SYSTXBBECW01 & SYSTXBBECN01 Evolutionr Connext Control Installation Instructions A12479 NOTE: Read the entire instruction manual before starting the installation. US Patents: Carrier U.S. Pat No. 7,243,004, Carrier U.S. Pat No. 7,775,452, pointSETt U.S. Pat No.
TABLE OF CONTENTS PAGE 1. Safety Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 2. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 3. Quick Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 3.1. Set Time and Date . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 3.2.
TABLE OF CONTENTS (cont.) PAGE 4.6. Humidifier Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 4.6.1. Bypass Humidifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 4.6.2. Fan Powered Humidifiers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 5. Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 5.1. Searching for Indoor Unit . . . . . . . . . . . . .
TABLE OF CONTENTS (cont.) PAGE 6.3. Set up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 6.3.1. Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 6.3.1.1. Auto Mode set up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 6.3.1.2. Heat/Cool Deadband . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 6.3.1.3. Offsets . . . . . . . . . . . . . . . . . . .
TABLE OF CONTENTS (cont.) PAGE 6.3.3.7. Furnace Dehumidifier Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 6.3.3.8. Furnace G Terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 6.3.4. AC/Heat Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 6.3.4.1. Cooling Lockout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 6.3.4.2. Defrost Interval . . . . . . . . . . . . . . . . . . . . . . . . . . .
TABLE OF CONTENTS (cont.) PAGE 6.3.7. Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 6.3.7.1 .Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 6.3.7.2. Humidifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 6.3.7.3. Ultraviolet Lights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 6.3.7.4. Ventilator . . . . . . . . . . . . . . . .
TABLE OF CONTENTS (cont.) PAGE 6.4.9.3. Zone Duct Assessment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 6.4.9.4. Sensor Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 6.5. Service Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 6.5.1. Fan Coil Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 6.5.2. Furnace Status . . . . . . . . . . . . . . . . . . . .
1. Safety Considerations Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury or property damage. Consult a qualified installer, service agency or your distributor or branch for information or assistance. The qualified installer or agency must use factory-- authorized kits or accessories when modifying this product.
Commands, operating conditions, and other data are passed continually between components over the ABCD bus. The result is a new level of comfort, versatility, and simplicity. All Evolutionr furnaces or fan coils are variable-- speed and multi stage for maximum flexibility, efficiency, and comfort. They support controlled ventilation, humidification, dehumidification, and air quality control. Either an Evolutionr (communicating), or a standard single-- stage 24VAC controlled outdoor unit may be used.
A12501 3.2. Set Dealer Information From the main screen, touch MENU, on the bottom of the control. The SERVICE icon allows you to upload your contact information into the Evolution Connex Control. A12480 S S S Format your contact information and logo (if applicable) using the PC/MAC application, save it to a standard USB drive. See Section 6.7. Touch the SERVICE icon for about 10 seconds, then touch DEALER LOGO UPLOAD.
Control and follow the on screen prompts. 4. 4.1. Installation Overview This instruction covers installation of the Evolutionr Connext Control and the Evolutionr Wireless Access Point only. Physical installation instructions for the indoor and outdoor equipment, and accessories are provided with each unit. Setup, commissioning, operation, and troubleshooting of the Evolutionr System are covered only in this installation instruction.
4.3. Location ! WARNING ELECTRICAL OPERATION HAZARD Failure to follow this warning could result in personal injury or death. Disconnect power before routing control wiring. All wiring must comply with national, local, and state codes. 4.3.1. Wall Control The Evolution Connex Control is the command center for the Evolution System. It should be located where it is easily accessible and visible to the adult homeowner or end user.
S S Close to or in direct airflow from supply registers. In areas with poor air circulation, such as behind a door or in an alcove. 4.3.2. Remote Room Sensors A Remote Room Sensor can be used with the Evolution Connex Control to take the place of the control’s internal temperature sensor. This allows the Evolution Connex Control to be mounted in areas with less than optimal airflow (such as near an exterior door, window or in a closet).
