Owner’s Manual Liquid-cooled, Prepackaged Standby Generators Model Number: ASPAS1BBL015 ! Not intended for use in critical life support applications. ! ONLY QUALIFIED ELECTRICIANS OR CONTRACTORS SHOULD ATTEMPT INSTALLATION!! DEADLY EXHAUST FUMES. OUTDOOR INSTALLATION ONLY! This manual should remain with the unit.
INTRODUCTION Thank you for purchasing a Bryant home standby generator system. Every effort was expended to make sure that the information and instructions in this manual are both accurate and current at the time the manual was written. However, the manufacturer reserves the right to change, alter or otherwise improve this product(s) at any time without prior notice.
Table of Contents Bryant Liquid-cooled 15 kW Generators INTRODUCTION ..................................IFC SAFETY RULES ......................................2 Section 3 — OPERATION....................12 3.1 Control Console Components......................12 3.2 Manual Transfer and Startup ......................13 Section 1 — GENERAL INFORMATION..................4 3.3 Automatic Operation ..................................13 3.4 Weekly Exercise Cycle..................................13 1.
IMPORTANT SAFETY INSTRUCTIONS Bryant Liquid-cooled 15 kW Generators ! SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe operation be copied and posted in potential hazard areas. Safety should be stressed to all operators, potential operators, and service and repair technicians for this equipment. ! SAVE THESE INSTRUCTIONS – This manual contains important instructions that should be followed during installation and maintenance of the generator and batteries.
IMPORTANT SAFETY INSTRUCTIONS Bryant Liquid-cooled 15 kW Generators • • • • • • • • • place before operating the generator. If work must be done around an operating unit, stand on an insulated, dry surface to reduce shock hazard. Do not handle any kind of electrical device while standing in water, while barefoot, or while hands or feet are wet. DANGEROUS ELECTRICAL SHOCK MAY RESULT.
Section 1 - General Information Bryant Liquid-cooled 15 kW Generators 1.1 GENERATOR 1.3 This equipment is a liquid-cooled, engine-driven generator set. The generator is designed to supply electrical power that operates critical electrical loads during utility power failure. The unit has been factory-installed in a weather resistant, all metal enclosure and is intended for outdoor installation only.
Section 1 - General Information Bryant Liquid-cooled 15 kW Generators 1.6 GENERATOR FUEL SYSTEM The generator has been factory tested and adjusted using a natural gas fuel system. If propane (LP requirements) gas is preferred, refer to Section 1.12. Recommended fuels should have a Btu content of at least 1,000 Btus per cubic foot for natural gas and at least 2,520 Btus per cubic foot for LP gas. Ask the fuel supplier for the Btu content of the fuel being used. 1.7.
Section 1 — General Information Bryant Liquid-cooled 15 kW Generators • LED 3 is GREEN. This LED will flash when the circuit board has load voltage available to it. This LED will function when voltage is available across T1 and T2. Figure 1.6 - Low Coolant Level Sensor 1.7.6 OVERCRANK SHUTDOWN After 90 seconds of crank-rest cycles, this function ends cranking if the engine fails to start in that 90-second span. 1.7.6 1.7.
Section 1 — General Information Bryant Liquid-cooled 15 kW Generators 1.10.2 ENGINE SPECIFICATIONS Make..............................................................................Mitsubishi Displacement ..............................................92 inches3 (1.5 liters) Cylinder Arrangement......................................................4, in-line Valve Arrangement................................................Overhead Cam Firing Order...........................................................
Section 2 — Installation Bryant Liquid-cooled 15 kW Generators 1.14 ENGINE OIL RECOMMENDATIONS 1.16 BEFORE INSTALLATION The unit has been filled with 15W-40 engine oil at the factory. Use a high-quality detergent oil classified “For Service SJ or latest available.” Detergent oils keep the engine cleaner and reduce carbon deposits.
Section 2 — Installation Bryant Liquid-cooled 15 kW Generators NOTE: It is essential to use the latest version of any standard to ensure correct and current information. • NFPA No. 37, STATIONARY COMBUSTION ENGINES AND GAS TURBINES. • NFPA No. 76A, ESSENTIAL ELECTRICAL SYSTEMS FOR HEALTH CARE FACILITIES. • NFPA No. 220, STANDARD TYPES OF BUILDING CONSTRUCTION • NFPA No. 68, GUIDE FOR EXPLOSION VENTING • NFPA No. 70, NATIONAL ELECTRICAL CODE. • NFPA No. 30, FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE. • NFPA No.
