Install Instructions

31
S Furnace Off Delay: 90, 120, 150 or 180 seconds
d Default = 120 seconds
6.3.3.6. Altitude
This setting will adjust the furnace’s airflow to compensate for altitude. Altitude
adjustment is not available with older furnaces. Please see furnace instructions for
further details. After the selection is made, touch SAVE.
S Altitude: 0000 2000, US 2001 3000, CN 2100 4500, US 3001 4000,
US 4001 5000, US 5001 6000, US 6001 7000, US 7001 8000, US 8001
9000, and US > 9000.
d Default = US 2001--3000
6.3.3.7. Furnace Dehumidifier Drain
This option selects the time the continuous fan turns off at the end of cooling in
order to drain the indoor coil of water. The fan will only be turned off if a
dehumidify demand existed at the start of or during the cooling cycle.
S Dehumidify Drain Time: Adjustable from 5 to 60 minutes
d Default = 15 minutes
6.3.3.8. Furnace G Terminal
This setup option selects desired operation when the R--G circuit changes state on
the furnace control board depending on setup.
Under the function option, FAN turns on fan to selected fan speed when G terminal
is energized. SHUTDOWN shuts off fan and equipment when initiated.
After the selections are made, touch SAVE.
S Function: Disabled, Fan or Shutdown
d Default = Disabled
S Fan Speed:Low,Med,orHigh