T6−PAC, T6−PHP, T6−NAC, T6−NHP PREFERREDt SERIES AC / HP THERMOSTAT Installation Instructions A07045 Programmable Control A07044 Non-Programmable Control Designed and Assembled in the U.S.A. NOTE: Read the entire instruction manual before starting the installation. US patents: US7287709 B2, US20080147242 A1, USD582800 SI, US20060165149 A1, US6956463 B2.
TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 INSTALLATION CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 SYSTEM START−UP AND CHECKOUT . . . . . . . . . . . . . . . . . . . . . . . . . .
INTRODUCTION Bryant’s 7−day, 5/2−day, 1−day programmable and non−programmable Preferred Series Thermostat Control is a wall−mounted, low−voltage temperature control in either a single unit or a two−piece unit. In two−piece configuration, the relays are located near the equipment and a two−wire connection is used between the Display Module and the Equipment Control Module. Single−piece installation requires more wiring and results in a higher profile.
INSTALLATION CONSIDERATIONS Power This control is powered by 24VAC only. It requires 24VAC (Rh and/or Rc and C terminals) of the low−voltage transformer to be connected to it for proper operation. It will not operate without these 2 connections. Rh and Rc are connected via PCB breakout jumper. See Fig. 1. For applications using two 24VAC transformers, one in the indoor unit and one in the outdoor unit, connect the common from each to the C terminal. Connect R from the indoor unit to the Rh terminal.
A07052 Fig. 1 − PCB Breakout Jumper Models There are programmable and non−programmable models for all applications. They can be configured for AC or HP installations, allowing it to be used in place of all Bryant thermostats. Programmable thermostats may be configured as non−programmable if user desires. Outdoor Temperature Sensor The outdoor air temperature sensor is not included with the AC/HP Control. It is available as an accessory, part number TSTATBBSEN01−B.
dedicated sensor wires may be used for its connection. Details are provided in sensor instructions. Remote Indoor Temperature Sensor A remote temperature sensor may be used with the programmable heat pump and programmable air conditioner thermostats where it is desirable to install the thermostat in a limited access location while measuring the temperature in the living space. The remote room sensor may be used as a stand alone or average with local sensor.
Wiring Wire length should be no more than 250 ft (76m). Use 22 AWG for normal wiring applications. Continuous wire lengths over 100 ft (30.5m) should use 20 AWG or larger. INSTALLATION Carton contains the following components. See Fig. 2 for programmable models or Fig. 3 for non−programmable models. A07756 Fig. 2 − T6−PAC / T6−PHP Carton Contents 1. 2. 3. 4.
A07757 Fig. 3 − T6−NAC / T6−NHP Carton Contents 1. 2. 3. 4. Display Module Stand−off for Equipment Control Module Screws and pig tail Equipment Control Module AC/HP Control Location AC/HP Control should be mounted: Approximately 5 ft (1.5m) from floor. Close to or in a frequently used room, preferably on an inside partitioning wall. On a section of wall without pipes or duct work.
AC/HP Control should NOT be mounted: Close to a window, on an outside wall, or next to a door leading to the outside. Exposed to direct light or heat from a lamp, sun, fireplace, or other temperature−radiating objects which could cause a false reading. Close to or in direct airflow from supply registers and return−air registers. In areas with poor air circulation, such as behind a door or in an alcove. Installer should determine whether control will be installed as single−piece or two−piece.
! CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation. Improper wiring or installation may damage AC/HP Control. Check to make sure wiring is correct before proceeding with installation or turning on power. 1. Turn off all power to equipment. 2. If an existing thermostat is being replaced a. Remove existing thermostat from wall. b. Disconnect wires from existing thermostat, 1 at a time. c.
Two−Piece Installation The following steps should be followed for the installation of the two−piece configuration. NOTE: The 2−wire pigtail is not intended to support the weight of the User Interface. Do not hang the User Interface from the equipment Control Module screw terminals. 1. Remove mounting plate from back of Display Module by pressing the two tabs on the bottom edge and pulling away. See Fig. 4 and 5. A07225 Fig.