Section 2 — Installation Bryant Liquid-cooled 15 kW Generators 2.5 EMERGENCY CIRCUIT ISOLATION METHOD This prevents overloading the generator by keeping electrical loads below the wattage/amperage capacity of the generator. If the generator is powering only critical loads, within the wattage/amperage capacity, during utility power outages, consider using the emergency circuit isolation method.
Section 2 — Installation Bryant Liquid-cooled 15 kW Generators 2.10 BATTERY INSTALLATION DANGER ! Standby generators installed with automatic transfer switches will crank and start automatically when NORMAL (UTILITY) source voltage is removed or is below an acceptable preset level. To prevent such automatic start-up and possible injury to personnel, do not connect battery cables until the NORMAL source voltage at the transfer switch is correct and the system is ready to be put into operation.
Section 3 — Operation Bryant Liquid-cooled 15 kW Generators Before starting the generator for the first time, the installer must complete the following procedures. For follow-up maintenance information and/or service intervals, please refer to Section 4, “Maintenance.” 2.11.2 TRANSFER SWITCH If this generator is used to supply power to any electrical system normally powered by an electric utility, the National Electrical Code requires that a transfer switch be installed.
Section 3 - Operation Bryant Liquid-cooled 15 kW Generators 3.1.2 FAULT INDICATOR LAMP The lamp goes ON when one or more of the following engine faults occurs and when engine shuts down. • Low oil pressure • High coolant temperature • Low coolant level 3.1.3 • Overcrank • Overspeed 15 AMP FUSE The fuse protects the control console’s DC control circuit against electrical overload. If the fuse has melted open because of an overload, engine cranking and startup cannot occur.
Section 4 — Maintenance Bryant Liquid-cooled 15 kW Generators 4.1 MAINTENANCE PERFORMED BY AUTHORIZED SERVICE FACILITIES The exhaust system parts from this product get extremely hot and remains hot after shutdown. High grass, weeds, brush, leaves, etc. must remain clear of the exhaust. Such materials may ignite and burn from the heat of the exhaust system. A. EVERY THREE MONTHS 1.Check battery state of charge and condition. 2.Inspect and test fuel system. 3.Check transfer switch. 4.
Section 4 — Maintenance Bryant Liquid-cooled 15 kW Generators 4.4.2 BATTERY FLUID 4.5.7 INSPECT EXHAUST SYSTEM Check battery electrolyte fluid at least once a month. Fluid should cover separators in all battery cells. If fluid level is low, add distilled water to cover tops of separators. DO NOT USE TAP WATER IN BATTERY. Inspect the exhaust system at least once every three months. Check all exhaust system pipes, mufflers, clamps, etc. for condition, tightness, leaks, security, damage. 4.4.
Section 4 — Maintenance Bryant Liquid-cooled 15 kW Generators Figure 4.2 - Oil Filter 4.5.12 SPARK PLUGS Reset the spark plug gap or replace the spark plugs as necessary. See Section 4.7. OIL FILTER 1. Clean the area around the base of the spark plugs to keep dirt and debris out of the engine. Clean by scraping or washing using a wire brush and commercial solvent. Do not blast the spark plugs to clean. 2. Remove the spark plugs and check the condition.
Section 4 — Maintenance Bryant Liquid-cooled 15 kW Generators Finally, have the insulation resistance of stator and rotor windings checked. If insulation resistances are excessively low, the generator may require drying. 4.6.2 DANGER Storage batteries give off explosive hydrogen gas. This gas can form an explosive mixture around the battery for several hours after charging. The slightest spark can ignite the gas and cause an explosion.
Section 4 — Maintenance Bryant Liquid-cooled 15 kW Generators 4.7 SCHEDULED MAINTENANCE The following is a recommended maintenance schedule for small standby and residential generator sets. The established intervals in the schedule are the maximum recommended when the unit is used in an average service application. They will need to be decreased (performed more frequently) if the unit is used in a severe application.
