580J*08--14D,F (2--COMPRESSOR) NOMINAL 7.5 to 12.5 TONS WITH PURONR (R--410A) REFRIGERANT Service and Maintenance Instructions TABLE OF CONTENTS SAFETY CONSIDERATIONS SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . 1 Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.
WARNING 580J ! ! FIRE, EXPLOSION HAZARD Failure to follow this warning could result in personal injury or death. Disconnect gas piping from unit when pressure testing at pressure greater than 0.5 psig. Pressures greater than 0.5 psig will cause gas valve damage resulting in hazardous condition. If gas valve is subjected to pressure greater than 0.5 psig, it must be replaced before use. When pressure testing field-supplied gas piping at pressures of 0.
Heating S Heat exchanger flue passageways cleanliness S Gas burner condition S Gas manifold pressure S Heating temperature rise Economizer or Outside Air Damper CONTROL BOX COMPRESSORS C09239 Fig.
SUPPLY FAN (BLOWER) SECTION 22 3/8 (569 mm) ! ELECTRICAL SHOCK HAZARD Failure to follow this warning could cause personal injury or death. Before performing service or maintenance operations on the fan system, shut off all unit power and tag-- out the unit disconnect switch. Do not reach into the fan section with power still applied to unit. DIVIDER OUTSIDE AIR HOOD 580J CLEANABLE ALUMINUM FILTER Supply Fan (Belt--Drive) FILTER BAROMETRIC RELIEF FILTER CAP Fig.
To replace the belt: To align fan and motor pulleys: 1. Use a belt with same section type or similar size. Do not substitute a “FHP” type belt. When installing the new belt, do not use a tool (screwdriver or pry-- bar) to force the belt over the pulley flanges, this will stress the belt and cause a reduction in belt life. 2. Loosen the motor mounting plate front bolts and rear bolts. 3.
Changing the Fan Wheel Speed by Changing Pulleys TUBES 580J The horsepower rating of the belt is primarily dictated by the pitch diameter of the smaller pulley in the drive system (typically the motor pulley in these units). Do not install a replacement motor pulley with a smaller pitch diameter than provided on the original factory pulley.
Routine Cleaning of NOVATION Condenser Coil Surfaces Totaline Environmentally Sound Coil Cleaner Application Equipment To clean the NOVATION condenser coil, chemicals are NOT to be used; only water is approved as the cleaning solution. Only clean potable water is authorized for cleaning NOVATION condensers. Carefully remove any foreign objects or debris attached to the coil face or trapped within the mounting frame and brackets.
9. Finned surfaces should remain wet with cleaning solution for 10 minutes. 10. Ensure surfaces are not allowed to dry before rinsing. Reapply cleaner as needed to ensure 10-- minute saturation is achieved. 11. Thoroughly rinse all surfaces with low velocity clean water using downward rinsing motion of water spray nozzle. Protect fins from damage from the spray nozzle.
SEAT CORE (Part No. EC39EZ067) 1/2-20 UNF RH 0.596 45 o o WASHER O-RING 5/8” HEX .47 1/2" HEX This surface provides a metal to metal seal when torqued into the seat. Appropriate handling is required to not scratch or dent the surface. Fig. 9 - CoreMax Access Port Assembly EXAMPLE: Model 580J*14D Circuit 1: Outdoor Temperature . . . . . . . . . . . . . . . . . . 85_F (29_C) Suction Pressure . . . . . . . . . . . . . . . . . 125 psig (860 kPa) Suction Temperature should be . . . . . . . . . .
580J COOLING CHARGING CHARTS Fig.
580J COOLING CHARGING CHARTS Fig.
COOLING CHARGING CHARTS 580J 12.5 TON CIRCUIT 1 Fig.
COOLING CHARGING CHARTS 580J 12.5 TON CIRCUIT 2 Fig.
Table 1 – Cooling Service Analysis PROBLEM Compressor and Condenser Fan Will Not Start. Compressor Will Not Start But Condenser Fan Runs. CAUSE Power failure. Fuse blown or circuit breaker tripped. Defective thermostat, contactor, transformer, or control relay. Insufficient line voltage. Incorrect or faulty wiring. Thermostat setting too high. Faulty wiring or loose connections in compressor circuit. Compressor motor burned out, seized, or internal overload open.
Compressors The suction and discharge pressure levels should now move to their normal start-- up levels. Compressors are charged with the correct amount of oil at the factory. ! CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in damage to components. The compressor is in a PuronR refrigerant system and uses a polyolester (POE) oil. This oil is extremely hygroscopic, meaning it absorbs water readily.