4.3.3. Smart Sensors (for zoning applications) Any zone may use a Smart Sensor. It provides a temperature display and buttons to adjust the desired temperature in that zone only. It also displays outdoor temperature and indoor humidity sensed at the control. Only one Smart Sensor may be used per zone. They cannot be averaged like Remote Room Sensors. If a Smart Sensor is used in a zone, a Remote Room Sensor may also be used in the same zone. The Remote Room Sensor has priority over the Smart Sensor.
A B C D A03193 It is not mandatory that the above color code be used, but each ABCD connector in the system MUST be wired consistently. NOTE: Some outdoor units provide their own low-- voltage power source and do not require the “C” (24VAC common) and “D” (24VAC power) connections. See the outdoor unit installation instructions for more information. ! WARNING ELECTRICAL OPERATION HAZARD Failure to follow this warning could result in personal injury or death.
Discard or recycle old control. S NOTE: Mercury is a hazardous waste, if existing control contains any mercury, it MUST be disposed of properly. The Evolution Connex Control does not contain mercury. Select Evolution Control mounting plastic (backplate and decorative backplate if desired). Route wires through large hole in mounting plastic. Level rear plastic against wall (for aesthetic value only; Evolution Connex Control need not be level to operate properly) and mark wall through two mounting holes.
NOT be connected to any terminal at the user interface. Connecting the shield to ground at both ends can cause current loops in the shield, reducing shield effectiveness. Connect one pair of the two-- pair (minimum) cable to the A and B communication terminals, and another pair to the C and D terminals at both ends of the cable. The shield wire should ONLY be connected at the indoor equipment ground or C terminal. Note that some outdoor units only require the A and B connections.
! CAUTION PERSONAL INJURY HAZARD Failure to follow this caution may result in personal injury. To prevent possible damage to the Damper Control Module, DO NOT mount on plenum, ductwork, or flush against furnace or fan coil. 4.5. Mounting First become familiar with all plastic assembly pieces shown on the following page. The Evolution Connex Control will snap together with the backplate. A backplate is supplied.
A12215 NOTE: Once Evolution Control is secured to wall with the backplate assembly (snapped together), care must be taken not to bend or break the interlocking tabs when removing. 4.5.1. Decorative Backplate Sold separately, a thin decorative backplate is available to hide any marks/screw holes left from the previous thermostat. This decorative backplate (or beauty ring) is used by snapping it onto the back of the mounting plate before securing the plate to the wall.
NOTE: Once the Evolution Connex Control is secured to wall with the backplate assembly (snapped together), care must be taken not to bend or break the interlocking tabs when removing. 4.6. Humidifier Connections A 24VAC bypass or fan powered humidifier may be installed. NOTE: Do NOT use a traditional humidistat to control humidifier operation. If a humidifier is installed, let the Evolution Connex Control operate humidifier. 4.6.1.
variable-- speed furnace / fan coil with a 2-- stage air-- conditioner / heat pump (including Hybrid Heatr dual fuel system). 5.1. Searching for Indoor Unit The Evolution Connex Control will light up and begin the commissioning process by displaying “Searching for indoor unit”. A12177 NOTE: If the variable-- speed indoor equipment (furnace or fan coil) cannot be found, the control will display “Indoor unit not found”. This MUST be corrected before the initial power up sequence can continue.
A12178 5.2. Searching for Outdoor Unit The Evolution Connex Control will then proceed to communicate with the outdoor unit by displaying “Searching for outdoor unit”. NOTE: If the outdoor unit cannot be found, the control will display “Outdoor unit not found”. S Select the appropriate unit installed; then, touch NEXT.
A12183 5.3. Indoor Evaporator Selection If a furnace is installed with a variable capacity heat pump, a screen will appear to select the installed indoor evaporator coil. This selection is used to adequately calculate the refrigerant charge required while in the heat pump charging screens under the Heat Pump Checkout menu (See page 44). Select “other” for non-- Bryant evaporators. 5.4.
