62/0.13 270 229 20.0 265 226 21.7 257 223 24.1 247 218 26.
PERFORMANCE DATA — 579F (cont) COOLING CAPACITIES (cont) 579F300 (25 Tons) (cont) Temp (F) Air Entering Condenser (Edb) TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 75 85 95 105 115 117 120 — — — — — — — — 80/0.00 392 108 21.9 384 106 25.3 — — — — — — — — — — — — — — — 3. The SHC is based on 80 F edb temperature of air entering evaporator coil. Below 80 F edb, subtract (corr factor x cfm) from SHC. Above 80 F edb, add (corr factor x cfm) to SHC.
PERFORMANCE DATA — 579F (cont) FAN PERFORMANCE — 579F180-300 UNITS 579F180230 (15 TONS) * Airflow (Cfm) 4500 4800 5100 5400 5700 6000 6300 6600 6900 7200 7500 Rpm 809 850 892 934 976 1019 1063 1106 1150 — — 0.2 Bhp 1.53 1.76 2.01 2.28 2.58 2.90 3.24 3.61 4.00 — — Watts 1317 1516 1733 1970 2225 2500 2795 3111 3448 — — Rpm 906 942 979 1017 1056 1096 1136 1177 1218 — — 0.4 Bhp 1.74 1.98 2.24 2.52 2.82 3.14 3.49 3.86 4.26 — — Rpm 1369 1390 1413 1437 1463 — — — — — — 1.6 Bhp 3.11 3.37 3.66 3.96 4.
PERFORMANCE DATA — 579F (cont) FAN PERFORMANCE — 579F180-300 UNITS (cont) 579F300275 (25 TONS) * Airflow (Cfm) 7,000 7,500 8,000 8,500 9,000 9,500 10,000 10,500 11,000 11,250 Rpm 941 999 1058 1117 1177 1237 1297 1358 1418 1449 0.2 Bhp 3.35 4.05 4.85 5.74 6.75 7.98 9.12 10.49 12.00 12.80 Watts 2,769 3,348 4,007 4,750 5,583 6,511 7,450 8,674 9,919 10,585 Rpm 1002 1057 1113 1169 1226 1284 1342 1400 1459 — 0.4 Bhp 3.80 4.53 5.35 6.28 7.31 8.46 9.74 11.14 12.
PERFORMANCE DATA — 579F (cont) FAN PERFORMANCE — 579F180-300 UNITS (cont) 579F216360 and 240360 (18 AND 20 TONS) * Airflow (Cfm) 5,500 6,000 6,500 7,000 7,500 8,000 8,500 9,000 9,500 10,000 Rpm 795 854 914 975 1037 1099 1161 1223 1286 1349 0.2 Bhp 2.43 2.92 3.46 4.06 4.72 5.44 6.22 7.07 7.98 8.95 Watts 2043 2452 2909 3414 3969 4575 5232 5943 6708 7528 Rpm 866 921 977 1034 1092 1150 1210 1270 1331 1392 0.4 Bhp 2.74 3.24 3.79 4.39 5.06 5.79 6.57 7.43 8.34 9.
PERFORMANCE DATA — 579F (cont) a50-4028 Fan Performance Using Accessory Power Exhaust (579F180-300) ALTITUDE COMPENSATION* — 579F180-300 0-3,000 3,000- 7,000 7,000- 9,000 9,000-10,000 above 10,000 ELEVATION (ft) NATURAL GAS ORIFICE SIZE† Low Heat High Heat 30 29 31 30 32 31 33 31 35 32 0-2,000 2,001-3,000 3,001-4,000 4,001-5,000 5,001-6,000 MAXIMUM HEATING VALUE (Btu/ft3) 1,100 1,050 1,000 950 900 *Derating of the unit is not required unless the heating value of the gas exceeds the values listed in
PERFORMANCE DATA — 579F (cont) ALTITUDE COMPENSATION — 579F180-300 (LP Gas Units) LIQUID PROPANE ORIFICE SIZE Low Heat and High Heat 36 37 38 38 39 40 41 41 42 43 ELEVATION (ft) 0-2,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 OUTDOOR SOUND POWER UNIT 579F 180 216 240 300 SOUND RATING (60 Hz) 88 dB 88 dB 95 dB 95 dB OCTAVE BANDS A-WEIGHTED (dB) 63 125 250 500 1000 2000 4000 8000 87.8 87.8 94.1 94.1 90.8 90.8 98.7 98.7 88.7 88.7 92.3 92.3 86.4 86.4 93.8 93.8 84.3 84.3 90.9 90.
PERFORMANCE DATA — 579F (cont) EVAPORATOR-FAN MOTOR DATA UNIT 579F 180 216 240 300 UNIT VOLTAGE 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 MAXIMUM ACCEPTABLE CONTINUOUS BHP* 4.25 4.25 3.45 MAXIMUM ACCEPTABLE CONTINUOUS BkW* 3.17 3.17 2.59 MAXIMUM ACCEPTABLE OPERATING WATTS 3,775 3,775 3,065 5.90 4.40 5,180 8.70 9.50 8.70 10.20 11.80 10.20 6.49 7.08 6.49 7.61 8.80 7.61 7,915 8,640 7,915 9,510 11,000 9,510 MAXIMUM AMP DRAW 10.5 4.8 3.9 15.8 7.9 6.0 22.0 13.0 10.0 28.0 14.
ELECTRICAL DATA UNIT 579F COMPRESSOR NOMINAL VOLTAGE OFM IFM RANGE No. 1 No. 2 VOLTAGE (3 Ph, 60 Hz) Min Max RLA LRA RLA LRA Qty Hp FLA (ea) Hp FLA 208/230 180 (15 Tons) 216 (18 Tons) 240 (20 Tons) 0TFQ004-012 579F180-300 300 (25 Tons) FLA — HACR — IFM — LRA — MCA — MOCP — NEC — OFM — RLA — POWER COMBUSTION EXHAUST FAN MOTOR 187 253 28.8 195 28.8 195 3 0.5 1.7 3.7 10.5/11.0 460 414 508 14.7 95 14.7 95 3 0.5 0.8 3.7 4.8 575 518 633 10.8 80 10.8 80 3 0.5 0.8 3.0 3.
TYPICAL WIRING SCHEMATICS — 579F (579F240, 208/230 V Shown) 0TFQ004-012 579F180-300 a48-7929 167
0TFQ004-012 579F180-300 TYPICAL WIRING SCHEMATICS — 579F (579F240, 208/230 V Shown) (cont) a48-5655 LEGEND AND NOTES LEGEND AHA BKR W/AT C CB CC CLO COMP CR CT DM DU EQUIP FPT FU GND HPS HS HV I IDM IFC — — — — — — — — — — — — — — — — — — — — — Adjustable Heat Anticipator Breaker with Amp Turns Contactor, Compressor Circuit Breaker Cooling Compensator Compressor Lockout Compressor Motor Control Relay Control Transformer Damper Motor Dummy Terminal Equipment Freeze Protection Thermostat Fuse Ground High
TYPICAL WIRING SCHEMATICS — 579F (cont) a48-7877 0TFQ004-012 579F180-300 LEGEND AL — Ambient Limit OA — Outdoor Air ECB — Economizer Control Board OAS — Outdoor Air Sensor IA — Indoor Air RAS — Return Air Sensor IAQ — Indoor Air Quality SAT — Supply Air Temperature EconoMi$er IV Wiring — 579F180-300 Units 4 3 7 RED 500 OHM RESISTOR 2 8 PINK 6 NOTE 1 BLUE RUN 5 OAT BLACK NOTE 2 1 10 50HJ540573 ACTUATOR ASSEMBLY 11 9 WHITE DIRECT DRIVE ACTUATOR a50-8058 LEGEND OAT — Outdoor Air Temperature S
TYPICAL WIRING SCHEMATICS — 579F (cont) a48-6005 NOTES: 1. If the Non-Fused Disconnect Service Option is ordered for these units, the Non-Fused Disconnect will be factory-installed. 2. The Disconnect takes the place of TB-1 as shown on the unit wiring diagram label and the component arrangement label.
