Install Instructions

41
S Airflow: Selectable from Off to Max in 50 CFM increments
d Off = 450 CFM, MAX = (odu_size in KBTU * 400) / 12)
d Default = Off
S Blower On Delay: Selectable from 0 to 240 seconds
d Default = 30 seconds
S Blower Off Delay: Selectable from 0 to 240 seconds
d Default = 0 seconds
6.4. Check out
Touch CHECKOUT to view the equipment installed in the system. Perform
checkout test to make sure each piece of equipment is operating properly.
A12195