A07226 Fig. 5 − Take Apart 2. Route wires through large hole in mounting base. Level mounting base against wall (for aesthetic value only—Display Module need not be leveled for proper operation) and mark wall through 4 mounting holes. To avoid unintended bending of wall plate plastic, use all 4 screws and anchors. See Fig. 6.
A07165 3. 4. 5. 6. Fig. 6 − Backplate Mounting Drill two 3/16−in. mounting holes in wall where marked. Thermostat may be mounted to a standard junction box, if desired. Hole pattern on thermostat mounting base matches junction box mounting holes. Secure rear plastic mounting base to wall with 4 screws and anchors provided. To avoid unintended bending of wall plate plastic, use all 4 screws and anchors Make sure all wires extend through hole in mounting base.
Control Module Wiring Guide Relays OAT RRS {SRTN HUM D1 dry contact D2 connect V+ to user interface Vg Rc Rh W / W1 G Y/Y2 C O/W2/B Y1 OAT / RRS return Y used for single stage cooling Y1 used for multi-speed cooling Y1 = stage 1 Y2 = stage 2 A07687 Fig. 7 − Control Module Wiring Guide HUM terminal is not used on this model.
A07166 Fig. 8 − Secure Wires to Terminal Strip A07167 Fig.
NOTE: The 2−wire pigtail is not intended to support the weight of the User Interface. Do not hang the User Interface from the equipment Control Module screw terminals. Red is V+ Black is Vg 7. Push any excess wire into wall and against mounting base. Seal hole in wall to prevent air leaks. Leaks can affect operation and cause incorrect temperature and/or humidity measurement. 8. Make sure to attach 2−wire pigtail to Display Module mounting base. It is packed loose in the box from the factory.
10. Find suitable indoor mounting location for Equipment Control Module, either near or on equipment. See Fig. 11. IMPORTANT NOTE: Equipment Control Module should not be mounted to duct work or below any other controls or equipment (i.e. humidistat, humidifier, etc.). A07217 Fig. 11 − Equipment Control Module on Equipment 11. Route wires through rear of Equipment Control Module using either a clearance hole or supplied standoff. See Fig. 12.
A07227 Fig. 12 − Standoff NOTE: Standoffs are provided as an aid when installing Equipment Control Module on inside equipment or a solid wall. 12. Match and connect equipment wires to proper terminals of each connector block being careful not to over tighten the screws. Correct polarity must be observed when connecting the two wires from the Equipment Control Module to the thermostat mounting base. If wires are connected incorrectly, the Display Module will not operate. See Fig. 7, 8 and 9. 13.
A07218 Fig. 13 − Cover on Equipment Control Module 14. Turn on power to equipment. On power up, all display segments will light for 5 sec. For the next 5 sec a 2−digit code appears on large display which identifies AC/HP Control configuration. Refer to Option 33. a. AC — 1−stage air conditioner, AC, with furnace or fan coil b. HP — 1−stage heat pump, HP only with fan coil c. H — heating only system, furnace only or fan coil with electric heat only d. C — cooling only system, AC with fan coil e.
Single−Piece Installation The following steps should be followed for the installation of the single−piece configuration. 1. Remove cover from Equipment Control Module by pressing the two tabs on the bottom edge and pulling away. Route wires through large hole in Equipment Control Module. Level Equipment Control Module against wall (for aesthetic value only − Equipment Control Module need not be leveled for proper operation) and mark wall through 4 mounting holes.
A07219 Fig. 14 − Equipment Control Module 5. Match and connect equipment wires to proper terminals of each connector block. 6. Push any excess wire into wall and against Equipment Control Module. Seal hole in wall to prevent air leaks. Leaks can affect operation and cause incorrect temperature and/or humidity measurement. 7. Remove 2−wire pigtail from thermostat mounting base and attach to Equipment Control Module terminal block (terminals V+ and Vg).