Section 4 — Maintenance Bryant Liquid-cooled 15 kW Generators Maintenance Tasks Level 1 Recommended to be done monthly/ 10 hrs. Level 2 Task Comp. (DateInitials) Required to be done 3 months/ Break-in 30 hrs. Level 3 Task Comp. (DateInitials) Required to be done Semiannually/ 50 hrs. Level 4 Task Comp. (DateInitials) Required to be done Annually/ 100 hrs. Task Comp. (DateInitials) 1. Disable the unit from operating per the first page warning. 2. Check the engine oil level. Adjust as necessary. 3.
Section 4 — Maintenance Bryant Liquid-cooled 15 kW Generators Maintenance Tasks 13. Initiate an automatic start and transfer of the unit to site load and exercise it for at least 1 hour looking for leaks, loose connections or components, and abnormal operating conditions. Correct as necessary. 14. Start and exercise the unit at full rated load (use a load bank if the site load is not enough) for at least 2 hours looking for leaks, loose connections or components, and abnormal operating conditions.
Section 5 — Troubleshooting Bryant Liquid-cooled 15 kW Generators 5.1 TROUBLESHOOTING POINTS PROBLEM CAUSE CORRECTION Engine won’t crank. 1. 15 amp fuse blown. 2. 7.5 amp fuse blown. 3. Loose or corroded or defective battery cables. 4. Defective starter contactor. 5. Defective starter motor. 6. Dead or Defective Battery. 1. Replace fuse. 2. Replace fuse. 3. Tighten, clean or replace battery cables as necessary. 4. Replace contactor. 5. Replace starter motor. 6. Remove, change or replace battery.
Section 6 — Notes Bryant Liquid-cooled 15 kW Generators 22 Bryant
Section 7 - Installation Diagram Bryant Liquid-cooled 15 kW Generators Drawing No.
Section 8 - Electrical Data Bryant Liquid-cooled 15 kW Generators Wiring Diagram — Control Panel —Drawing No. 0F5243 225A BLUE 178 239 225A BLUE SW1 5 6 7 B SW2 N.C.
EC CB1 22 5 00 AS 33 2 2 RED AR CB2 85 14 0 56 13 229 4 1 E2 44 162 6 RED S15 BLACK 2 1 5 6 162 S15 VR 4 229 RED BLACK BLUE BLUE 14 T1 17 2 85 5 7 T2 16 PCB 56 14 11 BROWN BLACK ORANGE YELLOW D 239 RED 14 9 178 239 23 176 15E 183 TO GOV ACTUATOR 194 E 4 3 15 15C 10 12 178 13 PCB - CIRCUIT BOARD CONTROLLER SA - SUPRESSION ASSEMBLY SW1 - AUTO/OFF/MANUAL SWITCH SW2 - SET EXERCISE SWITCH TR1 -TRANSFORMER, UTILITY SENSING TS1,2,3 - TERMINAL BOARDS
Section 8 - Electrical Data Bryant Liquid-cooled 15 kW Generators Wiring Diagram — 1.5L Engine — Drawing No.
Section 8 - Electrical Data Bryant Liquid-cooled 15 kW Generators Electrical Schematic — 1.5L Engine — Drawing No.
Section 9 - Exploded Views and Parts Bryant Liquid-cooled 15 kW Generators Governor Assembly — Drawing No. 0E1331-B 5 4 3 ITEM (13) NEOPRENE COATING 2 1 14 6 7 10 WIRE HARNESS 15 12 9 7 16 "A" 17 TO "A" 10 7 CARBURETOR ARM (REF.) 6 INTAKE MANIFOLD (REF.) 11 ITEM 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 PART NO. 098290 098941A 098958A 098942A 098225 043146 022097 084543A 098783 037398 0E1326 0A7106 074031 029333A 022507 022473 064526 0E1694 28 Bryant QTY.
Section 9 - Exploded Views and Parts Bryant Liquid-cooled 15 kW Generators Mounting Base — Drawing No. 0E0768-B 8 7 6 14 5 13 7 6 4 9 15 6 10 15 20 5 7 6 11 17 18 16 2 3 9 10 22 1 15 20 22 ITEM 1 2 3 4 5 6 7 8 9 10 11 13 14 15 16 17 18 19 20 21 22 PART NO. 0D8656 027482 070936 070936C 039253 022145 022129 045771 071956 051730 021991 0D9335 0D9336 0C2454 047411 022097 022473 055414 049813 026850 0A1694 QTY. 1 2 2 2 8 12 16 4 4 4 1 2 2 16 1 1 1 1 5 1 2 DESCRIPTION BASE MOUNTING 1.