A12184 5.4.1. Hydronic Heat Application The Evolution Connex Control supports 2 types of Hydronic Heat applications: 1. Hot water coil in combination with an FE fan coil and heat pump, or hot water coil as sole heat source with an FE fan coil. 2. Non-- zoned FE fan coil combined with radiant hot water heat. In either application, a Hydronic Heat kit should be installed in place of an electric heater. See FE fan coil Product Data for accessory part number.
See the Smart Sensor Installation Instructions on how to assign Smart Sensors to their respective zones. After each zone has been identified, touch NEXT. A12185 5.6. Filter Type Selection The installer will next be prompted to select the air filter type installed with the Evolution System. After the selection is made, touch NEXT. S Air Filter: 1-- in. to 4-- in. media filter S EAC: high voltage electronic air cleaner S Air Purifier: Evolutionr or Preferredt Air Purifier 5.7.
5.9. Equipment Summary The equipment summary screen will appear after accessories have been selected. This screen will give a summary of all equipment automatically found or manually selected. If an incorrect selection was made, touch RE-- INSTALL to go back to that particular screen and make changes. When everything is OK, touch NEXT to continue. A12502 5.10. Static Pressure Check This function is not available with the 986T furnace. The static pressure check screen will appear next.
5.11. Duct Assessment (zoning applications only) The duct assessment screen will be displayed next for zoning applications. Touch NEXT to start Duct Assessment. Duct Assessment will measure the relative size of the ductwork, up to and through the dampers. These measurements are used to control the correct amount of airflow in the zoned system. Status messages will appear on the screen to indicate what the system is doing. The process will take approximately one minute per zone.
A12186 6. Service Menu The Service menus contain a set of vital information. This information enables the installer or service person to view a summary of what has been installed, etc. This information is not covered in the Owner’s Manual. To enter service menus, touch menu, then touch and hold the SERVICE icon for at least ten seconds. The following screens are available in installation and service. To return to the previous screen, touch BACK. To exit the Service menus, touch DONE.
6.1. Equipment Summary Touch EQUIPMENT SUMMARY to show indoor unit type and model number, outdoor unit type (and model number if a 2-- stage unit), filter type, any accessories that are installed, and the number of zones in the system. To return to the previous screen, touch BACK. To exit the Service menus, touch DONE. A12502 6.2. Installation Touch INSTALLATION to perform the start-- up process in order to learn all equipment in system. Press right side button to initiate the process.
6.3. 6.3.1. Set up Thermostat First touch SETUP, then touch THERMOSTAT to set up the parameters for the Evolutionr Connex Control. A12187 6.3.1.1. Auto Mode set up Once the auto changeover option has been selected, touch SAVE. S Enable or Disable: Choose to enable or disable auto changeover mode d Default = Enable S Auto changeover time: Adjustable from 5 to 120 minutes d Default = 30 minutes 6.3.1.2.
d Default = 2_F 6.3.1.3. Offsets This option allows calibration (or deliberate miscalibration) of the temperature and humidity sensors. These offsets are added to the actual temperature/humidity values. When the correct offsets are made, touch SAVE. S Outdoor temperature: Adjustable from - 5 to 5_F (-- 3 to 3_C) d Default = 0_F S Humidity: Adjustable from - 10 – 10% d Default = 0% 6.3.1.4. Reset factory defaults This option allows the installer to reset certain factory parameters.
6.3.1.6. Smart Recovery Enable Applies to programmable operation only. Will start recovery 90 minutes prior to schedule change in both heating and cooling mode. After the selection is made, touch SAVE. S Smart Recovery: On or Off d Default = On 6.3.1.7. Temperature Units Display This option allows the installer to choose between Fahrenheit and Celsius display. After the selection is made, touch SAVE. S Display Option: Selectable between _F and _C d Default = _F 6.3.2.