CONVENIENCE OUTLETS ! COVER - WHILE-IN-USE WEATHERPROOF WARNING 580J ELECTRICAL OPERATION HAZARD Failure to follow this warning could result in personal injury or death. Units with convenience outlet circuits may use multiple disconnects. Check convenience outlet for power status before opening unit for service. Locate its disconnect switch, if appropriate, and open it. Tag-- out this switch, if necessary. Two types of convenience outlets are offered on 580J models: Non-- powered and unit-- powered.
Using Unit--Mounted Convenience Outlets Units with unit-- mounted convenience outlet circuits will often require that two disconnects be opened to de-- energize all power to the unit. Treat all units as electrically energized until the convenience outlet power is also checked and de-- energization is confirmed. Observe National Electrical Code Article 210, Branch Circuits, for use of convenience outlets.
Duct smoke sensor Duct smoke sensor controller Exhaust tube Conduit nuts (supplied by installer) Exhaust gasket Sensor housing and electronics See Detail A Conduit support plate Terminal block cover Controller housing and electronics Intake gasket Cover gasket (ordering option) Cover gasket (ordering option) Controller cover Conduit couplings (supplied by installer) TSD-CO2 (ordering option) 580J Sensor cover Plug Fastener (2X) Sampling tube (ordered separately) Coupling Detail A Trouble Al
Return Air Without Economizer The sampling tube is located across the return air opening on the unit basepan. (See Fig. 22.) The holes in the sampling tube face downward, into the return air stream. The sampling tube is connected via tubing to the return air sensor that is mounted on a bracket high on the partition between return filter and controller location. (This sensor is shipped in a flat-- mounting location.
B D C F 580J E A Fig. 26 - Typical Smoke Detector System Wiring Highlight B Smoke detector NC contact set will open on smoke alarm condition, de-- energizing the ORN conductor. Highlight C 24-- v power signal via ORN lead is removed at Smoke Detector input on LCTB; all unit operations cease immediately. RTU-- MP Controls Additional Application Data — Refer to Catalog No. HKRNKA-- 1XA for discussions on additional control features of these smoke detectors including multiple unit coordination.
Controller Alarm Test The controller alarm test checks the controller’s ability to initiate and indicate an alarm state. CAUTION OPERATIONAL TEST HAZARD Failure to follow this caution may result in personnel and authority concern. This test places the duct detector into the alarm state. Disconnect all auxiliary equipment from the controller before performing the test. If the duct detector is connected to a fire alarm system, notify the proper authorities before performing the test.
580J SD-- TRK4 Remote Alarm Test Procedure 1. Turn the key switch to the RESET/TEST position for seven seconds. 2. Verify that the test/reset station’s Alarm LED turns on. 3. Reset the sensor by turning the key switch to the RESET/TEST position for two seconds. 4. Verify that the test/reset station’s Alarm LED turns off. Remote Test/Reset Station Dirty Sensor Test The test/reset station dirty sensor test checks the test/reset station’s ability to initiate a sensor dirty test and indicate the results.
Normal State The smoke detector operates in the normal state in the absence of any trouble conditions and when its sensing chamber is free of smoke. In the normal state, the Power LED on both the sensor and the controller are on and all other LEDs are off. Alarm State The smoke detector enters the alarm state when the amount of smoke particulate in the sensor’s sensing chamber exceeds the alarm threshold value. (See Table 3.
Table 3 – Detector Indicators CONTROL OR INDICATOR Magnetic test/reset switch Alarm LED Trouble LED Dirty LED 580J Power LED DESCRIPTION Resets the sensor when it is in the alarm or trouble state. Activates or tests the sensor when it is in the normal state. Indicates the sensor is in the alarm state. Indicates the sensor is in the trouble state. Indicates the amount of environmental compensation used by the sensor (flashing continuously = 100%) Indicates the sensor is energized.
Troubleshooting Supply Fan Motor Overload Trips The supply fan used in 580J units is a forward-- curved centrifugal wheel. At a constant wheel speed, this wheel has a characteristic that causes the fan shaft load to DECREASE when the static pressure in the unit-- duct system increases and to INCREASE when the static pressure in the unit-- duct system decreases (and fan airflow rate increases).