TYPICAL PIPING AND WIRING — 579F180-300 (579F180 Shown) 0TFQ004-012 579F180-300 LEGEND NEC — National Electrical Code b48-1258 171
PHYSICAL DATA — 580F180-300 UNIT 580F NOMINAL CAPACITY (tons) OPERATING WEIGHT Unit EconoMi$er IV COMPRESSOR/MANUFACTURER Quantity...Model (Ckt 1, Ckt 2) Rows...Fins/in. Total Face Area (sq ft) EVAPORATOR FAN Quantity...Size (in.) Type Drive Nominal Cfm Motor Hp Motor Nominal Rpm Maximum Continuous Bhp 0TFQ004-012 580F180-300 Nominal Fan Shaft Diameter (in.) Belt, Quantity...Type...Length (in.) Pulley Center Line Distance (in.
PHYSICAL DATA — 580F180-300 (cont) UNIT 580F FURNACE SECTION Rollout Switch Cutout Temp (F)† Burner Orifice Diameter (in. ...drill size) Natural Gas Thermostat Heat Anticipator Setting (amps) 208/230, 575 v Stage 1 Stage 2 460 v Stage 1 Stage 2 Gas Input Stage 1 Stage 2 Efficiency (Steady-State) (%) Temperature Rise Range Manifold Pressure (in. wg) Natural Gas Gas Valve Quantity Gas Valve Pressure Range in. wg psig Field Gas Connection Size (in.-FPT) 180 210 240 300 190 190 190 190 0.1285...30/0.
0TFQ004-012 580F180-300 $ BASE UNIT DIMENSIONS — 580F180, 210 a48-8203 174
BASE UNIT DIMENSIONS — 580F240 0TFQ004-012 580F180-300 a48-8204 175
0TFQ004-012 580F180-300 $ BASE UNIT DIMENSIONS — 580F300 a48-8205 176
CRRFCURB010A00 CRRFCURB011A00 CRRFCURB012A00 a48-6314 177 CURB HEIGHT 1′ − 2″ (305) 2′ - 0″ (610) 2′ - 0″ (610) 580F180-240 Horizontal and Vertical Roof Curbs Standard Curb 14″ High Standard Curb for Units Requiring High Installation Side Supply and Return Curb for High Installation DESCRIPTION 0TFQ004-012 580F180-300 PKG. NO. REF.
0TFQ004-012 580F180-300 a48-7456 178 580F300 Vertical Roof Curbs ACCESSORY DIMENSIONS — 580F300
ACCESSORY DIMENSIONS — 580F (cont) a48-7458 2" X 1/4 SUPPORT TYP. STITCH WELDED 3 1/2" FULLY INSULATED SUPPLY PLENUM 1" INSULATION 1 1/2 # DENSITY, STICK PINNED & GLUED 14 3/4" 23" 6" a48-7457 NOTE: CRRFCURB013A00 is a fully factory preassembled horizontal adapter and includes an insulated transition duct. The pressure drop through the adapter curb is negligible. For horizontal return applications: The power exhaust and barometric relief dampers must be installed in the return air duct.
ACCESSORY DIMENSIONS — 580F (cont) LEGEND K.O.
SELECTION PROCEDURE (With 580F240 Example) IV DETERMINE FAN SPEED AND POWER REQUIREMENTS AT DESIGN CONDITIONS. Before entering the Fan Performance tables, calculate the total static pressure required based on unit components. From the given and the Accessory/FIOP Static Pressure table on page 191 find: External static pressure 0.60 in. wg EconoMi$er IV static pressure 0.10 in. wg Total static pressure 0.70 in. wg Enter the Fan Performance table 580F240360 at 8,000 cfm and 0.70 in.
PERFORMANCE DATA COOLING CAPACITIES 580F180 (15 TONS) Temp (F) Air Entering Condenser (Edb) 75 85 95 105 115 118 120 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 4,500/0.010 62 175.7 145.5 14.0 168.8 141.7 15.2 161.8 138.7 16.4 154.6 133.9 17.6 147.1 130.1 19.0 144.7 129.0 19.4 142.9 128 19.6 67 191.8 123.0 14.4 185.1 119.8 15.6 177.5 116.8 16.9 169.3 113.6 18.2 160.8 110.2 19.5 158.0 109.1 19.9 156.2 108 20.2 5,250/0.120 72 210.9 99.9 15.0 203.0 97.1 16.1 194.4 93.9 17.4 185.
PERFORMANCE DATA (cont) COOLING CAPACITIES (cont) 580F240 (20 TONS) Temp (F) Air Entering Condenser (Edb) 75 85 95 105 115 120 6,000/0.04 62 237 204 16.7 229 201 18.1 220 195 19.4 209 189 20.9 200 185 22.5 194 183 23.2 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 67 258 171 17.4 249 167 18.7 239 163 20.2 228 159 21.5 217 154 23.1 211 152 23.8 7,000/0.05 72 282 138 18.1 272 135 19.5 261 130 20.9 249 126 22.3 237 122 23.8 230 121 24.6 62 242 221 16.9 234 216 18.3 225 211 19.7 216 206 21.
PERFORMANCE DATA (cont) FAN PERFORMANCE — 580F180-300 UNITS 580F180275* Airflow (Cfm) 4500 4800 5100 5700 6000 6300 6600 6900 7200 7500 Rpm 753 747 741 810 844 879 915 950 986 1022 0.2 Watts 1307 1384 1465 1911 2164 2439 2737 3057 3401 3770 Bhp 1.53 1.62 1.72 2.24 2.54 2.86 3.21 3.59 3.99 4.42 Rpm 761 790 820 882 914 947 980 1013 1047 1081 0.4 Watts 1330 1515 1718 2182 2444 2729 3035 3364 3717 4095 Available External Static Pressure (in. wg) 0.6 0.8 Bhp Rpm Watts Bhp Rpm Watts 1.56 840 1572 1.
PERFORMANCE DATA (cont) FAN PERFORMANCE — 580F180-300 UNITS (cont) 580F180360* Airflow (Cfm) 4500 4800 5100 5700 6000 6300 6600 6900 7200 7500 Rpm 753 747 775 849 886 924 962 1000 1038 1077 0.2 Watts 1307 1384 1571 2054 2329 2628 2951 3298 3672 4072 Bhp 1.53 1.62 1.84 2.41 2.73 3.08 3.46 3.87 4.31 4.78 Rpm 786 818 850 918 952 987 1023 1059 1095 1131 0.4 Watts 1404 1603 1822 2323 2607 2915 3246 3603 3986 4394 Available External Static Pressure (in. wg) 0.6 0.8 Bhp Rpm Watts Bhp Rpm Watts 1.
PERFORMANCE DATA (cont) FAN PERFORMANCE — 580F180-300 UNITS (cont) 580F210275 (18 TONS)* Airflow (Cfm) 5,500 6,000 6,500 7,000 7,500 8,000 8,500 9,000 9,500 10,000 Rpm 755 810 866 923 980 1038 1096 1154 1213 1272 0.2 Bhp 2.27 2.72 3.22 3.78 4.39 5.06 5.78 6.56 7.40 8.30 Watts 1908 2287 2710 3177 3690 4251 4859 5517 6224 6983 Rpm 831 881 932 985 1038 1093 1148 1204 1260 1317 0.4 Bhp 2.58 3.04 3.55 4.11 4.73 5.40 6.13 6.92 7.77 8.67 Rpm 1204 1236 1270 1307 1346 1387 1429 1473 1519 — 1.6 Bhp 4.65 5.