A07221 Fig. 15 − Reattach Display Module 9. Turn on power to equipment. On power up, all display segments will light for 5 sec. For the next 5 sec a 2−digit code appears on large display which identifies AC/HP Control configuration. Refer to Option 33. a. AC — 1−stage air conditioner, AC, with furnace or fan coil b. HP — 1−stage heat pump, HP only with fan coil c. H — heating only system, furnace only or fan coil with electric heat only d. C — cooling only system, AC with fan coil e.
must be properly set by the installer. (Only those marked with an asterisk * below are available to the homeowner.) The homeowner configurations are described in the owner’s manual. A special procedure allows entry into the configuration mode. Description of each selection and how to use the configuration mode follows.
Option 18* — Option 19 — Option 20 — Option 21* — Option 24* — Backlight Configuration Dry Contact (programmable models only) Outdoor Air Temperature Offset Adjustment Keypad Lockout Programmable/Non−Programmable (programmable models only) Option 25* — Number of Programmable Periods per Day (programmable models only) Option 26 — Minimum Cooling Setpoint Option 27 — Maximum heating Setpoint Option 28 — UV Light Reminder Option 29 — Humidifier Pad Reminder Option 30* — Programmable Fan (programmable models o
WHILE IN CONFIGURATION MODE The option number is displayed in the heat setpoint location and the configuration setting is displayed in the cool setpoint location. On the T6−PAC/PHP (programmable) models, a box will surround the option number. The mode button is used to move the box between the two displayed values. The soft keys below the listed values may also be used to move the box between selected values. The value inside the box is changed by using the UP/DOWN buttons.
Defaults HP model defaults to HP. AC model defaults to AC. Option 02 — Clean Filter Timer Select hours of blower operation (heating, cooling, or fan) before CHECK FILTER icon is displayed. With OF selected, icon will never come on, disabling this feature. Time selection can range from 800 to 7200 hr by selecting numbers 1 through 9. (Time is 800 X number selected.) Default is 4 (3200 hr).
RRS SRTN Sensor 1 Sensor 2 Sensor 3 Sensor 4 A09130 Fig. 16 − Remote Room Sensor − Parallel Wiring This selection determines which sensor the control will use for measuring room air temperature. Room air temperature can be sensed in one of three ways; the local sensor (L) located on the Display Module, the remote room air sensor (r), or the average of local and remote sensors (Lr). Settings are L, r, Lr. Default is L.
Option 07 — Zoning This selection should be set to On when the thermostat is to be used as part of a zoning system. It is assumed that the zoning equipment will take care of time guard and cycle timers. The minimum on time is still controlled by the thermostat. Default is OF (off). Option 08 — Auxiliary Heat Lockout Temperature This selection is available on heat pump systems with a valid outdoor temperature sensor connected. Available settings are: Off, 5, 10, 15, 20, 25, 30, 35, 40, 45, 50, 55.
C — Reversing valve output (O/W2/B) is energized when COOL mode is selected. Default is C. Option 11 — Deadband Setting Between Heat & Cool This option is not available on Heat Only and Cool Only systems. This selection is to allow the installer to choose how much differential exists between the heating and cooling setpoints. Allowable selections are 1−6. Default is 2. Option 12 — Smart Recovery Smart Recovery OF (off) means setpoints change precisely at setback recovery time.
On — Auto mode is available. OF — Auto mode is not available. Default is On. Option 16 — Maximum Cycles Per Hour This selection limits the number of cycles per hour that the thermostat allows the system to operate. Selections are 2, 4, 6. 2 — The heating and cooling outputs will be energized no more than 2 times per hour. When an output is energized, it will not be energized again for 30 minutes. 4 — The heating and cooling outputs will be energized no more than 4 times per hour.
becomes brighter when a button is pressed. After 10 seconds of no button presses, the backlight will return to the dimmer level until another button press occurs. The range of brightness is 1 through 5 with 5 being full brightness. Default is 3. Option 19 — Dry Contact Configuration (programmable models only) There are 2 available selections, OF and 1. OF — The dry contact is always de−energized. 1 — The dry contact will be energized for the specified number of minutes per hour.