Table 7 – Liquid Propane Supply Line Pressure Ranges UNIT MODEL UNIT SIZE 580J All MIN 11.0 in. wg (2740 Pa) MAX 13.0 in. wg (3240 Pa) Manifold pressure for LP fuel use must be adjusted to specified range. (See Table 8.) Follow instructions in the accessory kit to make initial readjustment. Table 8 – Liquid Propane Manifold Pressure Ranges UNIT MODEL UNIT SIZE 580J All HIGH FIRE 10.0 in. wg (2490 Pa) LOW FIRE 5.0 in.
HEATER TUBE ASSEMBLY SEAL STRIPS, SPONGE RUBBER REGULATOR GASKET REGULATOR RETAINER 580J WIND CAP ASSEMBLY (SHOWN INVERTED, AS SHIPPED) SUPPORT INSULATION ASSEMBLY INDUCER FAN-MOTOR ASSEMBLY BURNER ASSEMBLY C08227 Fig. 34 - Heat Exchanger Assembly Burners and Igniters ! ORIFICE CAUTION 1.00-in (25.4 mm) EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in equipment damage. When working on gas train, do not hit or plug orifice spuds. MANIFOLD PIPE Fig.
7. Reinstall burner rack as described in Removal and Replacement of Gas Train section, above. MANIFOLD PRESSURE TAP Gas Valve — All unit sizes are equipped with 2-- stage gas valves. See Fig. 39 for locations of adjustment screws and features on the gas valves. To adjust gas valve pressure settings: GAS VALVE BURNERS 580J Fig. 36 - Burner Tray Details C09154 6. Remove igniter wires and sensor wires at the Integrated Gas Unit Controller (IGC). (See Fig. 37.) 7.
125,000/90,000 BTUH INPUT 580J 180,000/120,000 BTUH INPUT 240,000/180,000 BTUH INPUT 250,000/200,000 BTUH INPUT C08447 Fig. 38 - Spark Adjustment (08-- 14) Burner Ignition Table 9 – LED Error Code Description* Unit is equipped with a direct spark ignition 100% lockout system. Integrated Gas Unit Controller (IGC) is located in the control box. (See Fig. 37.) The IGC contains a self-- diagnostic LED (light-- emitting diode).
580J C08240 580J08(D,F)150 only All 580J*D,F except 150 C08241 Fig. 39 - Gas Valve Orifice Replacement This unit uses orifice type LH32RFnnn (where nnn indicates orifice reference size). When replacing unit orifices, order the necessary parts via Bryant RCD. See Table 11 for available orifice sizes. See Table 12 for orifice sizes for Natural Gas and LP fuel usage at various elevations above sea level.
580J Red LED-Status C08452 Fig.
580J Table 11 – Orifice Sizes ORIFICE DRILL SIZE #30 1/8 #31 #32 #33 #34 #35 #36 #37 #38 #39 #40 #41 #42 #43 #44 #45 #46 #47 #48 #49 #50 #51 #52 #53 #54 #55 #56 #57 #58 BRYANT PART NUMBER LH32RF129 LH32RF125 LH32RF120 LH32RF116 LH32RF113 LH32RF111 LH32RF110 LH32RF105 LH32RF104 LH32RF102 LH32RF103 LH32RF098 LH32RF096 LH32RF094 LH32RF089 LH32RF086 LH32RF082 LH32RF080 LH32RF079 LH32RF076 LH32RF073 LH32RF070 LH32RF067 LH32RF065 LH32RF060 LH32RF055 LH32RF052 LH32RF047 LH32RF043 LH32RF042 DRILL DIA. (in.) 0.
When operating on first stage heating, the minimum temperature of air entering the dimpled heat exchanger is 50_F continuous and 45_F intermittent for standard heat exchangers and 40_F continuous and 35_F intermittent for stainless steel heat exchangers. To operate at lower mixed-- air temperatures, a field-- supplied outdoor-- air thermostat must be used to initiate both stages of heat when the temperature is below the minimum required temperature to ensure full fire operation.
Table 14 – IGC Board LED Alarm Codes LED FLASH CODE On 580J Off DESCRIPTION Normal Operation Hardware Failure ACTION TAKEN BY CONTROL RESET METHOD — — No gas heating. — PROBABLE CAUSE — Loss of power to the IGC. Check 5 amp fuse on IGC, power to unit, 24V circuit breaker, transformer, and wiring to the IGC. High temperature limit switch is open. Check the operation of the indoor (evaporator) fan motor. Ensure that the supply-air temperature rise is within the range on the unit nameplate.