PERFORMANCE DATA (cont) FAN PERFORMANCE — 580F180-300 UNITS (cont) 580F240275 (20 TONS)* Cfm 6,000 6,500 7,000 7,500 8,000 8,500 9,000 9,500 10,000 Rpm 824 881 939 998 1056 1116 1175 1235 1295 0.2 Watts 2607 3030 3488 3982 4512 5077 5678 6315 6988 Bhp 3.09 3.59 4.14 4.72 5.35 6.02 6.74 7.49 8.29 Rpm 894 947 1001 1055 1111 1167 1224 1282 1340 0.4 Watts 2844 3266 3725 4218 4748 5314 5915 6552 7225 Available External Static Pressure (in. wg) 0.6 0.8 Bhp Rpm Watts Bhp Rpm Watts 3.37 961 3085 3.
PERFORMANCE DATA (cont) FAN PERFORMANCE — 580F180-300 UNITS (cont) 580F240360 (20 TONS)* Cfm 6,000 6,500 7,000 7,500 8,000 8,500 9,000 9,500 10,000 Rpm 868 929 991 1054 1117 1180 1244 1308 1372 0.2 Watts 2752 3201 3687 4211 4773 5373 6011 6687 7401 Bhp 3.26 3.80 4.37 5.00 5.66 6.37 7.13 7.93 8.78 Rpm 934 991 1049 1109 1168 1229 1290 1352 1414 0.4 Watts 2987 3436 3923 4447 5009 5609 6247 6924 7638 Available External Static Pressure (in. wg) 0.6 0.8 Bhp Rpm Watts Bhp Rpm Watts 3.54 997 3227 3.
PERFORMANCE DATA (cont)\ FAN PERFORMANCE — 580F180-300 UNITS (cont) 580F300275 (25 TONS)* Airflow (Cfm) 7,000 7,500 8,000 8,500 9,000 9,500 10,000 10,500 11,000 11,250 Rpm 941 999 1058 1117 1177 1237 1297 1358 1418 1449 0.2 Bhp 3.35 4.05 4.85 5.74 6.75 7.98 9.12 10.49 12.00 12.80 Watts 2,769 3,348 4,007 4,750 5,583 6,511 7,450 8,674 9,919 10,585 Rpm 1002 1057 1113 1169 1226 1284 1342 1400 1459 — 0.4 Bhp 3.80 4.53 5.35 6.28 7.31 8.46 9.74 11.14 12.
PERFORMANCE DATA (cont) ALTITUDE DERATING FACTOR* ELEVATION (ft) 0-2,000 2,001-3,000 3,001-4,000 4,001-5,000 5,001-6,000 MAXIMUM HEATING VALUE (Btu/ft3) 1,100 1,050 1,000 950 900 *Derating of the unit is not required unless the heating value of the gas exceeds the values listed in the table above, or if the elevation exceeds 6000 ft. Derating conditions must be 4% per thousand ft above 2000 ft.
PERFORMANCE DATA (cont) ACCESSORY/FIOP STATIC PRESSURE (in. wg)* — 580F180-300 COMPONENT 4500 0.040 EconoMi$er IV and EconoMi$er2 FIOP — 5000 0.050 5400 0.060 6000 0.070 CFM 7200 0.090 7500 0.100 9000 0.110 10,000 0.120 11,250 0.140 LEGEND Factory-Installed Option *The static pressure must be added to external static pressure. The sum and the evaporator entering-air cfm should then be used in conjunction with the Fan Performance tables to determine blower rpm and watts.
ELECTRICAL DATA UNIT 580F 180 210 240 Max COMPRESSOR OFM No. 1 No. 1A No. 2 RLA LRA RLA LRA RLA LRA Qty Hp FLA (ea) Hp 187 253 32.1 195 — — 20.7 156 3 0.5 1.7 5.0 15.8/15.8 460 414 508 16.4 95 — — 10 70 3 0.5 0.8 5.0 7.9 575 518 633 12 80 — — 8.2 54 3 0.5 0.75 5.0 6.0 208/230 187 253 30.1 225 — — 28.8 195 3 0.5 1.7 5.0 15.8/15.8 460 414 508 15.5 114 — — 14.7 95 3 0.5 0.8 5.0 7.9 575 518 632.5 12.1 80 — — 10.7 80 3 0.5 0.
TYPICAL WIRING SCHEMATICS — 580F LEGEND AHA — C — CAP — CB — CC — CH — CLO — COMP — CR — DU — EQUIP — FPT — — — — — — — — — — — — L LOR LPS LS MGV OFC OFM PL PRI QT R RS SEN SW TB TC TH TRAN — — — — — — — — — — — — — — — — — — 0TFQ004-012 580F180-300 FU GND HPS HS HV I IDM IFC IFCB IFM IGC Adjustable Heat Anticipator Contactor, Compressor Capacitor Circuit Breaker Cooling Compensator Crankcase Heater Compressor Lockout Compressor Motor Control Relay Dummy Terminal Equipment Freeze Protection Thermosta
TYPICAL WIRING SCHEMATICS — 580F (cont) a48-7877 AL ECB IA IAQ — Ambient Limit — Economizer Control Board — Indoor Air — Indoor Air Quality LEGEND OA — OAS— RAS— SAT — Outdoor Air Outdoor Air Sensor Return Air Sensor Supply Air Temperature EconoMi$er IV Wiring — 580F180-300 4 3 7 0TFQ004-012 580F180-300 RED 500 OHM RESISTOR 2 8 PINK 6 NOTE 1 BLUE RUN 5 OAT BLACK NOTE 2 1 10 50HJ540573 ACTUATOR ASSEMBLY 11 9 WHITE DIRECT DRIVE ACTUATOR a50-8058 LEGEND OAT — Outdoor Air Temperature Senso
TYPICAL WIRING SCHEMATICS — 580F (cont) a48-6005 NOTES: 1. If the Non-Fused Disconnect Service Option is ordered for these units, the Non-Fused Disconnect will be factory-installed. 2. The Disconnect takes the place of TB-1 as shown on the unit wiring diagram label and the component arrangement label.
TYPICAL PIPING AND WIRING — 580F180-300 LEGEND NEC — National Electrical Code 0TFQ004-012 580F180-300 b48-1258 196
PHYSICAL DATA — 581A155,180 UNIT 581A NOMINAL CAPACITY (tons) OPERATING WEIGHT (lb) Unit Al/Al* Al/Cu* Cu/Cu* EconoMi$er IV EconoMi$er2 Roof Curb† Hot Gas Reheat Dehumidification Package COMPRESSOR Quantity...Model (Ckt 1, Ckt 2) Number of Refrigerant Circuits Loading (% of full capacity) Crankcase Heater Watts Oil (oz) (Ckt 1, Ckt 2) REFRIGERANT TYPE Expansion Device Operating Charge (lb) Circuit 1** Circuit 2 CONDENSER FAN Nominal Cfm Quantity...Diameter (in.) Motor Hp...
PHYSICAL DATA — 581A210-300 UNIT 581A NOMINAL CAPACITY (tons) OPERATING WEIGHT (lb) Al/Al COMPRESSOR Quantity Number of Refrigerant Circuits Oil (ounces) Ckt A...Ckt B...Ckt C REFRIGERANT TYPE Expansion Device Operating Charge (lb) Circuit A Circuit B Circuit C CONDENSER FAN Nominal Cfm (Total, all fans) Quantity...Diameter (in.) Motor Hp...Rpm Watts Input (Total) CONDENSER COIL Rows...Fins/in. Total Face Area (sq ft) EVAPORATOR FAN Quantity...
PHYSICAL DATA (cont) EVAPORATOR FAN DATA — 581A210-300 VERTICAL SUPPLY/RETURN UNITS 581A LOW RANGE Motor Hp Motor Nominal RPM Maximum Continuous Bhp Maximum Continuous Watts Motor Frame Size Motor Shaft Diameter (in.) Fan Rpm Range Motor Pulley Min. Pitch Diameter (in.) Motor Pulley Max. Pitch Diameter (in.) Blower Pulley Pitch Diameter (in.) Blower Pulley Shaft Diameter (in.) Blower Pulley Type Pulley Center Line Distance (in.) Belt, Quantity...Type...Length (in.