6.3.2.1. Fan Coil Airflow This option allows the installer to select the appropriate air flow based on the needs of the installation. The QUIET airflow means the minimum cooling airflow that the system can safely run (typically 300 CFM/ton). Use this setting if duct noise is a severe problem. Note that duct sweating in high humidity environments could become an issue at low airflows. The COMFORT airflow means airflow is varied depending on humidity and temperature demand settings.
6.3.2.2. Fan Coil Dehumidification The Dehum Drain Time option turns off the continuous fan at the end of cooling for five minutes in order to drain the indoor coil of water. The fan will only be turned off if a dehumidify demand existed at the start of or during the cooling cycle. The Electric Reheat option enables the electric heat to be used while cool-- to-- dehumidify is running. This will allow the cool-- to-- dehumidify function to run longer, greatly improving humidity control in cooling mode.
d d Normally Open Normally Closed 6.3.3. Furnace First touch SETUP, then touch FURNACE to set up the parameters for the furnace unit. A12189 6.3.3.1. Furnace Airflow Selects the airflow of the furnace when heating. EFFICIENCY is the airflow used to meet specified ratings, COMFORT is a decreased airflow used to increase the output air temperature and provide increased comfort. For the Low heat rise option, set to ON if the system contains a bypass humidifier.
6.3.3.2. AC/HP Air Flow This option elects the airflow of the furnace when cooling, heat pump heating, and dehumidification. The QUIET airflow means the minimum cooling airflow that the system can safely run (typically 300 CFM/ton). Use this setting if duct noise is a severe problem. Note that duct sweating in high humidity environments could become an issue at low airflows. The COMFORT airflow means airflow is varied depending on humidity and temperature demand settings.
6.3.3.3. Furnace Staging The operation of this option will vary based on the furnace installed. SYSTEM setting will allow the Evolutionr Zone Control to determine furnace staging. FURNACE setting will allow the furnace to determine staging. LOW will only run the low stage of furnace heat. LOW-- MED will run the low and medium stages (2 stages of heat). MED will only run the medium stage of heat. MED-- HIGH will run the medium and high stages (2 stages of heat).
S Furnace Off Delay: 90, 120, 150 or 180 seconds Default = 120 seconds d 6.3.3.6. Altitude This setting will adjust the furnace’s airflow to compensate for altitude. Altitude adjustment is not available with older furnaces. Please see furnace instructions for further details. After the selection is made, touch SAVE. S Altitude: 0000 – 2000, US 2001 – 3000, CN 2100 – 4500, US 3001 – 4000, US 4001 – 5000, US 5001 6000, US 6001 – 7000, US 7001 – 8000, US 8001 – 9000, and US > 9000.
Default = Low Shutdown: d Normally Open d Normally Closed d S 6.3.4. AC/Heat Pump First touch SETUP, then touch AC/HEAT PUMP to set up the parameters for the AC/Heat Pump unit.
6.3.4.1. Cooling Lockout Outside temperature below which cooling will not be provided. After the selection is made, touch SAVE. S Cooling Lockout Temp: None, 45, 50 or 55 (_F) d Default = None 6.3.4.2. Defrost Interval Time interval at which defrost cycles can occur on a heat pump. AUTO means the defrost interval is optimized by the outdoor control. After the selection is made, touch SAVE. S Set Defrost Interval: 30, 60, 90, 120 minutes or AUTO d Default = 30 minutes 6.3.4.3.
6.3.4.5. AC/Heat Pump RPM Max Used with variable capacity heat pumps, this option clamps the operating speed of the heat pump to this maximum value. Used to reduce operating noise while in high heating capacity. Reducing this value will reduce the heating capacity of the heat pump. After the selection is made, touch SAVE. S AC Heat Pump Max RPM: Adjustable from 4500 – 7000 d Default = 4500 RPM d Default = Off 6.3.4.6.