CONDENSER COIL SERVICE The condenser coil is new NOVATION Heat Exchanger Technology. This is an all-- aluminum construction with louvered fins over single-- depth crosstubes. The crosstubes have multiple small passages through which the refrigerant passes from header to header on each end. Tubes and fins are both aluminum construction. Connection tube joints are copper. The coil may be one-- row or two-- row. Two-- row coils are spaced apart to assist in cleaning.
580J Fig.
Fig.
Table 15 – RTU-- MP Controller Inputs and Outputs POINT NAME 580J Space Temperature Sensor Supply Air Temperature Local Outside Air Temperature Sensor Space Temperature Offset Pot Indoor Air Quality Outdoor Air Quality Safety Chain Feedback Compressor Safety Fire Shutdown Enthalpy Switch Humidistat Input Status Space Relative Humidity Outside Air Relative Humidity Supply Fan Status Filter Status Remote Occupancy Input Economizer Commanded Position Supply Fan Relay State Compressor 1 Relay State Compressor
TEMP (C) ---40 ---35 ---30 ---25 ---20 ---15 ---10 ---5 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 TEMP (F) ---40 ---31 ---22 ---13 ---4 5 14 23 32 41 50 59 68 77 86 95 104 113 122 131 140 149 158 RESISTANCE (Ohms) 335,651 242,195 176,683 130,243 96,974 72,895 55,298 42,315 32,651 25,395 19,903 15,714 12,494 10,000 8,056 6,530 5,325 4,367 3,601 2,985 2,487 2,082 1,752 S Enthalpy control (outdoor air or differential sensors) S Space CO2 sensor S Outdoor air CO2 sensor Field Connections - Field connections
SEN J20-1 SEN J20-2 BRN (COM) BLK (STO) Fig. 46 - RTU-- MP T-- 55 Sensor Connections BLU (SPT) SENSOR WIRING C08460 OR SET SEN OPB COM- PWR+ Connect T-- 56 See Fig. 47 for T-- 56 internal connections. Install a jumper between SEN and SET terminals as illustrated. Connect T-- 56 terminals to RTU-- MP J20-- 1, J20-- 2 and J20-- 3 per Fig. 48. 580J 24 VAC POWER WIRING NOTE: Must use a separate isolated transformer. 1 2 3 4 SEN SW1 5 6 RED(+) WHT(GND) BLK(-) C07132 CCN COM Fig.
The enthalpy control receives the outdoor air enthalpy from the outdoor air enthalpy sensor and provides a dry contact switch input to the RTU-- MP controller. A closed contact indicates that outside air is preferred to the return air. An open contact indicates that the economizer should remain at minimum position. Differential Enthalpy Control Differential enthalpy control is provided by sensing and comparing the outside air and return air enthalpy conditions.
To connect the sensor to the control, identify the positive (4 to 20 mA) and ground (SIG COM) terminals on the sensor. (See Fig. 52.) Connect the 4-- 20 mA terminal to RTU-- MP J4-- 2 and connect the SIG COM terminal to RTU-- MP J4-- 3. (See Fig. 53.) OAQ Sensor/RH Sensor IAQ Sensor SEN J4-5 COM J4-6 24 VAC J4-2 SEN COM J4-3 24 VAC C08462 580J Fig. 55 - RTU-- MP / Outdoor CO2 Sensor (33ZCSENCO2) Connections Fig.
Power Exhaust (output) Connect the accessory Power Exhaust contactor coil(s) per Fig. 56. Power Exhaust PEC J11-3 TAN GRA LCTB THERMOSTAT C C08464 Fig. 56 - RTU-- MP Power Exhaust Connections Space Relative Humidity Sensor Space Relative Humidity Sensor - The RH sensor is not used with 580J models at this time. Communication Wiring -- Protocols General Protocols are the communication languages spoken by control devices.
SW3 Protocol Selection PROTOCOL BACnet MS/TP (Master) Modbus (Slave) N2 (Slave) LonWorks DS8 DS7 DS6 DS5 DS4 DS3 DS2 DS1 Unused OFF OFF OFF ON OFF Select Baud Select Baud Unused OFF OFF ON ON OFF Select Baud Select Baud Unused OFF OFF OFF ON ON OFF OFF Unused ON ON OFF ON OFF OFF OFF NOTE: DS = Dip Switch BACnet MS/TP SW3 example shown 580J Baud Rate Selections BAUD RATE 9600 19,200 38,400 76,800 DS2 OFF ON OFF ON DS1 OFF OFF ON ON Fig.