PHYSICAL DATA (cont) OPERATING AND RIGGING WEIGHTS — 581A155,180 BASE UNIT OPERATING WEIGHTS* UNIT 581A 155 lb 1725 180 kg 782 lb 1800 kg 816 *Base unit weight does not include electric heaters, copper coils, economizer, power exhaust, barometric relief or crating. See Options and Accessories table below for more information. NOTE: For 155 and 180 unit sizes add 75 lb (34 kg) for domestic crating. For export crating add 500 lb (227 kg).
155 180 UNIT 581A STD UNIT WEIGHT Lb Kg 1725 782 1800 816 ECONOMI$ER IV WEIGHT Lb Kg 90 41 90 41 CORNER A Lb Kg 407 185 417 189 CORNER C Lb Kg 383 174 481 218 CORNER D Lb Kg 410 186 503 228 mm 991 961 DIM A ft-in. 3-3 3- 2 Direction of airflow. Center of Gravity. mm 559 559 DIM C ft-in. 1-10 1-10 5. Ductwork to be attached to accessory roof curb only. 6. Minimum clearance: • Rear: 7′ -0″ (2134) for coil removal.
581A155-300 BASE UNIT DIMENSIONS — 581A210-300 a48-8206 202
CURB HEIGHT 1′ -2″ (305) 2′ -0″ (610) 2′ -0″ (610) CRRFCURB011A00 CRRFCURB012A00 581A155-300 PKG. NO. REF. CRRFCURB010A00 DESCRIPTION Standard Curb 14″ High Standard Curb for Units Requiring High Installation Side Supply and Return Curb for High Installation 581A155,180 Direction of airflow. 203 ALL UNIT in. .45 Deg. .28 A .28 Deg. B DIMENSIONS* (degrees and inches) .43 in. 5. Roof curb: 16 ga. (VA03-56) stl. 6.
ACCESSORY DIMENSIONS (cont) a48-7458 2" X 1/4 SUPPORT TYP. STITCH WELDED 3 1/2" FULLY INSULATED SUPPLY PLENUM 1" INSULATION 1 1/2 # DENSITY, STICK PINNED & GLUED 14 3/4" 23" 6" a48-7457 NOTE: CRRFCURB013A00 is a fully factory preassembled horizontal adapter and includes an insulated transition duct. The pressure drop through the adapter curb is negligible. For horizontal return applications: The power exhaust and barometric relief dampers must be installed in the return air duct.
ACCESSORY DIMENSIONS (cont) a48-4184 Factory-Installed Convenience Outlet 581A155-300 a48-6126 Factory-Installed Non-Fused Disconnect 205
581A155-300 ACCESSORY DIMENSIONS — 581A210-300 a48-8234 206
SELECTION PROCEDURE Calculate pressure drop: Design External Static Pressure 1.40 EconoMi$er IV 0.07 1.47 in. wg (ESP) Enter Fan Performance tables for 581A180 (low heat units) at 6,000 cfm and 1.47 in. wg. The rpm is 1228 and the Bhp is 4.73. The factory-installed 5 hp motor and alternate high-static drive are sufficient for this operation. V DETERMINE NET COOLING CAPACITIES. Cooling capacities are gross capacities and do not include indoor (evaporator) fan motor (IFM) heat.
PERFORMANCE DATA COOLING CAPACITIES — STANDARD UNITS 581A155 (12 Tons) Temp (F) Air Ent Cond TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 60 70 75 85 95 105 115 125 3600/0.01 54 152 152 7.56 148 148 8.5 146 146 9.02 142 142 10.1 138 138 11.4 134 134 12.7 129 129 14.2 124 124 15.8 58 156 144 7.65 152 141 8.58 150 139 9.1 145 136 10.2 141 133 11.4 136 129 12.8 130 125 14.2 125 121 15.8 62 161 135 7.74 156 133 8.67 154 132 9.18 149 129 10.3 143 127 11.5 138 124 12.
PERFORMANCE DATA (cont) COOLING CAPACITIES — STANDARD UNITS (cont) 581A180 (15 Tons) Temp (F) Air Ent Cond TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 60 70 75 85 95 105 115 125 4500/0.01 54 180.5 180.5 9.41 176.7 176.7 10.5 174.7 174.7 11.07 169.6 169.6 12.29 164.3 164.3 13.59 158.1 158.1 14.97 151.8 151.8 16.45 144.7 144.7 17.96 58 184.6 172.4 9.49 180.5 169 10.57 177.5 167.2 11.14 172.2 163.3 12.35 166.5 158.9 13.65 159.8 154.2 15.02 152.8 149.1 16.48 145.4 143.
PERFORMANCE DATA (cont) COOLING CAPACITIES — STANDARD UNITS (cont) 581A210 (18 Tons) Temp (F) Air Ent Cond TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 60 70 75 85 95 105 115 125 5400/0.05 54 202 202 10.2 197 197 11.4 195 195 12.1 190 190 13.5 184 184 15 178 178 16.6 171 171 18.4 164 164 20.2 58 206 193 10.3 202 189 11.5 199 187 12.2 193 183 13.5 187 179 15 180 173 16.7 172 168 18.4 165 162 20.3 62 211 184 10.4 206 181 11.5 203 180 12.2 196 177 13.6 190 173 15.
PERFORMANCE DATA (cont) COOLING CAPACITIES — STANDARD UNITS (cont) 581A240 (20 Tons) Temp (F) Air Ent Cond TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 60 70 75 85 95 105 115 125 6,000/0.04 54 235 235 11.5 231 231 13.1 228 228 13.9 223 223 15.6 216 216 17.4 208 208 19.3 200 200 21.3 191 191 23.5 58 242 224 11.6 237 220 13.2 234 218 14 227 213 15.7 219 208 17.5 211 202 19.4 202 195 21.4 192 188 23.5 62 248 212 11.7 242 209 13.3 239 208 14.1 231 204 15.8 223 200 17.
PERFORMANCE DATA (cont) COOLING CAPACITIES — STANDARD UNITS (cont) 581A300 (25 Tons) Temp (F) Air Ent Cond TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 60 70 75 85 95 105 115 125 7,500/0.05 54 287 287 15.5 279 279 17 275 275 17.9 267 267 19.8 259 259 22.1 253 253 24.9 246 246 28.1 238 238 31.6 58 296 274 15.7 286 267 17.2 281 264 18.1 272 257 19.9 263 251 22.2 256 246 25 249 240 28.2 240 234 31.7 62 304 261 15.9 293 255 17.3 287 252 18.2 277 247 20 267 242 22.
PERFORMANCE DATA (cont) COOLING CAPACITIES, UNITS WITH HOT GAS REHEAT OPTION 581A181 (15 TONS) UNIT WITH HOT GAS REHEAT IN COOLING MODE Air Entering Evaporator — Cfm/BF Temp (F) 4500/0.02 5250/0.03 6000/0.04 Air Entering Condenser Air Entering Evaporator — Ewb (F) (Edb) 57 62 67 72 57 62 67 72 57 62 67 72 57 TC 166 179 193 214 175 186 202 221 183 191 208 227 190 75 SHC 165 152 129 108 175 166 140 115 183 178 150 121 190 kW 10.4 10.6 10.7 10.9 10.5 10.6 10.8 11.0 10.6 10.7 10.9 11.1 10.
PERFORMANCE DATA (cont) COOLING CAPACITIES, UNITS WITH HOT GAS REHEAT OPTION (cont) 581A181 (15 TONS) UNIT WITH HOT GAS REHEAT — A AND B IN REHEAT, C ON Evaporator Air Quantity — Cfm/BF Temp (F) 4500/0.12 5250/0.14 6000/.015 Air Entering Condenser Evaporator Air — Relative Humidity (%) (Edb) 50 55 60 50 55 60 50 55 60 50 TC 133 140 146 134 141 147 135 142 148 136 65 SHC 73 69 65 75 71 67 77 73 69 79 kW 10.7 10.7 10.8 10.7 10.7 10.8 10.7 10.7 10.8 10.