1 — The user has access to modify setpoints, time of day. 2 — The user has access to change the setpoints only. 3 — The entire keypad is locked. When a button is pressed, the backlight will turn on but none of the operating parameters will be changed. When the keypad lock selection is turned on, the padlock icon will be displayed. To unlock the keypad, press and hold the UP/DOWN buttons simultaneously for five seconds. When the keypad is unlocked, the padlock icon will turn off.
Option 22 — High Cool Latch Temperature (only available if outdoor sensor is present) An outdoor sensor is required for high cool latch feature. This selection is only available when Option 1 is set to H2, A2, or h2 and when Option 7 (zoning) is set to OF (off). Configuration settings are OF (off), 80, 85, 90, 95, 100, 105, 110, On. OF (off) — Cooling always starts in low stage (Y1) and stages up to high stage (Y1 and Y/Y2) when demand is sufficient and staging timer constraints have been satisfied.
When a cycle starts under a high heat latch, it will finish the heating cycle on high stage. On — The Y1 and Y/Y2 outputs are simultaneously energized to satisfy all heating demands. Default is OF (off). Option 24 — Programmable/Non−Programmable This selection allows the installer to configure the thermostat as either programmable or non−programmable. Selections are P, nP. Default is P (programmable models only).
Option 27 — Maximum Heating Setpoint This selection allows the installer to configure the maximum heating setpoint. The range is based on the adjustable deadband value Option 11, such that the minimum of the range is 50 F/10 C and the maximum is 90 F/32 C minus the deadband. Default is 88 F/31 C (based on the adjustable deadband default = 2).
“overrides” the programmed fan setting by pressing the fan button, the override selection will remain in effect until the next programmed period time. Default is OF (off). Option 31 — Daylight Savings Time Configuration (programmable models only) This selection allows the installer to set the thermostat to automatically change by one hour on the specified day, month, and week specified. OF (off) — Daylight Savings Time Function disabled.
2 — Thermostat will control the W1 and O/W2/B outputs. Default is 1. Option 33 — Single or Two−Piece Installation This configuration allows the thermostat to compensate for the amount of heat generated by the thermostat electronics to allow more accurate sensing of the temperature sensor. The amount of heat compensation will be different between single installation and two−piece installation. Range: 1P or 2P 1P — The installation is single piece. 2P — The installation is two separate pieces. Default is 2P.
off even if the user has the fan selection set to continuous fan. The fan output will be turned back on in this temperature range if the maximum capacity of auxiliary heat is on due to system demand (auxiliary heat on in response to a defrost signal shouldn’t cause the fan to turn back on). If the outdoor air temperature is below 12 F/−11 C and there is sufficient demand for the equipment to be on, then the fan output is turned back on and the W/W1 output is energized.
SYSTEM START−UP AND CHECKOUT The AC/HP Control is designed with a built−in installer test capability. It allows easy operation of equipment without delays or setpoint adjustments to force heating or cooling. To enable installer test mode, press and hold the fan button for 15 seconds. After 10 seconds, the thermostat will enter Configuration Mode. Continuing to hold the Fan button through 15 seconds will cause the thermostat to enter Installer Test Mode.
TO TEST FAN Fan button switches FAN icon between AUTO and On. While On is displayed, G output will be energized, turning fan on. On some fan coils, fan continues to operate for 90 sec after G signal is removed. Final Settings Be sure to press DONE to exit installer setup mode. If the system is to be left in operation after installation is complete, use MODE button to select between HEAT, COOL, or AUTO to provide desired operation of heating, cooling, or auto.
If fixed temperatures are desired, use SCHEDULE button to turn on arrow icon next to HOLD. This will maintain setpoints, not allowing them to change with programmed schedule. The FAN button may be used to select between AUTO (fan on only with equipment) and On (fan on continuously) fan modes. For further information on temperature selection and programming, refer to Homeowner’s Guide.
Vacation (programmable models only) A vacation selection is available specifically for times where the home will not be occupied for an extended period. Vacation mode has an automatic hold, meaning that setpoints are not affected by the programmed schedule. Vacation mode is active for a specified period of time. While in vacation mode, the system provides temperature protection for the home in the selected mode, but not comfort.