Table 17 – LEDs The LEDs on the RTU-- MP show the status of certain functions Status is... The RTU MP has power The RTU MP is receiving data from the network segment The RTU MP is transmitting data over the network segment The digital output is active If this LED is on... Power Rx Tx DO# If Run LED shows... 2 flashes per second 2 flashes per second 2 flashes per second 2 flashes per second And Error LED shows...
580J Table 18 – Troubleshooting Alarms POINT NAME BACnet OBJECT NAME Safety Chain Alarm safety_chain Fire Shutdown Alarm fire_alarm Space Temp Sensor Failure spt_alarm SAT Sensor Alarm sat_alarm High Space Temp Alarm spt_hi Alarm Generated Automatic Low Space Temp Alarm spt_lo Alarm Generated Automatic High Supply Air Temp sat_hi Alarm Generated Automatic Low Supply Air Temp sat_lo Alarm Generated Automatic Supply Fan Failed to Start sf_fail Supply Fan in Hand sf_hand Compress
Alarms can be checked through the network and/or the local access. All the alarms are listed in Table 18 with name, object name, action taken by control, reset method, and probable cause. There are help screens for each alarm on the local access display and listed in RTU-- MP Controls, Start-- Up, Operation, and Troubleshooting Instructions (Form 48-- 50H-- T-- 2T), Appendix A: Help Screens. Some alarms are explained in detail below.
Device Instance: 0160001 1 PRGs loaded. 1 PRGs running. Module status: Firmware sections validated in flash memory ============================================ Boot16-H - v2.06:001 Jun 19 2007 RTU-MP DRIVER - v2.
Table 19 – Manufacture Date When troubleshooting, you may need to know a control module’s manufacture date Notes Module status report (modstat) To obtain a modstat with BACview6: 1. Press Function (FN) key and hold. 2. Then press period (.) 3. Release both buttons. The report shows the date under Main board hardware.
NOTE: See RTU-- MP 3rd Party Integration Guide (or alternatively RTU-- MP 3rd Party Integration Guide (or alternatively RTU-- MP Controls, Start-- Up, Operation, and Troubleshooting Instructions (Form 48-- 50H-- T-- 2T), Appendix) for Modbus Protocol Conformance Statement. 580J N2 1. Verify that the BAS and controller are both set to speak the N2 protocol. The protocol of the controller is set via SW3 (switches 3, 4, 5, and 6).
580J C09023 Fig. 62 - EconoMi$er IV Wiring BLACK 4 TRANSFORMER GROUND 3 5 BLUE 500 OHM RESISTOR 2 8 VIOLET 6 NOTE 1 PINK 7 RUN OAT SENSOR RED NOTE 3 1 24 VAC 10 YELLOW 50HJ540573 ACTUATOR ASSEMBLY 11 9 DIRECT DRIVE ACTUATOR 4-20mA SIGNAL WHITE 12 ECONOMISER2 PLUG NOTES: 1. Switch on actuator must be in run position for economizer to operate. 2. 50HJ540573 actuator consists of the 50HJ540567 actuator and a harness with 500-ohm resistor. Fig.
Table 22 – EconoMi$er IV Input/Output Logic Demand Control Ventilation (DCV) 580J Below set (DCV LED Off) Above set (DCV LED On) INPUTS Enthalpy* Outdoor Return High (Free Cooling LED Off) Low Low (Free Cooling LED On) High High (Free Cooling LED Off) Low Low (Free Cooling LED On) High On On Off Compressor Y2 Stage Stage 1 2 On On On Off On Off Off Off Off On On On Off On Off Off Off Off On Off On Off On Off On On Off On Off Off On On Off Off On Off Off Off On Off Off Off
Supply Air Temperature (SAT) Sensor The supply air temperature sensor is a 3 K thermistor located at the inlet of the indoor fan. (See Fig. 65.) This sensor is factory installed. The operating range of temperature measurement is 0° to 158_F (-- 18_ to 70_C). See Table 16 for sensor temperature/resistance values. SUPPLY AIR TEMPERATURE SENSOR MOUNTING LOCATION C06034 Fig. 65 - Supply Air Sensor Location Fig.
Differential Dry Bulb Control For differential dry bulb control the standard outdoor dry bulb sensor is used in conjunction with an additional accessory dry bulb sensor (part number CRTEMPSN002A00). The accessory sensor must be mounted in the return airstream. (See Fig. 69.) Wiring is provided in the EconoMi$er IV wiring harness. (See Fig. 62.) In this mode of operation, the outdoor-air temperature is compared to the return-air temperature and the lower temperature airstream is used for cooling.