PERFORMANCE DATA (cont) COOLING CAPACITIES, UNITS WITH HOT GAS REHEAT OPTION (cont) 581A210 (18 TONS) UNIT WITH HOT GAS REHEAT — A AND B IN REHEAT, C OFF Evaporator Air Quantity — Cfm/BF Temp (F) 5400/0.03 6300/0.04 7200/0.05 Air Entering Condenser Evaporator Air — Relative Humidity (%) (Edb) 50 55 60 50 55 60 50 55 60 50 TC 90 93 95 91 94 97 92 95 98 93 65 SHC 38 35 33 40 37 35 41 39 37 43 kW 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 TC 68 71 73 69 72 74 70 73 75 71 75 SHC 24 21 18 26 23 20 28 25 22 30 kW 9.
PERFORMANCE DATA (cont) COOLING CAPACITIES, UNITS WITH HOT GAS REHEAT OPTION (cont) 581A240 (20 TONS) UNIT WITH HOT GAS REHEAT — A IN REHEAT, B AND C OFF Evaporator Air Quantity — Cfm/BF Temp (F) 6000/0.04 7000/0.05 8000/0.06 Air Entering Condenser Evaporator Air — Relative Humidity (%) (Edb) 50 55 60 50 55 60 50 55 60 50 TC 73 75 77 73 76 78 74 76 79 75 65 SHC 45 42 40 47 44 42 49 47 44 51 kW 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 TC 55 57 59 56 58 60 56 58 60 57 75 SHC 29 25 22 31 27 24 33 30 26 35 kW 6.
PERFORMANCE DATA (cont) COOLING CAPACITIES, UNITS WITH HOT GAS REHEAT OPTION (cont) 581A300 (25 TONS) UNIT WITH HOT GAS REHEAT IN COOLING MODE Air Entering Evaporator — Cfm/BF Temp (F) 7000/0.042 8250/0.052 9500/0.062 Air Entering Condenser Air Entering Evaporator — Ewb (F) (Edb) 57 62 67 72 57 62 67 72 57 62 67 72 57 TC 245 268 293 318 259 282 303 333 274 291 314 340 289 75 SHC 245 229 197 162 259 254 213 173 274 271 230 183 289 kW 16.4 17.0 17.6 18.2 16.7 17.4 17.9 18.6 17.1 17.6 18.2 18.8 17.
PERFORMANCE DATA (cont) FAN PERFORMANCE — VERTICAL DISCHARGE UNITS 581A155 (12 TONS) WITH STANDARD MOTOR (Low Heat Units)* Available External Static Pressure (in. wg) 0.6 Bhp Rpm Watts Bhp Rpm 1.07 781 1150 1.33 858 1.21 800 1292 1.48 876 1.36 820 1442 1.64 895 1.54 840 1599 1.82 914 1.73 861 1765 2.01 934 1.94 884 1940 2.22 954 2.16 907 2125 2.45 974 2.41 931 2321 2.70 996 2.67 956 2528 2.97 1018 2.96 982 2748 3.26 1041 3.27 1008 2981 3.58 1065 0.
PERFORMANCE DATA (cont) FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 581A155 (12 TONS) WITH STANDARD MOTOR (High Heat Units)* Available External Static Pressure (in. wg) Airflow 0.2 0.4 0.6 (Cfm) Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm 3750 622 888 0.89 713 1027 1.13 795 1234 1.37 869 4000 652 1015 1.04 738 1168 1.28 818 1388 1.54 890 4250 682 1151 1.20 763 1317 1.45 841 1550 1.72 911 4500 713 1295 1.38 790 1474 1.63 864 1719 1.91 934 4750 744 1448 1.58 817 1641 1.84 889 1896 2.
PERFORMANCE DATA (cont) FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 581A180 (15 TONS) (Low Heat Units)* Airflow (Cfm) 4500 4800 5100 5700 6000 6300 6600 6900 7200 7500 Rpm 753 747 741 810 844 879 915 950 986 1022 0.2 Watts 1307 1384 1465 1911 2164 2439 2737 3057 3401 3770 Bhp 1.53 1.62 1.72 2.24 2.54 2.86 3.21 3.59 3.99 4.42 Rpm 761 790 820 882 914 947 980 1013 1047 1081 0.4 Watts 1330 1515 1718 2182 2444 2729 3035 3364 3717 4095 Available External Static Pressure (in. wg) 0.6 0.
PERFORMANCE DATA (cont) FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 581A180 (15 TONS) (High Heat Units)* Airflow (Cfm) 4500 4800 5100 5700 6000 6300 6600 6900 7200 7500 Rpm 753 747 775 849 886 924 962 1000 1038 1077 0.2 Watts 1307 1384 1571 2054 2329 2628 2951 3298 3672 4072 Bhp 1.53 1.62 1.84 2.41 2.73 3.08 3.46 3.87 4.31 4.78 Rpm 786 818 850 918 952 987 1023 1059 1095 1131 0.4 Watts 1404 1603 1822 2323 2607 2915 3246 3603 3986 4394 Available External Static Pressure (in. wg) 0.6 0.
PERFORMANCE DATA (cont) FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 581A210 (18 TONS) (Low Heat Units)* Airflow (Cfm) 3500 4000 4500 5000 5500 6000 6500 7000 7500 8000 8500 Rpm 460 499 538 579 621 664 707 751 795 839 884 0.2 Watts 591 774 990 1243 1536 1871 2250 2676 3150 3676 4253 Bhp 0.68 0.89 1.14 1.43 1.77 2.15 2.59 3.08 3.62 4.23 4.89 Rpm 548 581 617 654 693 732 772 813 855 897 940 0.4 Watts 774 976 1212 1485 1798 2152 2550 2994 3487 4029 4625 Available External Static Pressure (in. wg) 0.
PERFORMANCE DATA (cont) FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 581A210 (18 TONS) (Medium Heat Units)* Airflow (Cfm) 3500 4000 4500 5000 5500 6000 6500 7000 7500 8000 8500 Rpm 470 511 553 597 641 686 732 779 826 873 921 0.2 Watts 611 802 1029 1297 1606 1961 2363 2815 3320 3879 4495 Bhp 0.70 0.92 1.18 1.49 1.85 2.26 2.72 3.24 3.82 4.46 5.17 Rpm 556 591 629 669 709 751 794 837 882 926 972 0.4 Watts 791 1001 1248 1534 1862 2234 2653 3122 3642 4217 4847 Available External Static Pressure (in.
PERFORMANCE DATA (cont) FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 581A210 (18 TONS) (High Heat Units)* Airflow (Cfm) 3500 4000 4500 5000 5500 6000 6500 7000 7500 8000 8500 Rpm 470 511 553 597 641 686 732 779 826 873 921 0.2 Watts 611 802 1029 1297 1606 1961 2363 2815 3320 3879 4495 Bhp 0.70 0.92 1.18 1.49 1.85 2.26 2.72 3.24 3.82 4.46 5.17 Rpm 556 591 629 669 709 751 794 837 882 926 972 0.4 Watts 791 1001 1248 1534 1862 2234 2653 3122 3642 4217 4847 Available External Static Pressure (in.
PERFORMANCE DATA (cont) FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 581A240 (20 TONS) (Low Heat Units)* Airflow (Cfm) 5,000 5,500 6,000 6,500 7,000 7,500 8,000 8,500 9,000 9,500 10,000 Rpm 590 633 677 722 767 813 859 906 952 999 1047 0.2 Watts 1276 1579 1925 2317 2758 3250 3795 4394 5051 5767 6544 Bhp 1.47 1.82 2.21 2.67 3.17 3.74 4.36 5.05 5.81 6.63 7.53 Rpm 663 703 744 786 828 871 915 959 1004 1049 1094 0.