For hydronic heat applications, this option allows the installer to set the lockout temperatures below the which only the hydronic coil will operate, and the lockout temperature above which the hydronic coil will not operate. After the selections are made, touch SAVE.
A12191 6.3.6.1. Zoning Disable This option allows the installer to enable or disable zoning. After the selection is made, touch SAVE. S Disable Zoning: Yes or No d Default = No 6.3.6.2. Zone Offsets This option allows actual temperature offset for each zone, allowing calibration (or deliberate miscalibration) of each sensor. Use the Left (<) or Right (>) buttons to change the zone. After the selection is made, touch SAVE.
airflow; HIGH means 250% of maximum assessed airflow; and NO LIMIT means the equipment does not stage down. CFM associated for each limit is shown on the screen. Compare this value with the equipment’s low stage CFM value to ensure that equipment will run for each zone. Assessed airflow is determined as described in DUCT ASSESSMENT. After the selections are made, touch SAVE.
A12192 6.3.7.1. Filter With this option, the installer has the option of selecting pressure monitoring, the type of filter installed, and the time interval for cleaning. After the selections are made, touch SAVE.
S Change Pad: Selectable from 1 to 24 months Default = 12 months Humidify with Fan: Yes or No d Default = No d S 6.3.7.3. Ultraviolet Lights With this option, the installer has the option of selecting whether ultraviolet lights are installed, and the time interval for changing the ultraviolet lights. After the selections are made, touch SAVE.
lows stage when the curtailment function is active. After the selections are made, touch SAVE. A12193 S S Cooling: Disabled, Low Stage or Turn off d Default = Disabled Heat Pump: Disabled, Low Stage or Turn off d Default = Disabled 6.3.9. Hydronic Airflow This option allows the installer to select the airflow for the fan coil when paired with a hydronic coil. After the selections are made, touch SAVE.
S Airflow: Selectable from Off to Max in 50 CFM increments Off = 450 CFM, MAX = (odu_size in KBTU * 400) / 12) d Default = Off Blower On Delay: Selectable from 0 to 240 seconds d Default = 30 seconds Blower Off Delay: Selectable from 0 to 240 seconds d Default = 0 seconds d S S 6.4. Check out Touch CHECKOUT to view the equipment installed in the system. Perform checkout test to make sure each piece of equipment is operating properly.
6.4.1. Electric Heat If you have a fan coil with electric heaters, this menu item will allow the heaters to be exercised. With self-- identifying electric heaters, three stages of electric heat are available to be exercised in any combination. Non-- identifying heaters will only provide one stage of heat. After the selections are made, touch START.
S Hydronic heater check: Selectable from 0 to 120 minutes Default = 5 minutes d 6.4.4. Air Conditioning This option allows the air conditioner to be exercised. With a 2-- stage AC unit, a low cool and a high cool run time are independently selectable to exercise. The display will change to show the AC operating status. After the selections are made, touch START. NOTE: Airflows during Checkout modes are fixed to the EFFICIENCY setting and are independent of other airflow settings.
S Low Heat Run Time: Selectable from 0 to 120 minutes Default = 5 minutes High Heat Run Time: Selectable from 0 to 120 minutes d Default = 5 minutes Speed (variable speed heat pump only): Selectable from lowest available to 100% d Default = lowest available as specified by variable speed heat pump Defrost: Yes or No d Default = No d S S S 6.4.6. Heat Pump Cooling The heat pump cooling mode can be exercised with this menu option.
100% d Default = lowest available as specified by variable speed heat pump 6.4.7. Humidifier The humidifier can be exercised On and Off with this menu option. To end the humidifier checkout, touch STOP. S Humidifier Check: On or Off 6.4.8. Ventilator The ventilator can be exercised through all of its operating speeds with this menu option. To end the ventilator checkout, touch STOP. S Ventilator Check: High, Low or Off 6.4.9.