Section 9 - Exploded Views and Parts Bryant Liquid-cooled 15 kW Generators Enclosure — Drawing No. 0F4490 WELD STUD UNDER ROOF PANEL FOR ACCESS ER CABLE 21 1 11 8 13 2 15 4 "Y" 26 10 12 29 22 23 20 26 10 17 11 18 15 8 24 11 4 5 9 26 26 17 6 25 26 24 19 17 10 7 11 30 Bryant 24 3 NOTE: USE DOOR LATCH FASTENER TO SECURE GROUND WIRE. NOTE: USE LOCTITE ON NUTS ITEM #26.
Section 9 - Exploded Views and Parts Bryant Liquid-cooled 15 kW Generators Enclosure — Drawing No. 0F4490 ITEM 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 PART NO. 0D8666 0D8664C 0D8657 0D8660 0A7568 0D8659 0D8662 0D8661 0D8658 067042 0C2454 033530 051716 022152 0912970064 023762 0912970063 022264 067035 022127 0F4487A 022473 022097 0D2023 0F3390 037337 0D2023 0D8664A 0D8664B QTY.
25 26 27 10 8 5 31 55 54 9 53 52 TO 'A' 3 50 34 42 38 49 39 40 41 12 28 11 2 30 31 57 17 28 28 18 26 16 51 29 13 P/N 0E1 38 23 39 40 'A' 24 41 0 28 0 29 56 14 0 32 Bryant 15 22 35 4 33 6 7 1 28 43 45 44 46 47 32 32 37 39 36 40 41 48 4 Section 9 - Exploded Views and Parts Bryant Liquid-cooled 15 kW Generators Control Panel — Drawing No.
Section 9 - Exploded Views and Parts Bryant Liquid-cooled 15 kW Generators Control Panel — Drawing No. 0F5240 ITEM PART NO. QTY.
6 34 Bryant 8 7 2 9 10 5 11 12 24 4 13 14 39 10 41 15 1 24 32 30 42 16 24 4 72 14 1 10 9 24 35 34 33 11 45 10 44 11 14 19 10 24 36 17 11 20 10 11 14 12 47 17 26 46 18 11 49 71 14 10 21 20 70 11 57 22 6 24 25 69 29 67 56 59 58 63 65 54 64 52 61 7 WATERPUMP HARDWARE 62 60 Section 9 - Exploded Views and Parts Bryant Liquid-cooled 15 kW Generators Engine — Drawing No.
Section 9 - Exploded Views and Parts Bryant Liquid-cooled 15 kW Generators Engine — Drawing No. 0F5273 ITEM PART NO. QTY.
28 22 36 Bryant 11 28 "A" 15 16 (BOTTOM ONLY) 1 10 "A" 2 21 9 11 13 23 27 26 5 10 8 8 8 8 3 14 12 12 24 18 TO THERMOSTAT ADAPTER 14 WATER INLET TUBE (ON BLOCK) 19 20 7 6 4 17 17 6 7 Section 9 - Exploded Views and Parts Bryant Liquid-cooled 15 kW Generators Radiator — Drawing No.
Section 9 - Exploded Views and Parts Bryant Liquid-cooled 15 kW Generators Radiator — Drawing No. 0F5274 ITEM 1 2 3 4* 5 6 7 8 9 10 11 12 13 14 15 16 17 * 18 19 20 21 22 23 24 26 27 28 PART NO. 0D8657 0A5734 0A6237 0A6238 047290A 065852 0A2111 099502 083709 052250 0A7275 022097 035461 022473 0E0726 076749 075443 056892 0A6284 0A6258 029032 031669 060035 022127 046627 0C7649 0C2454 QTY. 1 1 1 1 1 2 2 4 1 2 3 4 1 7 1 1 6 4 1 1 1 4 4 4 1 1 4 DESCRIPTION SUPPORT RADIATOR 1.5L MITSU RADIATOR 1.5L VENTURI 1.
