Instruction manual

condensate connection to ensure proper drainage. Make sure that
the outlet of the trap is at least 1 in. lower than the drain-pan
condensate connection to prevent the pan from overflowing. Prime
the trap with water. When using a gravel apron, make sure it slopes
away from the unit.
If the installation requires draining the condensate water away
from the unit, install a field-supplied 2 -in. trap at the condensate
connection to ensure proper drainage. Condensate trap is available
as an accessory or is field-supplied. Make sure that the outlet of the
trap is at least 1 in. lower than the unit drain-pan condensate
connection to prevent the pan from overflowing. Connect a drain
trough using a minimum of field-supplied 3/4-in. PVC or field-
supplied 3/4-in. copper pipe at outlet end of the 2-in. trap. (See Fig.
12) Do not undersize the tube. Pitch the drain trough downward at
a slope of at least 1 in. every 10 ft. of horizontal run. Be sure to
check the drain trough for leaks. Prime the trap at the beginning of
the cooling season start-up.
VII. INSTALL ELECTRICAL CONNECTIONS
WARNING: The unit cabinet must have an uninter-
rupted, unbroken electrical ground to minimize the pos-
sibility of personal injury if an electrical fault should
occur. This ground may consist of an electrical wire
connected to the unit ground lug in the control compart-
ment, or conduit approved for electrical ground when
installed in accordance with NEC, ANSI/NFPA Ameri-
can National Standards Institute/National Fire Protection
Association (latest edition) (in Canada, Canadian Electri-
cal Code CSA C22.1) and local electrical codes. Failure
to adhere to this warning could result in serious injury or
death.
Fig. 6Unit Leveling Tolerances
C99065
A
B
C
MAXIMUM ALLOWABLE
DIFFERENCE (in.)
A-B B-C A-C
1/4 1/4 1/4
Fig. 7Slab Mounting Detail
C99096
OPTIONAL
RETURN
AIR
OPENING
OPTIONAL
SUPPLY
AIR
OPENING
EVAP. COIL COND. COIL
2"
Fig. 8Threading Belt
C99067
HANDHOLD
FEED
HOOK
Fig. 9Suggested Rigging
UNIT MAXIMUM WEIGHT A B
Size lb kg in. mm. in. mm.
602B024 321 145.6 19.0 482.6 18.25 463.6
602B030 342 155.2 20.0 508 19.25 489
602B036 350 158.8 20.0 508 19.0 482.6
602B042 372 168.8 21.0 533.4 20.5 520.7
602B048 377 171.0 20.0 508 21.25 539.8
602B060 450 204.2 21.0 533.4 20.0 508.0
C99075
PLACE RIGGING BRACKET ASSEMBLY IN 4
HAND HOLES AND INSTALL TIE DOWN STRAP
AROUND PERIMETER OF UNIT AND THROUGH
SPACE IN BRACKET ASSEMBLY
INSTALL SAFETY STRAPS TO
RIGGING CLEVIS AT 4 RIGGING BRACKETS
TIGHTEN STRAPPING SECURELY
WITH TENSION BUCKLE
SEE DETAIL A
DETAIL A
SCALE 0.250
914-137"
(36"-54")
“A”
“B”
7