PERFORMANCE DATA (cont) FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 581A240 (20 TONS) (Medium Heat Units)* Airflow (Cfm) 5,000 5,500 6,000 6,500 7,000 7,500 8,000 8,500 9,000 9,500 10,000 Rpm 607 652 699 746 794 842 891 940 990 1039 1089 0.2 Watts 1329 1648 2013 2428 2895 3415 3992 4628 5325 6085 6911 Bhp 1.53 1.90 2.32 2.79 3.33 3.93 4.59 5.32 6.12 7.00 7.95 Rpm 677 719 763 807 851 897 943 990 1037 1085 1133 0.
PERFORMANCE DATA (cont) FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 581A240 (20 TONS) (High Heat Units)* Airflow (Cfm) 5,000 5,500 6,000 6,500 7,000 7,500 8,000 8,500 9,000 9,500 10,000 Rpm 607 652 699 746 794 842 891 940 990 1039 1089 0.2 Watts 1329 1648 2013 2428 2895 3415 3992 4628 5325 6085 6911 Bhp 1.53 1.90 2.32 2.79 3.33 3.93 4.59 5.32 6.12 7.00 7.95 Rpm 677 719 763 807 851 897 943 990 1037 1085 1133 0.
PERFORMANCE DATA (cont) FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 581A300 (25 TONS) (Low Heat Units)* Airflow (Cfm) 6,500 7,000 7,500 8,000 8,500 9,000 9,500 10,000 10,500 11,000 11,500 12,000 12,500 Rpm 750 797 845 892 939 986 1033 1079 1126 1172 1219 1265 1311 0.2 Watts 2,468 2,942 3,468 4,045 4,677 5,364 6,108 6,911 7,773 8,696 9,681 10,732 11,848 Bhp 2.84 3.38 3.99 4.65 5.38 6.17 7.03 7.95 8.94 10.00 11.13 12.34 13.63 Rpm 806 853 900 948 995 1042 1090 1137 1184 1232 1279 1326 — 0.
PERFORMANCE DATA (cont) FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 581A300 (25 TONS) (Medium Heat Units)* Airflow (Cfm) 6,500 7,000 7,500 8,000 8,500 9,000 9,500 10,000 10,500 11,000 11,500 12,000 12,500 Rpm 775 826 878 929 981 1033 1085 1137 1190 1242 1294 1347 — 0.2 Watts 2,600 3,115 3,690 4,326 5,029 5,799 6,640 7,553 8,542 9,609 10,756 11,985 — Bhp 2.99 3.58 4.24 4.98 5.78 6.67 7.64 8.69 9.82 11.05 12.37 13.78 — Rpm 825 875 925 975 1026 1076 1128 1179 1230 1282 1333 — — 0.
PERFORMANCE DATA (cont) FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 581A300 (25 TONS) (High Heat Units)* Airflow (Cfm) 6,500 7,000 7,500 8,000 8,500 9,000 9,500 10,000 10,500 11,000 11,500 12,000 12,500 Rpm 775 826 878 929 981 1033 1085 1137 1190 1242 1294 1347 — 0.2 Watts 2,600 3,115 3,690 4,326 5,029 5,799 6,640 7,553 8,542 9,609 10,756 11,985 — Bhp 2.99 3.58 4.24 4.98 5.78 6.67 7.64 8.69 9.82 11.05 12.37 13.78 — Rpm 825 875 925 975 1026 1076 1128 1179 1230 1282 1333 — — 0.
PERFORMANCE DATA (cont) FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 581A210 (18 TONS) (Low Heat Units)* Airflow (Cfm) 3,500 4,000 4,500 5,000 5,500 6,000 6,500 7,000 7,500 8,000 8,500 9,000 9,500 10,000 Rpm 0.2 Bhp Watts Rpm 0.4 Bhp 635 707 780 853 928 1003 1079 1155 1231 1308 1385 — — — 1064 1402 1802 2264 2794 3047 3812 4697 5714 6871 8177 — — — 1.22 1.61 2.07 2.60 3.21 3.50 4.38 5.40 6.57 7.90 9.
PERFORMANCE DATA (cont) FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 581A210 (18 TONS) (Medium Heat Units)* Airflow (Cfm) 3,500 4,000 4,500 5,000 5,500 6,000 6,500 7,000 7,500 8,000 8,500 9,000 9,500 10,000 Rpm 0.2 Bhp Watts Rpm 0.4 Bhp 645 718 792 867 943 1019 1096 1173 1250 1328 — — — — 1105 1454 1866 2343 2889 3177 3973 4894 5952 7153 — — — — 1.27 1.67 2.15 2.69 3.32 3.65 4.57 5.63 6.85 8.
PERFORMANCE DATA (cont) FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 581A210 (18 TONS) (High Heat Units)* Airflow (Cfm) 3,500 4,000 4,500 5,000 5,500 6,000 6,500 7,000 7,500 8,000 8,500 9,000 9,500 10,000 Rpm 0.2 Bhp Watts Rpm 0.4 Bhp 645 718 792 867 943 1019 1096 1173 1250 1328 — — — — 1105 1454 1866 2343 2889 3177 3973 4894 5952 7153 — — — — 1.27 1.67 2.15 2.69 3.32 3.65 4.57 5.63 6.85 8.
PERFORMANCE DATA (cont) FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 581A240 (20 TONS) (Low Heat Units)* Airflow (Cfm) 3,500 4,000 4,500 5,000 5,500 6,000 6,500 7,000 7,500 8,000 8,500 9,000 9,500 10,000 Rpm 0.2 Bhp Watts Rpm 0.4 Bhp 642 714 787 862 937 1013 1089 1166 1243 1320 1398 — — — 1082 1426 1831 2301 2838 3113 3893 4798 5837 7017 8350 — — — 1.24 1.64 2.11 2.65 3.26 3.58 4.48 5.52 6.71 8.07 9.
PERFORMANCE DATA (cont) FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 581A240 (20 TONS) (Medium Heat Units)* Airflow (Cfm) 3,500 4,000 4,500 5,000 5,500 6,000 6,500 7,000 7,500 8,000 8,500 9,000 9,500 10,000 Rpm 0.2 Bhp Watts Rpm 0.4 Bhp 652 725 800 875 952 1029 1106 1184 1262 1341 — — — — 1123 1479 1897 2383 2937 3249 4061 5003 6083 7312 — — — — 1.29 1.70 2.18 2.74 3.38 3.74 4.67 5.75 7.00 8.
PERFORMANCE DATA (cont) FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 581A240 (20 TONS) (High Heat Units)* Airflow (Cfm) 3,500 4,000 4,500 5,000 5,500 6,000 6,500 7,000 7,500 8,000 8,500 9,000 9,500 10,000 Rpm 0.2 Bhp Watts Rpm 0.4 Bhp 652 725 800 875 952 1029 1106 1184 1262 1341 — — — — 1123 1479 1897 2383 2937 3249 4061 5003 6083 7312 — — — — 1.29 1.70 2.18 2.74 3.38 3.74 4.67 5.75 7.00 8.
PERFORMANCE DATA (cont) FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 581A300 (25 TONS) (Low Heat Units)* Airflow (Cfm) 6,500 7,000 7,500 8,000 8,500 9,000 9,500 10,000 10,500 11,000 11,500 12,000 12,500 Rpm 0.2 Bhp Watts Rpm 0.4 Bhp 786 842 898 955 1012 1069 1127 1184 1242 1299 1357 — — 2,658 3,208 3,827 4,518 5,284 6,127 7,050 8,057 9,149 10,331 11,604 — — 3.06 3.69 4.40 5.20 6.08 7.05 8.11 9.27 10.52 11.88 13.
PERFORMANCE DATA (cont) FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 581A300 (25 TONS) (Medium Heat Units)* Airflow (Cfm) 6,500 7,000 7,500 8,000 8,500 9,000 9,500 10,000 10,500 11,000 11,500 12,000 12,500 Rpm 0.2 Bhp Watts Rpm 0.4 Bhp 799 856 913 971 1029 1087 1145 1203 1261 1320 1378 — — 2,730 3,294 3,929 4,637 5,421 6,285 7,231 8,262 9,381 10,592 11,896 — — 3.14 3.79 4.52 5.33 6.24 7.23 8.32 9.50 10.79 12.18 13.