6.4.9.2. Damper/Sensor Check The Sensor/Damper Check allows the installer to check each zone damper for operation, as well as insure the zone sensor corresponds to that particular zone. When first initiated, the Zone 1 damper will fully open, and all other zones will close. Using the Left (<) or Right (>) buttons, the installer can select each zone and verify the damper is fully open while all other dampers remain closed.
6.4.9.4. Sensor Type This option shows a list of all zones with corresponding sensor types. 6.5. Service Information The Service Info menu will only show the equipment installed in the system. To enter this menu of options, touch SERVICE INFORMATION. A12196 6.5.1. Fan Coil Status The fan coil status screen displays relevant information about the fan coil operation. To return to the previous screen, touch BACK. To exit the Service menus, touch DONE.
A12197 6.5.2. Furnace Status The furnace status screen displays relevant information about the furnace operation. To return to the previous screen, touch BACK. To exit the Service menus, touch DONE. A12198 6.5.3. AC Status The AC status screen displays relevant information about the AC operation. To return to the previous screen, touch BACK. To exit the Service menus, touch DONE.
A12199 6.5.4. Heat Pump Status The heat pump status screen displays relevant information about the heat pump operation. To return to the previous screen, touch BACK. To exit the Service menus, touch DONE. A12200 6.5.5. Zoning Status The zoning status screen displays relevant information about the zoning operation. To return to the previous screen, touch BACK. To exit the Service menus, touch DONE.
A12201 6.5.6. Last 10 System Faults This screen will show the last 10 events that occurred throughout the system. Each entry has the time and date incident recorded. These events are stored in the memory of the control and are resettable in the THERMOSTAT SETUP screen under the RESET FACTORY DEFAULT selection. Each entry shows the equipment that generated the event. To return to the previous screen, touch BACK. To exit the Service menus, touch DONE.
6.5.7. Run/Fault History This information is stored in the equipment circuit boards (if communicating) and displayed on the control. The indoor unit and outdoor unit (if communicating) have the following histories. To return to the previous screen, touch BACK. To exit the Service menus, touch DONE. S Resettable Faults: Fault counters for each piece of equipment that can be reset. S Cycle Counters: Number of heat/cool/power cycles the unit has performed.
6.5.9. Service Phone Number This menu item allows the installer to view the name and phone number that the homeowner can call for future service of the system. This name and phone number will appear to the homeowner whenever a service reminder pop-- up message is displayed (i.e. Change Filter, etc.). To return to the previous screen, touch BACK. To exit, touch DONE. See Section 6.7. 6.6.
Next, the installer will enter the WEIGH IN screen to verify the current total charge is accurate. Once the installer has confirmed, touch DONE. Next, the installer will enter the SERVICE VALVE SUBCOOL screen. This screen will show the current liquid line subcool target (in _F). To begin the charging, touch START. Next, the installer will enter the SERVICE VALVE INFORMATION screen.
inadequate vacuum obtained. The control has provisions to open the EXV for refrigerant recovery and/or evacuation. S Set desired time period. d Default time period for procedure is 120 minutes. S Touch START on UI to open the valve. S Begin evacuation or refrigerant recovery as required for the procedure after control indicates the EXV is open. Power may be removed from heat pump after the control indicates “READY TO EVACUATE.” 6.7.
The PC/MAC software application to format the dealer logo and contact information can be found at: www.HVACpartners.
A12205 7. Wireless and Remote Access Setup (Wi-- Fi Option, only) The Evolutionr Connext Control, when supplied with the Wi-- Fi option, may be accessed by consumers through the www.MyEvolution.com website, or by dealers through www.HVACpartners.com. The Evolution Connex Control connects to a home Internet connection through an existing home Local Area Network (LAN).
the user’s internet service provider or mobile device carrier service.
indicator lights will begin to blink (LAN Activity, Wi-- Fi Activity and WAN/Internet Activity). Verify the signal strength of the wireless access point radio signal at the desired location of the Evolution Connex Control with a wireless laptop computer or mobile phone with Wi-- Fi network scanning capabilities. Use the Scan for Wireless Networks utility and verify that the signal for “MyHVACxxxxxx” is “Strong” or better.