Cycle Timer Based on the selection of 2, 4, or 6 cycles per hour, this timer is set to 30, 15, or 10 minutes. This much time must elapse from the start of one cycle before another cycle can start. It serves to impose the cycles per hour limits. It can be defeated for one cycle by simultaneously pressing the FAN and UP buttons. Ten−Minute Staging Timer In multistage heating or cooling, this timer prevents any higher stage from turning on until preceding stage has been on for 10 minutes.
Detect that defrost is in progress and energize the auxiliary heat to provide homeowner comfort during the defrost cycle Allow a defrost cycle to run to completion regardless of the system demand Three−Minute Minimum on Time In normal operation, when a stage turns on, it will not turn off for a minimum of 3 minutes. If the setpoint is changed, this timer is canceled, allowing the equipment to turn off immediately when the demand is removed.
Emergency Heat Mode When AC/HP Control is configured as a heat pump and emergency heat is selected, all Y signals are locked out, and W becomes energized upon a call for heat. Programmable Fan (programmable models only) The fan output can be programmed based on period of the day. When programming for each day and period the fan can be set to On or AUTO.
Relays This thermostat uses latching relays. When the thermostat loses power, the relays will remain in their last position until power is restored and all relays are reset to their correct position. Out of the box, the outputs may appear to be On when the thermostat is not powered. This is normal. Output states should only be checked when the thermostat is powered.
temperature sensed by the working sensor every 10 seconds. The control will operate from the temperature sensed by the working sensor. E1 − If the Display Module and the Equipment Control Module cannot communicate via two−wire connection, an E1 will be displayed. E2 − There is no E2 error message. E3 − If AC/HP Control cannot properly read outdoor temperature, and it is needed for proper operation, display will indicate “−−” in the outdoor temperature location.
Table 3 – Equipment Configuration Outputs For COOL, HEAT and Emergency Heat modes, the following chart shows the state for each output in each stage of operation EQUIP CONFIG OPTION 01 HARDWARE CONFIG COOL STG 1 COOL STG 2 HEAT STG 1 HEAT STG 2 HEAT STG 3 HEAT STG 4 EM HEAT STG 1 EM HEAT STG 2 SS AC AC Y/Y2 - W/W1 - - - - - - - - - SS AC HP 2S Y/Y2 - W/W1 W/W1 O/W2/B (if Opt32+2) SS HP RVS + O HP Y/Y2, O/W2/B - Y/Y2 Y/Y2, W/W1 - - W/W1 - SS HP RVS + B HP Y/Y2 - Y/
Table 3 − Equipment Configuration Outputs (cont.
WIRING DIAGRAMS Display module Display module wall mount Equipment Control Module V+ Fan Coil Heat Pump V+ O O V+ Vg V+ RVS/Heat Stage 2 Vg O/B W2 W3 W2 Vg Vg Heat Stage 1 W/W1 W2 Compressor Y/Y2 Y Not Used Y1 Y Fan G G 24VAC Hot Heating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 24VAC Common C COM COM Outdoor Air Temp OAT Remote Room Sensor RRS Outdoor Sensor * OAT/RRS Com OAT/RRS Remote Room Sensor * * Indicates connection may not be req
WIRING DIAGRAMS(cont.) Thermostat Fan Coil Heat Pump O RVS/Heat Stage 2 O/B W2 W3 Heat Stage 1 W/W1 W2 Compressor Y/Y2 Y Not Used Y1 O W2** Y Fan G G 24VAC Hot Heating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 24VAC Common C COM COM Outdoor Air Temp OAT Remote Room Sensor RRS Outdoor Sensor * OAT/RRS Com OAT/RRS Remote Room Sensor * * Indicates connection may not be required/available. ** Some heat pumps may designate W1. A09154 Fig.
WIRING DIAGRAMS(cont.) Thermostat Fan Coil O RVS/Heat Stage 2 O/B W2 W3 Heat Stage 1 W/W1 W2 Compressor Y/Y2 Not Used Y1 Fan G G 24VAC Hot Heating Rh R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 24VAC Common C Aux. Connection COM Outdoor Air Temp OAT Remote Room Sensor RRS Outdoor Sensor * OAT/RRS Com OAT/RRS Remote Room Sensor * * Indicates connection may not be required/available. A09155 Fig.
