Specifications

21
PERFORMANCE DATA (cont)
COOLING CAPACITIES (cont)
Standard Ratings
LEGEND
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
Where h
ewb
= Enthalpy of air entering indoor coil.
3. The SHC is based on 80 F edb temperature of air entering evap-
orator coil.
Below 80 F db, subtract (corr factor x cfm) from SHC.
Above 80 F db, add (corr factor x cfm) to SHC
.
Correction Factor = 1.10 x (1 BF) x (db 80).
581B120 (10 TONS)
Temp (F)
Air Ent
Condenser
(Edb)
Temp (F) Air Entering Evaporator Cfm/BF
3000/0.03 3200/0.03 4000/0.04 5000/0.04
Temp (F) Air Entering Evaporator Ewb
72 67 62 72 67 62 72 67 62 72 67 62
75
TC
140.3 129.4 115.0 141.2 130.4 118.1 145.2 134.0 122.1 147.5 136.6 125.3
SHC
65.6 82.2 97.4 66.7 84.4 101.5 71.3 93.1 113.5 77.9 103.7 124.7
kW
7.35 7.21 7.12 7.37 7.23 7.13 7.46 7.31 7.17 7.51 7.37 7.22
85
TC
137.7 125.3 110.0 138.9 126.6 113.6 142.6 130.6 117.7 144.6 133.3 122.3
SHC
65.0 81.2 95.2 66.3 83.6 99.7 71.0 92.8 112.0 76.9 103.1 122.2
kW
8.29 8.13 8.02 8.32 8.16 8.03 8.40 8.24 8.09 8.45 8.31 8.16
95
TC
133.8 120.7 103.0 135.1
121.9 107.2 138.8 125.8 112.8 141.7 128.5 118.5
SHC
63.9 79.6 92.2 65.2
82.0 97.0 70.6 91.5 109.7 76.9 102.5 118.4
kW
9.33 9.16 8.98 9.35
9.18 9.00 9.44 9.27 9.07 9.51 9.33 9.19
105
TC
128.7 115.4 96.5 129.8 116.6 99.7 133.7 120.3 107.1 136.7 122.8 114.5
SHC
62.3 77.6 89.4 63.6 80.2 93.5 69.4 89.6 106.8 76.0 100.6 114.3
kW
10.46 10.28 10.00 10.47 10.30 10.07 10.57 10.38 10.21 10.66 10.43 10.31
115
TC
123.2 109.1 90.8 124.3 110.3 92.2 127.9 114.4 100.8 130.9 116.8 110.1
SHC
60.4 75.1 86.6 61.9 77.8 90.0 67.6 87.6 100.7 74.6 98.7 109.9
kW
11.66 11.47 11.20 11.68 11.51 11.25 11.77 11.60 11.41 11.89 11.66 11.58
125
TC
117.5 101.8 86.2 118.5 103.0 87.4 121.6 107.1 96.0 124.1 110.3 104.8
SHC
58.5 72.5 84.5 60.0 75.0 87.3 65.8 85.1 96.0 72.5 96.9 104.8
kW
12.99 12.77 12.50 13.02 12.81 12.55 13.10 12.92 12.74 13.19 13.01 12.91
581B150 (12
1
/
2
TONS)
Temp (F)
Air Ent
Condenser
(Edb)
Temp (F) Air Entering Evaporator Cfm/BF
3750/0.08 4300/0.09 5000/0.11 6250/0.13
Temp (F) Air Entering Evaporator Ewb
72 67 62 72 67 62 72 67 62 72 67 62
75
TC
164.3 154.8 132.8 168.5 157.7 143.6 171.7 160.6 148.3 174.7 164.6 153.5
SHC
91.0 107.5 111.6 95.7 114.1 121.0 101.6 121.5 129.7 49.4 110.6 142.3
kW
9.56 9.43 9.18 9.67 9.44 9.26 9.75 9.51 9.25 9.83 9.61 9.38
85
TC
159.5 149.4 125.8 163.8 152.7 136.6 166.8 155.6 143.6 170.2 159.5 149.4
SHC
78.3 102.0 116.4 82.8 108.2 128.8 86.7 116.1 140.0 93.3 130.0 149.3
kW
10.60 10.50 10.19 10.47 10.49 10.27 10.81 10.57 10.33 10.92 10.69 10.43
95
TC
154.0 143.2 118.0 157.7
146.7 128.8 161.1 149.6 137.5 164.4 153.6 144.3
SHC
76.6 99.5 112.5 80.5
106.1 124.8 85.1 114.4 136.3 75.5 112.1 135.8
kW
11.59 11.62 11.41 11.64
11.71 11.49 11.78 11.80 11.56 12.08 11.90 11.69
105
TC
148.0 134.1 110.7 151.5 139.5 120.6 153.9 142.4 128.3 157.0 145.8 138.7
SHC
74.4 95.9 108.6 78.9 104.0 119.9 83.2 111.6 128.3 89.3 125.2 138.7
kW
12.94 12.69 12.36 13.04 12.77 12.45 13.10 12.84 12.57 13.18 12.93 12.76
115
TC
139.1 120.4 103.2 143.0 125.0 110.6 146.1 128.8 118.2 148.9 135.7 129.5
SHC
71.3 90.5 103.2 76.0 98.1 110.5 80.5 107.0 118.2 87.2 122.1 129.5
kW
14.12 13.83 13.50 14.20 13.93 13.63 14.29 14.03 13.78 14.37 14.14 13.97
125
TC
127.1 106.2 97.5 131.6 108.7 100.7 136.1 112.0 105.7 139.5 118.4 116.4
SHC
67.2 85.1 97.4 72.4 91.9 100.3 77.6 100.4 105.6 84.6 114.2 116.3
kW
15.31 14.99 14.65 15.42 15.08 14.85 15.51 15.18 15.03 15.60 15.28 15.22
BF
Bypass Factor
Edb
Entering Dry Bulb
Ewb
Entering Wet Bulb
kW
Compressor Motor Power Input
SHC
Sensible Heat Capacity (1000 Btuh) Gross
TC
Total Capacity (1000 Btuh) Gross
t
ldb
=t
edb
sensible heat capacity (Btuh)
1.10 x cfm
t
lwb
= wet-bulb temperature corresponding to enthalpy of air
leaving indoor coil (h
lwb
)
h
lwb
=h
ewb
total capacity (Btuh)
4.5 x cfm