P Min Pos T1 DCV 2V AQ SO SR + _ Max 10V 1 2 CO2 SENSOR MAX RANGE SETTING 6000 5 DCV SO+ SR+ 24 Vac COM Open T AQ1 24 Vac HOT Adjust the DCV potentiometers to correspond to the DCV voltage output of the indoor air quality sensor at the user-determined setpoint. (See Fig. 72.
Adjust the minimum position potentiometer to allow the minimum amount of outdoor air, as required by local codes, to enter the building. Make minimum position adjustments with at least 10_F temperature difference between the outdoor and return-air temperatures. To determine the minimum position setting, perform the following procedure: 1.
Once the fully occupied damper position has been determined, set the maximum damper demand control ventilation potentiometer to this position. Do not set to the maximum position as this can result in over-ventilation to the space and potential high humidity levels. CO2 Sensor Configuration The CO2 sensor has preset standard voltage settings that can be selected anytime after the sensor is powered up. (See Table 23.) Use setting 1 or 2 for Bryant equipment. (See Table 23.) 1. Press Clear and Mode buttons.
Table 24 – EconoMi$er IV Sensor Usage 580J APPLICATION Outdoor Air Dry Bulb Differential Dry Bulb Single Enthalpy Differential Enthalpy CO2 for DCV Control using a Wall-Mounted CO2 Sensor CO2 for DCV Control using a Duct-Mounted CO2 Sensor ECONOMI$ER IV WITH OUTDOOR AIR DRY BULB SENSOR Accessories Required None. The outdoor air dry bulb sensor is factory installed.
To check the DCV minimum and maximum position: 1. Make sure EconoMi$er IV preparation procedure has been performed. 2. Connect a 9-- v battery to AQ (positive node) and AQ1 (negative node). The DCV LED should turn on. The actuator should drive to between 90 and 95% open. 3. Turn the DCV Maximum Position potentiometer to midpoint. The actuator should drive to between 20 and 80% open. 4. Turn the DCV Maximum Position potentiometer to fully CCW. The actuator should drive fully closed. 5.
580J Fig.
580J Fig.
PRE--START--UP 580J ! ! WARNING PERSONAL INJURY AND ENVIRONMENTAL HAZARD Failure to follow this warning could result in personal injury or death. Relieve pressure and recover all refrigerant before system repair or final unit disposal. Wear safety glasses and gloves when handling refrigerants. Keep torches and other ignition sources away from refrigerants and oils. PERSONAL INJURY HAZARD Failure to follow this warning could result in personal injury or death. 1.
WARNING UNIT OPERATION AND SAFETY HAZARD Failure to follow this warning could result in personal injury or death. Disconnect gas piping from unit when leak testing at pressure greater than 1/2 psig. Pressures greater than 1/2 psig will cause gas valve damage resulting in hazardous condition. If gas valve is subjected to pressure greater than 1/2 psig, it must be replaced before use.
NOTE: The default value for the evaporator-- fan motor on/off delay is 45 seconds. The Integrated Gas Unit Controller (IGC) modifies this value when abnormal limit switch cycles occur. Based upon unit operating conditions, the on delay can be reduced to 0 seconds and the off delay can be extended to 180 seconds.
Number of Compressor Stages This refers to the number of mechanical cooling stages available on a specific unit. Set this point to “One Stage” if there is one compressor in the specific unit, set to “Two Stage” if there are two compressors in the unit, and set to “None” if economizer cooling ONLY is desired.
580J Input 5 This input is a discrete input and can be configured to be one of five different inputs: No Function, Fire Shutdown, Fan Status, Filter Status, or Remote Occupancy. This input can also be configured to be either Normally Open (N/O) or Normally Closed (N/C). Input 5 is factory wired to pin J1-- 10. Field accessories get wired to its parallel pin J5-- 3. Do not connect inputs to both locations, one function per input.
Max Differential CO2 Setpt If the difference between indoor an outdoor air quality becomes greater then this value the damper position will stay at the IAQ Greatest Min Dmpr Pos. configuration point Factory Default = 650 PPM Range = 300-- 950 PPM IAQ Greatest Min Dmpr Pos. This is the greatest minimum position the economizer will open to while trying to control the indoor air quality, CO2 differential.