Section 9 - Exploded Views and Parts Bryant Liquid-cooled 15 kW Generators Fuel System — Drawing No. 0E0774-E 18 13 8 21 24 25 22 17 "C" 16 29 "C" 14 30 12 34 31 36 37 35 32 33 38 39 19 40 1 26 20 6 28 PORT "OUT 1" (NATURAL GAS) 41 6 11 43 9 1 10 42 "D" 23 40 41 PORT "OUT 2" 6 2 3 15 11 4 L.P.
Section 9 - Exploded Views and Parts Bryant Liquid-cooled 15 kW Generators Fuel System — Drawing No. 0E0774-E ITEM PART NO.
Section 9 - Exploded Views and Parts 14 15 2 18 9 To Blower Housing 8 36 32 24 1 23 35 17 7 13 16 29 28 33 22 10 30 21 3 31 12 21 20 19 6 5 4 26 To Engine Crankshaft Bryant Liquid-cooled 15 kW Generators Alternator — Drawing No.
Section 9 - Exploded Views and Parts Bryant Liquid-cooled 15 kW Generators Alternator — Drawing No. 0A9348-F ITEM 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 26 * 27 28 29 30 31 32 33 35 36 PART NO.
Section 9 - Exploded Views and Parts Bryant Liquid-cooled 15 kW Generators Battery — Drawing No. 0E0770-B 2 STARTER SOLENOID 8 13 4 14 8 3 1 TO ENGINE BLOCK 16 6 5 7 9 15 ITEM 1 2 3 4 5 6 7 8 9 13 14 15 16 17 PART NO. 077483 038804D 038805B 0742600131 022131 046526 052213 075763 0D8668 050331A 050331 0C2454 025507 027482 42 Bryant QTY. REF 1 1 1 1 1 1 3 1 1 1 2 1 2 DESCRIPTION BATT 12VDC 75-AH 26 (NOT INCLUDED) CABLE BATT RED #4 X 20.00 CABLE BATT BLK #4 X 23.00 ASSY,WIRE#16 RED 1.
Section 9 - Exploded Views and Parts Bryant Liquid-cooled 15 kW Generators Muffler — Drawing No. 0E0773-A 10 9 14 8 15 6 12 13 9 3 7 3 5 4 3 2 ITEM 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 PART NO. 0A4355 0E2844 036434 036449 0E0109 0C1318 0D8657 0E0170 0D9437 060366 039253 022145 022129 045771 0A8974 027837 QTY. 1 1 3 3 1 1 1 1 1 2 4 4 4 4 1 2 DESCRIPTION MANIFOLD EXHAUST 1.5L NIPPLE TOE 1.5NPTX5.5 BLK IRON BOLT U 5/16-18 X 2.09 SADDLE 2 INCH PIPE,EXHAUST 1.
Section 10 – Warranty Bryant Liquid-cooled 15 kW Generators CALIFORNIA EMISSION CONTROL WARRANTY STATEMENT YOUR WARRANTY RIGHTS AND OBLIGATIONS The California Air Resources Board (CARB) and Generac Power Systems, Inc. (Generac) are pleased to explain the Emission Control System Warranty on your new engine.* In California, new utility, and lawn and garden equipment engines must be designed, built and equipped to meet the state’s stringent anti-smog standards.
Section 10 – Warranty Bryant Liquid-cooled 15 kW Generators EMISSION CONTROL SYSTEM WARRANTY Emission Control System Warranty (ECS Warranty) for 1995 and later model year engines: (a) Applicability: This warranty shall apply to 1995 and later model year engines. The ECS Warranty Period shall begin on the date the new engine or equipment is purchased by/delivered to its original, end-use purchaser/owner and shall continue for 24 consecutive months thereafter.
Section 10 – Warranty Bryant Liquid-cooled 15 kW Generators BRYANT "TWO YEAR" LIMITED WARRANTY FOR "PREPACKAGED EMERGENCY AUTOMATIC STANDBY GENERATORS" For a period of two years from the date of original sale, Bryant warrants that its generator will be free from defects in material and workmanship for the items and period set forth below. Bryant will, at its option, repair or replace any part which, upon examination, inspection and testing by a Bryant Dealer, is found to be defective.