PERFORMANCE DATA (cont) FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 581A300 (25 TONS) (High Heat Units)* Airflow (Cfm) 6,500 7,000 7,500 8,000 8,500 9,000 9,500 10,000 10,500 11,000 11,500 12,000 12,500 Rpm 0.2 Bhp Watts Rpm 0.4 Bhp 799 856 913 971 1029 1087 1145 1203 1261 1320 1378 — — 2,730 3,294 3,929 4,637 5,421 6,285 7,231 8,262 9,381 10,592 11,896 — — 3.14 3.79 4.52 5.33 6.24 7.23 8.32 9.50 10.79 12.18 13.
PERFORMANCE DATA (cont) ALTITUDE COMPENSATION — 581A210-300 (LP Gas) ELEVATION (ft) 0-2,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 above 10,000 a50-4028 ELEVATION (ft) 0-2,000 2,001-3,000 3,001-4,000 4,001-5,000 5,001-6,000 ALTITUDE COMPENSATION* — 581A155,180 (Natural Gas Units) NATURAL GAS ORIFICE SIZE† Low Heat High Heat 30 29 31 30 32 31 33 31 35 32 0-3,000 3,000- 7,000 7,000- 9,000 9,000-10,000 above 10,000 ALTITUDE COMPENSATION — 581A155,180 (LP Gas Units) MOTOR HORSEPOWER 3.0 2.9, 3.
PERFORMANCE DATA (cont) ACCESSORY/FIOP STATIC PRESSURE (in. wg)* — 581A155,180 COMPONENT 4500 0.040 EconoMi$er IV 5000 0.050 LEGEND FIOP — Factory-Installed Option 5400 0.060 6000 0.070 CFM 7200 0.090 7500 0.100 9000 0.110 10,000 0.120 11,250 0.140 *The static pressure must be added to external static pressure. The sum and the evaporator entering-air cfm should then be used in conjunction with the Fan Performance tables to determine blower rpm and watts.
PERFORMANCE DATA (cont) OUTDOOR SOUND POWER (TOTAL UNIT) UNIT 581A 155,180 210, 240 300 ARI ARI RATING (decibels) 88 82 85 OCTAVE BANDS A-WEIGHTED (db) 63 125 250 500 1000 2000 4000 8000 87.6 81.7 84.9 90.8 90.2 90.0 88.7 84.8 86.3 86.4 80.7 83.6 84.3 79.0 82.9 83.5 77.6 80.3 78.4 71.4 74.9 75.6 66.7 71.4 66.8 60.7 66.
PERFORMANCE DATA (cont) EVAPORATOR FAN MOTOR SPECIFICATIONS — 581A210-300 UNIT 581A DRIVE ORIENTATION Low Vertical High Vertical Low Horizontal High Horizontal Low Vertical High Vertical Low Horizontal High Horizontal Mid-Low Vertical Mid-High Vertical Mid-Low Horizontal Mid-High Horizontal 210 240 300 MOTOR P/N HD60FK651 HD60FK651 HD60FK651 HD58DL575 HD60FL650 HD60FL650 HD60FL650 HD60FL575 HD60FK651 HD60FK651 HD60FK651 HD58DL575 HD60FL650 HD60FL650 HD60FL650 HD60FL575 HD60FL65
ELECTRICAL DATA — 581A (cont) ELECTRICAL DATA — 581A155,180 UNIT 581A COMPRESSOR NOMINAL VOLTAGE OFM IFM RANGE No. 1 No. 2 VOLTAGE (3 Ph, 60 Hz) Min Max RLA LRA RLA LRA Qty Hp FLA (ea) Hp FLA 208/230 155 (Standard IFM) 155 (Optional IFM) 187 253 20.7 156 20.7 156 3 0.5 1.70 460 414 506 10.0 75 10.0 75 3 0.5 0.80 575 518 633 54 54 3 0.5 0.75 187 253 20.7 156 20.7 156 3 0.5 1.70 414 506 10.0 75 3 0.5 0.80 187 253 32.1 195 20.7 156 3 0.5 1.70 460 414 506 16.4 95 10.
ELECTRICAL DATA — 581A (cont) ELECTRICAL DATA — 581A210-300 WITHOUT CONVENIENCE OUTLET NOMINAL UNIT VOLTAGE 581A (3 Ph, 60 Hz) 208/230 210 460 575 208/230 VOLTAGE RANGE Min 187 414 518 187 Max 253 506 633 253 COMPRESSOR No. 2 No. 1 RLA 16.7 9 7 22.4 LRA 130 70 55 184 RLA 16.7 9 7 22.4 LRA 130 70 55 184 OFM No. 3 RLA 22.4 10.7 9.3 22.4 LRA 184 90 73 184 Qty 4 4 4 4 Hp IFM FLA (ea) 0.25 0.25 0.25 0.25 Hp 3.7 10.6/ 9.6 1.5 5 16.7/15.2 7.5 24.
ELECTRICAL DATA — 581A (cont) ELECTRICAL DATA — 581A210-300 WITH OPTIONAL CONVENIENCE OUTLET NOMINAL UNIT VOLTAGE 581A (3 Ph, 60 Hz) 208/230 210 460 575 208/230 VOLTAGE RANGE Min 187 414 518 187 Max 253 506 633 253 COMPRESSOR No. 2 No. 1 RLA 16.7 9 7 22.4 LRA 130 70 55 184 RLA 16.7 9 7 22.4 LRA 130 70 55 184 OFM No. 3 RLA 22.4 10.7 9.3 22.4 LRA 184 90 73 184 Qty 4 4 4 4 Hp IFM FLA (ea) 0.25 0.25 0.25 0.25 Hp 3.7 10.6/ 9.6 1.5 5 16.7/15.2 7.
TYPICAL WIRING SCHEMATICS — 581A LEGEND AHA C CAP CB CC CH CLO COMP CR DM DU EQUIP FPT FU GND HPS HS HV I IDM IFC IFM IGC L LOR LPS LS MGV OFC OFM PL PRI QT RS SW TB TC TH TRAN — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — Adjustable Heat Anticipator Contactor, Compressor Capacitor Circuit Breaker Cooling Compensator Crankcase Heater Compressor Lockout Compressor Motor Control Relay Damper Motor Dummy Terminal Equipment Freeze Protection Thermostat Fuse Ground High-Pressure
TYPICAL WIRING SCHEMATICS — 581A a48-7877 AL ECB IA IAQ — Ambient Limit — Economizer Control Board — Indoor Air — Indoor Air Quality LEGEND OA — OAS— RAS— SAT — Outdoor Air Outdoor Air Sensor Return Air Sensor Supply Air Temperature EconoMi$er IV Wiring — 581A155,180 4 3 7 RED 500 OHM RESISTOR 8 PINK 6 NOTE 1 BLUE RUN 5 OAT BLACK NOTE 2 1 10 50HJ540573 ACTUATOR ASSEMBLY 581A155-300 2 11 9 WHITE DIRECT DRIVE ACTUATOR a50-8058 12 ECONOMISER2 PLUG LEGEND OAT — Outdoor Air Temperature Sen
TYPICAL PIPING AND WIRING — 581A (581A155 Shown) LEGEND NEC — National Electrical Code b48-1258 581A155-300 249
579F/580F/581A155-300 GUIDE SPECIFICATIONS — 579F/580F180-300 AND 581A155,180 SIZE UNITS PACKAGED ROOFTOP ELECTRIC COOLING UNIT WITH GAS HEAT — CONSTANT VOLUME APPLICATION HVAC GUIDE SPECIFICATIONS SIZE RANGE: 13 AND 15 TONS (581A), 15 TO 25 TONS (579F, 580F), NOMINAL (COOLING) 230,000 TO 360,000 BTUH, NOMINAL (INPUT HEATING) (GAS UNITS) BRYANT MODEL NUMBERS: 580F, 579F, 581A PART 1 — GENERAL 1.