When free cooling is available as determined by the appropriate changeover command (dry bulb, outdoor enthalpy, differential dry bulb or differential enthalpy), a call for cooling (Y1 closes at the thermostat) will cause the economizer control to modulate the dampers open and closed to maintain the unit supply air temperature at 50 to 55_F. Compressor will not run.
BACnet Schedule For use with a Building Automation System that supports native BACnet scheduling is scheduling the unit. With the Occupancy Source set to BACnet schedule the BAS will control the unit through network communication and it’s own scheduling function. BAS On/Off The Building Automation System is scheduling the unit via an On/Off command to the BAS ON/OFF software point.
580J Cooling The compressor outputs are controlled by the Cooling Control PID Loop and Cooling Stages Capacity algorithm. They will be used to calculate the desired number of stages needed to satisfy the space by comparing the Space Temperature (SPT) to the Occupied Cool Setpoint plus the T56 slider offset when occupied and the Unoccupied Cool Setpoint (UCSP) plus the T56 slider offset, if unoccupied. The economizer, if available, will be used for cooling in addition to the compressors.
If the calculated IAQ minimum position is greater than the IAQ maximum damper position configuration then it will be clamped to the configured value. Demand Limit If the RTU-- MP receives a level 1 (one degree offset), 2 (two degree offset), or a 3 (4 degree offset) to the BACnet demand limit variable, the controller will expand the heating and cooling setpoints by the configured demand limit setpoint value and remain in effect until the BACnet demand limit variable receives a 0 value.
APPENDIX I. MODEL NUMBER SIGNIFICANCE Model Number Nomenclature 1 2 3 4 5 5 8 0 J E 0 ____________ 6 7 8 9 8 D 1 ______ 10 11 12 13 14 15 16 17 18 2 5 A 1 A 0 A A -- ________ ______ Unit Type Design Revision 580J = Cooling/Gas Heat RTU --- = First Revision Voltage Packaging E = 460--- 3--- 60 A = Standard P = 208/230--- 3--- 60 B = LTL T = 575--- 3--- 60 580J Factory Installed Options Cooling Tons 0A = None 08 = 7.5 Ton 12 = 10 Ton Intake/Exhaust Options 14 = 12.
APPENDIX II. PHYSICAL DATA 580J*12D,F 580J*14D,F 2 / 2 / Scroll 2 / 2 / Scroll 2 / 2 / Scroll 4--- 6 / 4--- 6 6--- 0 / 6--- 0 7--- 6/8--- 0 42 / 42 Accutrol 630 / 505 54 / 117 42 / 42 Accutrol 630 / 505 54 / 117 56 / 56 Accutrol 630 / 505 54 / 117 Cu / Al 3/8” RTPF 3 / 15 8.9 3/4” Cu / Al 3/8” RTPF 4 / 15 11.1 3/4” Cu / Al 3/8” RTPF 4 / 15 11.1 3/4” Motor Qty / Drive Type Max BHP RPM Range Motor Frame Size Fan Qty / Type Fan Diameter (in) 1 / Belt 1.
APPENDIX II. PHYSICAL DATA (cont.) Physical Data (Heating) 7.5 -- 12.5TONS 580J**08 580J**12 580J**14 1 4--- 13 / 0.18--- 0.47 11--- 13 / 0.40--- 0.47 1 4--- 13 / 0.18--- 0.47 11--- 13 / 0.40--- 0.47 1 4--- 13 / 0.18--- 0.47 11--- 13 / 0.40--- 0.47 0.14 0.14 0.14 0.14 0.14 0.
APPENDIX III. FAN PERFORMANCE CFM 2250 2438 2625 2813 3000 3188 3375 3563 3750 CFM 2250 2438 2625 2813 3000 3188 3375 3563 3750 3 PHASE 0.2 RPM BHP RPM 505 533 562 591 621 652 682 713 745 0.52 0.62 0.74 0.88 1.03 1.21 1.40 1.61 1.85 586 610 635 661 688 715 743 772 801 1.2 RPM BHP 838 854 872 890 910 930 951 973 996 1.81 1.96 2.12 2.31 2.51 2.74 2.99 3.26 3.55 7.5 TON HORIZONTAL SUPPLY AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.4 0.6 0.8 BHP RPM BHP RPM Standard Static Option 0.73 657 0.
