Operating instructions

CAUTION: When vent pipe is exposed to temperatures
below freezing, such as when it passes through an
unheated space or when a chimney is used as a raceway,
pipe must be insulated as shown in Table 8 with
Armaflex-type insulation. Failure to follow this caution
will result in intermittent unit operation.
CAUTION: Combustion air must not be taken from
inside structure because inside air is frequently contami-
nated by halogens, which include fluorides, chlorides,
bromides, and iodides. These elements are found in
aerosols, detergents, bleaches, cleaning solvents, salts, air
fresheners, adhesives, paint, and other household prod-
ucts. Locate combustion-air inlet as far as possible from
swimming pool and swimming pool pump house.
Excessive exposure to contaminated combustion air will
result in safety and performance related problems.
WARNING: Solvent cements are combustible. Keep
away from heat, sparks, and open flame. Use only in
well-ventilated areas. Avoid breathing in vapor or allow-
ing contact with skin or eyes. Failure to follow this
warning could result in fire, property damage, personal
injury, or death.
WARNING: All combustion-air and vent pipes must be
airtight and watertight. Pipes must also terminate exactly
as shown in Fig. 36, 37, 38, 39, or 40. Failure to follow
this warning could result in property damage, personal
injury, or death.
NOTE: The minimum combustion-air and vent pipe length (each)
for these furnaces is 5 ft. Short pipe lengths (5-8 ft) may discharge
water droplets. These droplets may be undesirable, and a 12-in.
minimum offset pipe section is recommended, as shown in Fig. 34,
to reduce excessive droplets from exiting vent pipe outlet.
COMBUSTION-AIR AND VENT PIPE DIAMETER
Determine combustion-air and vent pipe diameter.
1. Using Table 7, individually determine the smallest
combustion-air and vent pipe diameters permitted for each
pipe. Pick the larger of these 2 pipe diameters and use this
diameter for both combustion-air and vent pipes.
2. When installing vent systems of short pipe length, use the
smallest allowable pipe diameter. Do not use pipe size
greater than required or incomplete combustion, flame
disturbance, or flame sense lockout may occur.
TABLE 6—APPROVED COMBUSTION-AIR AND VENT PIPE, FITTING AND CEMENT MATERIALS
ASTM SPECIFICATION
(MARKED ON MATERIAL)
MATERIAL PIPE FITTINGS SOLVENT CEMENT AND PRIMERS DESCRIPTION
D1527 ABS Pipe Schedule-40
D1785 PVC Pipe Schedule-40
D2235 For ABS
Solvent
Cement
For ABS
D2241 PVC Pipe SDR-21 & SDR-26
D2466 PVC Fittings Schedule-40
D2468 ABS Fittings Schedule-40
D2564 For PVC
Solvent
Cement
For PVC
D2661 ABS Pipe Fittings DWV at Schedule-40 IPS sizes
D2665 PVC Pipe Fittings DWV
F438 CPVC Fittings Schedule-40
F441 CPVC Pipe Schedule-40
F442 CPVC Pipe SDR
F493 For CPVC
Solvent
Cement
For CPVC
F628 ABS Pipe Cellular Core DWV at Schedule-40 IPS sizes
F656 For PVC Primer For PVC
F891 PVC Pipe Cellular Core Schedule-40 & DWV
Fig. 33—Combustion-Air and Vent Pipe Connections
A96187
COMBUSTION-
AIR
COMBUSTION-
AIR
AIR
FLOW
VENT
VENT
VENT
AIR
FLOW
AIR
FLOW
AIR
FLOW
UPFLOW DOWNFLOW
HORIZONTAL-LEFT DISCHARGE HORIZONTAL-RIGHT DISCHARGE
Select 1 vent pipe connection and
1 combustion-air pipe connection.
COMBUSTION-
AIR
COMBUSTION-
AIR
COMBUSTION-
AIR
COMBUSTION-
AIR
VENT
VENT
VENT
NOTE: Select 1 vent pipe connection and
1 combustion-air pipe connection.
NOTE:
—25—