Specifications

19
PERFORMANCE DATA (cont)
COOLING CAPACITIES (cont)
Standard Ratings
LEGEND
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
Where h
ewb
= Enthalpy of air entering indoor coil.
3. The SHC is based on 80 F edb temperature of air entering evap-
orator coil.
Below 80 F db, subtract (corr factor x cfm) from SHC.
Above 80 F db, add (corr factor x cfm) to SHC
.
Correction Factor = 1.10 x (1 BF) x (db 80).
581B060 (5 TONS)
Temp (F)
Air Ent
Condenser
(Edb)
Temp (F) Air Entering Evaporator Cfm/BF
1500/0.08 1750/0.09 2000/0.11 2500/0.13
Temp (F) Air Entering Evaporator Ewb (F)
72 67 62 72 67 62 72 67 62 72 67 62
75
TC
70.8 65.4 58.5 72.5 67.3 61.1 73.0 68.4 62.8 74.8 70.3 64.8
SHC
34.1 42.7 49.9 35.7 45.5 54.2 36.8 48.0 57.8 39.6 53.0 63.4
kW
3.53 3.49 3.44 3.55 3.50 3.46 3.55 3.51 3.47 3.57 3.54 3.48
85
TC
68.9 63.2 55.3 70.5 65.1 57.9 72.2 66.4 60.2 73.2 68.1 62.9
SHC
33.5 41.8 48.4 35.0 44.8 52.8 37.0 47.6 56.8 39.3 52.5 62.4
kW
3.98 3.94 3.87 4.00 3.96 3.90 4.03 3.97 3.92 4.04 3.99 3.94
95
TC
66.8 60.6 52.4 68.3
62.5 54.3 69.3 63.8 56.6 71.2 65.6 60.6
SHC
32.8 40.7 47.0 34.5
43.8 51.1 36.0 46.7 55.0 39.1 51.8 60.5
kW
4.48 4.43 4.35 4.50
4.45 4.37 4.51 4.46 4.40 4.55 4.48 4.44
105
TC
64.3 57.7 49.9 65.9 59.8 51.7 66.9 61.1 54.1 68.4 62.8 58.4
SHC
32.0 39.6 45.8 33.7 42.8 49.7 35.3 45.7 53.5 38.4 51.0 58.4
kW
5.03 4.96 4.87 5.05 4.99 4.90 5.06 5.00 4.93 5.08 5.02 4.98
115
TC
61.5 54.8 47.3 62.8 56.7 49.1 64.0 58.2 51.6 65.4 59.9 56.1
SHC
31.0 38.4 44.5 32.5 41.6 48.2 34.4 44.6 51.6 37.4 50.0 56.1
kW
5.61 5.55 5.46 5.62 5.58 5.49 5.65 5.60 5.52 5.67 5.61 5.57
125
TC
58.7 51.6 44.5 59.9 53.4 46.2 60.8 54.9 49.0 62.2 56.8 53.5
SHC
30.0 37.2 43.1 31.7 40.4 46.2 33.3 43.4 48.9 36.4 48.9 53.4
kW
6.27 6.19 6.09 6.28 6.21 6.13 6.29 6.24 6.17 6.31 6.27 6.22
581B072 (6 TONS)
Temp (F)
Air Ent
Condenser
(Edb)
Temp (F) Air Entering Evaporator Cfm/BF
1800/0.05 2100/0.06 2400/0.06 3000/0.08
Temp (F) Air Entering Evaporator Ewb (F)
72 67 62 72 67 62 72 67 62 72 67 62
75
TC
86.7 80.7 74.4 88.8 82.7 76.6 90.5 84.4 78.2 92.6 86.3 81.0
SHC
43.0 53.7 63.8 45.0 57.4 68.9 47.2 61.2 73.6 51.2 67.4 80.7
kW
4.58 4.46 4.33 4.63 4.50 4.38 4.67 4.55 4.41 4.72 4.58 4.47
85
TC
84.1 78.2 72.0 86.4 80.3 74.1 88.2 81.7 75.7 90.2 84.0 78.8
SHC
42.0 52.6 62.7 44.5 56.6 68.0 46.8 60.2 72.5 50.6 67.4 78.7
kW
5.10 4.97 4.85 5.16 5.03 4.90 5.21 5.06 4.93 5.26 5.12 4.99
95
TC
81.3 75.3 69.2 83.4
77.3 71.3 85.1 78.9 72.9 87.2 80.6 76.2
SHC
41.0 51.4 61.4 43.4
55.3 66.6 45.8 59.2 71.2 50.2 65.8 76.2
kW
5.65 5.52 5.39 5.71
5.57 5.44 5.77 5.62 5.48 5.83 5.66 5.55
105
TC
77.9 72.0 66.1 80.0 73.8 68.0 81.6 75.3 69.6 83.4 77.1 73.2
SHC
39.7 50.2 60.0 42.2 54.0 65.2 44.6 57.8 69.3 49.0 64.5 73.2
kW
6.22 6.08 5.94 6.29 6.13 6.00 6.34 6.17 6.04 6.40 6.22 6.12
115
TC
74.7 68.4 61.8 75.9 70.0 64.1 77.6 71.3 66.5 78.7 73.0 70.1
SHC
38.7 48.8 58.1 40.8 52.6 63.2 43.3 56.4 66.4 46.9 63.2 70.0
kW
6.84 6.68 6.49 6.87 6.71 6.56 6.93 6.75 6.63 6.96 6.80 6.72
125
TC
70.3 63.6 57.2 71.8 65.5 59.1 72.9 66.8 61.9 74.0 68.6 66.4
SHC
37.2 47.0 55.8 39.5 51.0 59.1 41.7 55.0 61.9 45.4 61.8 66.3
kW
7.43 7.25 7.03 7.48 7.30 7.13 7.51 7.35 7.22 7.54 7.41 7.33
BF
Bypass Factor
Edb
Entering Dry Bulb
Ewb
Entering Wet Bulb
kW
Compressor Motor Power Input
SHC
Sensible Heat Capacity (1000 Btuh) Gross
TC
Total Capacity (1000 Btuh) Gross
t
ldb
=t
edb
sensible heat capacity (Btuh)
1.10 x cfm
t
lwb
= wet-bulb temperature corresponding to enthalpy of air
leaving indoor coil (h
lwb
)
h
lwb
=h
ewb
total capacity (Btuh)
4.5 x cfm