FAN PERFORMANCE (cont.) 580J**12 CFM 580J 3000 3250 3500 3750 4000 4250 4500 4750 5000 CFM 3000 3250 3500 3750 4000 4250 4500 4750 5000 3 PHASE 0.2 RPM BHP Field---Supplied Drive1 579 0.70 613 0.85 648 1.03 683 1.23 719 1.45 756 1.71 792 1.99 830 2.31 867 2.66 RPM 660 690 721 753 786 819 853 888 923 1.2 RPM BHP RPM 917 938 961 985 1011 1037 1064 1091 1120 1.70 1.93 2.18 2.46 2.76 3.09 3.46 3.85 4.
CFM 3 PHASE 0.2 RPM 0.4 BHP RPM 12.5 TON HORIZONTAL SUPPLY Available External Static Pressure (in. wg) 0.6 0.8 BHP RPM BHP RPM 1.0 BHP Standard Static Option 3438 3750 4063 4375 4688 5000 5313 5625 5938 6250 CFM 3438 3750 4063 4375 4688 5000 5313 5625 5938 6250 639 683 728 774 820 867 914 962 1009 - 0.98 1.23 1.52 1.85 2.23 2.66 3.15 3.69 4.30 1.2 713 753 794 836 879 923 967 1012 1058 - 1.20 1.47 1.78 2.13 2.53 2.98 3.49 4.05 4.68 - 781 817 855 894 935 976 1018 1061 - 1.43 1.71 2.04 2.41 2.
580J**14 CFM 580J 3438 3750 4063 4375 4688 5000 5313 5625 5938 6250 CFM 3438 3750 4063 4375 4688 5000 5313 5625 5938 6250 3 PHASE 0.2 12.5 TON VERTICAL SUPPLY Available External Static Pressure (in. wg) 0.6 0.8 1.0 RPM BHP RPM BHP RPM BHP RPM Standard Static Option Medium Static Option 751 1.32 813 1.54 871 1.76 927 797 1.63 855 1.86 910 2.10 963 844 1.99 898 2.24 951 2.49 1001 892 2.40 943 2.67 993 2.94 1041 941 2.87 990 3.15 1037 3.44 1082 991 3.40 1037 3.70 1082 4.00 1125 1042 4.00 1085 4.
APPENDIX III. FAN PERFORMANCE (cont.) 3 phase 3 phase 3 phase 14 12 08 UNIT MOTOR/DRIVE COMBO 0.0 0.5 1.0 MOTOR PULLEY TURNS OPEN 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.
ELECTRICAL INFORMATION 580J*08D,F V ---Ph---Hz 2 ---Stage Cooling VOLTAGE RANGE 580J MIN MAX COMP (Cir 1) COMP (Cir 2) OFM (ea) RLA LRA RLA LRA WATTS FLA 208--- 3--- 60 187 253 13.6 83 13.6 83 325 1.5 230--- 3--- 60 187 253 13.6 83 13.6 83 325 1.5 460--- 3--- 60 414 506 6.1 41 6.1 41 325 0.8 575--- 3--- 60 518 633 4.2 33 4.2 33 325 0.
NOM. V ---Ph---Hz IFM TYPE 580J*08D,F 208/230--- 3--- 60 460--- 3--- 60 575--- 3--- 60 580J*12D,F 208/230--- 3--- 60 460--- 3--- 60 575--- 3--- 60 580J*14D,F 208/230--- 3--- 60 460--- 3--- 60 575--- 3--- 60 STD MED HIGH STD MED HIGH STD MED HIGH STD MED HIGH STD MED HIGH STD MED HIGH STD MED HIGH STD MED HIGH STD MED HIGH NO C.O. or UNPWRD C.O. NO P.E. w/ P.E. (pwrd fr/ unit) DISC. SIZE DISC. SIZE MCA MOCP MCA MOCP FLA LRA FLA LRA 43.6 50 46 198 47.4 60 51 202 45.9 50 49 235 49.7 60 53 239 0.48 3.
APPENDIX IV.
APPENDIX V. MOTORMASTER SENSOR LOCATIONS 580J 580/558J-D08 580/558J-D12 C09226 Fig. 75 - 580J*08-- 12D,F Outdoor Circuiting NOTE: The low ambient kit for the 12.5 ton unit utilizes a pressure transducer, and therefore there is no Motormaster temperature sensor location for this unit. E2009 Bryant Heating & Cooling Systems D 7310 W. Morris St. D Indianapolis, IN 46231 Printed in U.S.A.
580J
UNIT START-UP CHECKLIST I. PRELIMINARY INFORMATION: MODEL NO.