A12115 S Select the myHVACxxxxxx connection from the list, then touch NEXT d Note that “myHVAC” is followed by the last 6 digits of your Wireless Access Point’s MAC address d This is the “SSID” of the Wireless Access Point d The SSID for the Wireless Access Point may also be found on a label on the bottom of the Wireless Access Point d You may have to use the down arrow to scan to the next screen to find the “myHVACxxxxxx”SSID A12162 59
S Use the on-- screen keyboard to enter the Wi-- Fi security key, then touch NEXT The security key can be found on the label on the bottom of the Wireless Access Point d Touch in the security key area, and the keyboard will appear d Begin typing and the ENTER TEXT label will disappear d A12163 S The control will inform you if the connection is successful. If so, touch DONE.
A12165 Verify the status of the Wi-- Fi connection by touching VIEW REMOTE ACCESS STATUS on the WI-- FI SETUP screen d “Connected” should appear next to Network Status d If the Network Status is “not connected”, repeat the process in section 7.2 d The MyEvolution Server status may take up to 15 minutes to show “Connected” due to Internet traffic d If the MyEvolution Server status fails to show “Connected” after 15 minutes, check Internet connectivity with other devices in the home.
WI-- FI SETUP screen, touch MYEVOLUTION REGISTRATION INFO. Write down the Evolution Connex Control Serial Number, MAC Address, and PIN that are displayed on this screen. This is the information that the consumer will need to register on the www.MyEvolution.com website. It is also the information that you may need to identify the system through www.HVACpartners.com, if the homeowner allows you access to their system.
8. Appendix A - Wiring Diagrams Variable-Speed Furnace/ Fan Coil User Interface A B C D S1 S2 Green - Data A Yellow - Data B White - COM A Green B Yellow C Red - 24VAC D Optional Remote Room Sensor HUM Humidifier Connection Communicating AC or H P* White Red A B C D ABCD Connections COM 24V OAT OAT Sensor (Optional) *NOTE: Some outdoor units do not require the “C” and “D” connections. See outdoor unit Installation Instructions.
Variable-Speed Furnace/Fan Coil User Interface A B C D S1 S2 Green - Data A Yellow - Data B White - COM Red - 24VAC A B C D Optional Remote Room Sensor Humidifier Connection ABCD Connection HUM 1-Spd.
Variable-Speed Fan Coil User Interface Green - Data A A A Yellow - Data B B B White - COM C C Red - 24VAC D D S1 S2 Optional Remote Room Sensor Humidifier Connection ABCD Connection HUM C 1-Spd.
Zone Control User Interface & Smart Sensor(s) Green Yellow A B C D White Red A B C D Indoor Unit Communicating AC or HP A A B B C C D D A B C D Humidifier Connection Damper Control module HUM COM 24V OAT Sensor (Optional) OAT A04018 Zoning Connection for Communicating Indoor Unit with 2-- Stage Communicating Outdoor Unit 66
Indoor Unit Zone Control User Interface & Smart Sensor(s) A B Green Yellow C D White Red A B C D A B C A B C D 1-Stage .
Variable-Speed Fan Coil Zone Control User Interface & Smart Sensor(s) Green A Yellow B A B C D White C Red D A B C D 1-Spd.
R FE Fan Coil or Variable Speed Furnace G A07114 G Input Wiring for Blower Operation 69
R FE Fan Coil or Variable Speed Furnace G A07115 G Input Wiring for System Shutdown 70
TP-- LINK is a registered trademark of TP-- LINK TECHNOLOGIES CO., LTD. E2013 Bryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231 Edition Date: 01/13 Catalog No: II---SYSTXBBEC ---02 Manufacturer reserves the right to change, at any time, specifications Replaces: II--- SYSTXBBEC--- 01 and designs without notice and without obligations.