Fan User Manual

23
Table 11 – Electrical Data — 569J*12--14D/E 60 Hz Units
WTIHOUT POWERED CONVENIENCE OUTLET
UNIT V --- P h --- H z
VOLTAGE
RANGE
}
COMP RESSOR
1
COMP RESSOR
2
OFM (ea)
POWER
SUPPLY
MIN MAX RLA LRA RLA LRA WATTS FLA MCA MOCP
569J*12D/E
208/230---3--- 60 187 253 16 110 16 110 325 1.5 40.6 60
4 6 0 --- 3 --- 6 0 414 506 7.8 52 7.8 52 325 0.8 22.5 40
5 7 5 --- 3 --- 6 0 518 633 5.7 39 5.7 39 325 0.6 16.4 30
569J*14D/E
208/230---3--- 60 187 253 22.4 149 22.4 149 325 1.5 53.4 60
4 6 0 --- 3 --- 6 0 414 506 10.6 75 10.6 75 325 0.8 25.4 30
5 7 5 --- 3 --- 6 0 518 633 7.7 54 7.7 54 325 0.6 18.5 25
WTIH POWER E D CONVENIENCE OUTLET
UNIT V --- P h --- H z
VOLTAGE
RANGE
}
COMP RESSOR
1
COMP RESSOR
2
OFM (ea)
POWER
SUPPLY
MIN MAX RLA LRA RLA LRA WATTS FLA MCA MOCP
569J*12D/E
208/230---3--- 60 187 253 16 110 16 110 325 1.5 43.8 50
4 6 0 --- 3 --- 6 0 414 506 7.8 52 7.8 52 325 0.8 21.3 25
5 7 5 --- 3 --- 6 0 518 633 5.7 39 5.7 39 325 0.6 15.7 20
569J*14D/E
208/230---3--- 60 187 253 22.4 149 22.4 149 325 1.5 58.2 80
4 6 0 --- 3 --- 6 0 414 506 10.6 75 10.6 75 325 0.8 27.7 35
5 7 5 --- 3 --- 6 0 518 633 7.7 54 7.7 54 325 0.6 20.2 25
NOTE: See “Legend and Notes for Tables 10 and 11” below
Legend and Notes for Tables 10 and 11
LEGEND:
F L A --- F u l l L o a d A m p s
LRA --- Locked Rotor Amps
MOCP --- Maximum Over Current
Protection
NEC --- National Electrical Code
RLA --- Rated Load Amps
}
Units are suitable for use on electrical systems where voltage
supplied to the unit terminals is not below or above the listed
limits.
NOTES:
1. The MCA and Fuse values are calculated in accordance with
The NEC. Article 440.
2. Motor RLA and LRA values are established in accordance
with Underwriters’ Laboratories (UL). Standard 1995.
3 . T h e 5 7 5 --- v u n i t s a r e U L , C a n a d a --- l i s t e d o n l y.
4. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply
voltage is greater than 2%. Use the following f ormula to de-
termine the percentage of voltage imbalance.
Example: Supply voltage is 230-3-60
% Voltage Imbalance = 100 x
max voltage deviation from average voltage
average voltage
AB = 224 v
BC = 231 v
AC = 226 v
Average Voltage =
(224 + 231 + 226)
=
681
3
3
= 227
Determine maximum deviation from average voltage.
(AB) 227 224 = 3 v
(BC) 231 227 = 4 v
(AC) 227 226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
4
227
= 1.76%
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.
569J