GUIDE SPECIFICATIONS — 579F/580F180-300 AND 581A155,180 SIZE UNITS (cont) G. H. I. J. K. L. the Energy Policy Act of 1992 (EPACT) effective October 24, 1997. N. Special Features: Certain features are not applicable when the features designated * are specified. For assistance in amending the specifications, contact your local Bryant Sales Office. 1. Coils: a.
GUIDE SPECIFICATIONS — 579F/580F180-300 AND 581A155,180 SIZE UNITS (cont) 579F/580F/581A155-300 * 2. Roof Curbs (Horizontal and Vertical): a. Formed of 16-gage galvanized steel with wood nailer strip and shall be capable of supporting entire unit weight. b. Permits installing and securing ductwork to curb prior to mounting unit on the curb. 3. Horizontal Adapter Roof Curb: Includes factory-assembled adapter and internal duct and substantially improves evaporator fan static performance (static regain).
GUIDE SPECIFICATIONS — 579F/580F180-300 AND 581A155,180 SIZE UNITS (cont) * * 20. 21. 22. 23. 24. 25. 26. 27. 28. 29. 30. 253 from outside the unit and shall provide power off lockout capability. Alternate Drive: Shall provide higher static drive capability to enhance evaporator-fan performance rpm range. Hail Guard, Condenser Coil Grille: Shall protect the condenser coil from hail, flying debris, and damage by large objects without increasing unit clearances.
GUIDE SPECIFICATIONS — 579F/580F180-300 AND 581A155,180 SIZE UNITS (cont) 33. Indoor Air Quality (CO2) Room Sensor (EconoMi$er IV): Sensor shall have the ability to provide demand ventilation control through the EconoMi$er IV. The IAQ sensor shall be wall mounted with an LED display in parts per million. The set point shall have adjustment capability. 34. Humidistat: Field-installed, wall-mounted humidistat is used to control activation of the dehumidification package.
GUIDE SPECIFICATIONS — 581A210-300 UNITS PACKAGED ROOFTOP ELECTRIC COOLING UNIT WITH GAS HEAT — CONSTANT VOLUME APPLICATION HVAC GUIDE SPECIFICATIONS SIZE RANGE: 18 TO 25 TONS NOMINAL (COOLING) 250,000 TO 400,000 BTUH, NOMINAL (INPUT HEATING) BRYANT MODEL NUMBERS: 581A PART 1 — GENERAL 1.
581A210-300 GUIDE SPECIFICATIONS — 581A210-300 UNITS (cont) 3. Optional pre-coated aluminum-fin coils shall have a durable epoxy-phenolic coating to provide protection in mildly corrosive coastal environments. Coating shall be applied to the aluminum fin stock prior to the fin stamping process to create an inert barrier between the aluminum fin and copper tube. Epoxyphenolic barrier shall minimize galvanic action between dissimilar metals. 4.
GUIDE SPECIFICATIONS — 581A210-300 UNITS (cont) * 3. * 4. * 5. * 6. 7. 8. 9. 10. 11. 257 o. Compressor lockout sensor (opens at 35 F, closes at 50 F). p. Actuator shall be direct coupled to economizer gear, eliminating linkage arms and rods. q. Control LEDs: 1) When the outdoor air damper is capable of providing free cooling, the “Free Cool” LED shall illuminate. 2) The IAQ LED indicates when the module is on the DCV mode. 3) The EXH LED indicates when the exhaust fan contact is closed. r.
GUIDE SPECIFICATIONS — 581A210-300 UNITS (cont) 12. Return Air Smoke Detector: The smoke detector shall send input to the controller to shut down the unit in case smoke is detected. The smoke detector shall be factory installed in the return air section or shall be available as a field-installed accessory. 13. Two-Position Damper: The damper shall admit up to 25% outdoor air and shall close upon shutdown. The package shall include a single-blade damper and motor. 14.
CONTROLS If there is a further demand for cooling (cooling second stage — Y2 is energized), then the control will bring on compressor stage 1 to maintain the mixed-air temperature set point. The EconoMi$er IV damper will be open at maximum position. EconoMi$er IV operation is limited to a single compressor. Heating, Units With Economizer NOTE: The units have 2 stages of heat. When the thermostat calls for heating, power is sent to W1 on the IGC (integrated gas unit controller) board.
CONTROLS (cont) Heating, Units Without Economizer — When the thermostat calls for heating, power is sent to W on the IGC (integrated gas unit controller) board. An LED (light-emitting diode) on the IGC board will be on during normal operation. A check is made to ensure that the rollout switch and limit switch are closed. The induced-draft motor is then energized, and when speed is proven with the hall effect sensor on the motor, the ignition activation period begins.
CONTROLS (cont) from the thermostat energizes compressor contactor C1 (B1 on 300 units). Heating, Units Without Economizer NOTE: The 581A210-300 units have 2 stages of heat. When the thermostat calls for heating, power is sent to W on the IGC (integrated gas unit controller) board. An LED (lightemitting diode) on the IGC board will be on during normal operation. A check is made to ensure that the rollout switch and limit switch are closed and the induced-draft motor is running.
CONTROLS (cont) induced-draft motor is then energized, and when speed is proven with the hall effect sensor on the motor, the ignition activation period begins. The burners will ignite within 5 seconds. If the burners do not light, there is a 22-second delay before another 5-second attempt. If the burners still do not light, this sequence is repeated for 15 minutes. After the 15 minutes have elapsed, if the burners still have not lit, heating is locked out.
APPLICATION DATA 45 F for aluminum heat exchangers. This temperature setting will bring on the second stage of heat whenever the ambient temperature is below the thermostat set point. Indoor comfort may be compromised when heating is initiated using low entering air temperatures with insufficient heating temperature rise. 1. CONDENSATE DRAIN PAN — A sloped condensate drain pan is supplied on all units. The condensate pan must be externally trapped.
APPLICATION DATA (cont) CONCENTRIC DUCT DISTRIBUTION CONCENTRIC DUCT DETAILS 6'-2 3/8'' MAX. 5'-9 3/16'' MAX. 1'-10 11/16'' MAX. 5 3/16'' 4'-6 13/16'' 1'-0 3/16'' 1'-7 15/16'' 1'-0 3/16'' B B 24'' MIN. A A a50-530 a48-7482 BAFFLE Shaded area indicates block-off panels. NOTE: Do not drill in this area, damage to basepan may result in water leak. NOTE: Dimensions A, A′ and B, B′ are obtained from field-supplied ceiling diffuser.
APPLICATION DATA (cont) b. CONTROL FEATURES — The EconoMi$er IV controller provides superior functionality for rooftop unit operation. EconoMi$er IV control features are included as follows: Remote Minimum Position — The EconoMi$er IV controller can be used with a field-supplied and fieldinstalled remote minimum position control switch that will enable and disable the EconoMi$er IV to open or close the damper beyond the minimum position for modified ventilation, providing 2 to 10 vdc output.
APPLICATION DATA (cont) 46 85 90 95 100 105 110 (29) (32) (35) (38) (41) (43) 44 CONTROL CONTROL POINT CURVE APPROX.
INDEX 579F180-300 section 144-171, 250-254 580F036-151 section 20-82, 139-143 580F180-300 section 172-196, 250-254 581A155-300 section 197-258 581B036-150 section 83-143 Airflow Configuration 263 Maximum 263 Minimum 263 Altitude compensation 579F180-300 163,164 580F036-151 71 580F180-300 190 581A155-300 240 581B036-150 127 Altitude derating factor 71, 127, 163, 190, 240 Application data 263-266 ARI capacity ratings 579F180-300 12 580F036-151 8, 9 580F180-300 13 581A155-300 14, 15 581B036-150 10, 11 Barometr
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Copyright 2006 Bryant Heating & Cooling Systems Printed in U.S.A. 6/06 Catalog No.