User's Manual

65
Table 20—Two--Stage Compressor Resistances
(Winding Resistance at 70_F±20_)
Winding 286BNA024 286BNA036 286BNA048 286BNA060
Start (S--C) 1.40 1.29 1.52 0.60
Run (R--C) 1.32 0.89 0.64 0.49
Status Codes
Table 21 shows the status codes flashed by the amber status light.
Most system problems can be diagnosed by reading the status code
as flashed by the amber status light on the control board.
The codes are flashed by a series of short and long flashes of the
status light. The short flashes indicate the first digit in the status
code, followed by long flashes indicating the second digit of the
error code.
The short flash is 0.25 seconds ON and the long flash is 1.0 second
ON. Time between flashes is 0.25 seconds. Time between short
flash and first long flash is 1.0 second. Time between code
repeating is 2.5 seconds with LED OFF.
EXAMPLE:
3 short flashes followed by 2 long flashes indicates a 32 code.
Table 21 shows this to be low pressure switch open.
Table 21—TROUBLESHOOTING
OPERATION FAUL T
AMBER
LED
FLASH
CODE
POSSIBLE CAUSE AND ACTION
Standby no call for unit operation None
On solid,
no flash
Normal operation
Low Stage Cool/Heat Operation None 1, pause Normal operation
High Stage Cool/Heat Operation None 2, pause Normal operation
System C ommu-
nications Failure
16
Communication with User Interface lost. Check wiring to UI, indoor and
outdoor units
Invalid Model Plug 25
Control does not detect a model plug or detects an invalid model plug. Unit
will not operate without correct model plug.
High Pressure
Switch Open
31*
High--- pressure switch trip. Check refrigerant charge, outdoor fan operation
and coils for airflow restrictions.
Low Pressure
Switch Open
32* Low ---pressure switch trip. Check refrigerant charge and indoor air flow .
Control Fault 45 Outdoor unit control board has failed. Control board needs to be replaced.
Brown Out (230v) 46
Line voltage < 187v for at least 4 seconds. Compressor and fan operation
not allowed until voltage>
190v. Verify line voltage.
No 230v at U nit
Measured at L1
and L2 on circuit
board
47
There is no 230v at the contactor when indoor unit is powered and cooling/
heating demand exists. Verify the disconnect is closed and 230v wiring is
connected to the unit.
Outdoor Air Temp
Sensor Fault
53
Outdoor a ir sensor not reading or out of range. Ohm out sensor and check
wiring.
Outdoor Coil
Sensor Fault
55 Coil sensor not reading or out of range. Ohm out sensor and check wiring.
Thermistors out of
range
56
Improper relationship between coil sensor and outdoor air sensor. Ohm out
sensors and check wiring.
Low Stage
Thermal Cutout
71*
Compressor operation detected then disappears while low stage demand
exists. Possible causes are internal compressor overload trip or start relay
and capacitor held in circuit too long (if installed).
High Stage
Thermal Cutout
72*
Compressor operation detected then disappears while high stage demand
exists. Possible causes are internal compressor overload trip or start relay
and capacitor held in circuit too long (if installed).
Contactor Shorted 73*
Compressor voltage sensed when no demand for compressor operation
exists. Contactor may be stuck closed or there is a wiring error.
No 230V at
Compressor (289B
Only)
74
Compressor voltage not sensed when compressor should be starting. Con-
tactor may be stuck open or there is a wiring error.
Low Stage
Thermal Lockout
81
Thermal cutout occurs in three consecutive low/high stage cycles. Low
stage locked out for 4 hours or until 24v power recycled.
High Stage
Thermal Lockout
82
Thermal cutout occurs in thr ee consecutive high/low stage cycles. High
stage locked out for 4 hours or until 24v power recycled.
L o w --- P r e s s u r e
Lockout
83
Low pressure switch trip has occurred during 3 consecutive cycles. Unit
operation locked out for 4 hours or until 24v power recycled.
H i g h --- P r e s s u r e
Lockout
84
High pressure switch trip has occurred during 3 consecutive cycles. Unit
operation locked out for 4 hours or until 24v power recycled.
* Sequence: Compressor contactor is de---energized and outdoor fan is energized for up to 15 minu tes. If demand still exists, control will energize
compressor contactor after 15 minute delay. If fault is cleared, unit will resume operation. If fault still exists, fan shuts off, and error code continues to flash.
Control will attempt re---start every 15 minutes. Cycling low voltage defeats the 15 minute delay.