WIRING DIAGRAMS(cont.) Thermostat Fan Coil Air Conditioner O RVS/Heat Stage 2 O/B W2 W3 Heat Stage 1 W/W1 W2 Compressor Y/Y2 Y Not Used Y1 Y Fan G G 24VAC Hot Heating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 24VAC Common C COM COM Outdoor Air Temp OAT Remote Room Sensor RRS Outdoor Sensor * OAT/RRS Com OAT/RRS Remote Room Sensor * * Indicates connection may not be required/available. A09175 Fig.
WIRING DIAGRAMS(cont.) Thermostat Fan Coil O RVS/Heat Stage 2 O/B W2 W3 Heat Stage 1 W/W1 W2 Compressor Y/Y2 Not Used Y1 Fan G G 24VAC Hot Heating Rh R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 24VAC Common C Aux. Connection COM Outdoor Air Temp OAT Remote Room Sensor RRS Outdoor Sensor * OAT/RRS Com OAT/RRS Remote Room Sensor * * Indicates connection may not be required/available. A09156 Fig.
WIRING DIAGRAMS(cont.) Thermostat Furnace * Heat Stage 2 O/B W2 W2* Heat Stage 1 W/W1 W/W1 Compressor Y/Y2 Y/Y2 Not Used Y1 Air Conditioner Y Fan G G 24VAC Hot Heating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 24VAC Common C COM COM Outdoor Air Temp OAT Remote Room Sensor RRS Outdoor Sensor * OAT/RRS Com OAT/RRS Remote Room Sensor * * Indicates connection may not be required/available. A09157 Fig.
WIRING DIAGRAMS(cont.) Thermostat RVS/Heat Stage 2 O/B W2 Heat Stage 1 W/W1 Compressor Y/Y2 Not Used Y1 Fan G G 24VAC Hot Heating Rh R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 24VAC Common C Outdoor Air Temp OAT Remote Room Sensor RRS OAT/RRS Com OAT/RRS C A09158 Fig.
WIRING DIAGRAMS(cont.) Thermostat Furnace Air Conditioner W2 RVS/Heat Stage 2 O/B W2 Heat Stage 1 W/W1 W/W1 Compressor Y/Y2 Y/Y2 Not Used Y1 Y Fan G G 24VAC Hot Heating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 24VAC Common C COM COM Outdoor Air Temp OAT Remote Room Sensor RRS Outdoor Sensor * OAT/RRS Com OAT/RRS Remote Room Sensor * * Indicates connection may not be required/available. A09159 Fig.
WIRING DIAGRAMS(cont.) Single-Stage Furnace Thermostat RVS/Heat Stage 2 O/B W2 Heat Stage 1 W/W1 Compressor Low Y1 Compressor High Y/Y2 Y/Y2 Fan G G 24VAC Hot Heating Rh R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 24VAC Common C Single-Stage Air Conditioner W/W1 Y R* COM Outdoor Air Temp OAT Remote Room Sensor RRS Outdoor Sensor * OAT/RRS Com OAT/RRS Remote Room Sensor * COM * Indicates connection may not be required/available.
THERMOSTAT CONFIGURATION RECORD Installer _________________________ Model Number ______________________________ Date _________________________ A. Hardware Configuration __________ Seal Hole In Wall B. Mode Settings __________ Mode (Off, Heat, Cool, Auto, Em Heat) __________ Heating Setpoint Value __________ Cooling Setpoint Value __________ Fan (Auto or On) C. Home, Away, Sleep Settings Home Away Sleep Heat Cool ____ ____ ____ ____ ____ ____ D.
E Configuration Options Option 01 Option 02 Option 03* Option 04 Option 05 Option 06 Option 07 Option 08 Option 10 Option 11 Option 12 Option 13 Option 15 Option 16 Option 17 Option 18* Option 19 Option 20 _____ _____ _____ _____ _____ _____ _____ _____ _____ _____ _____ _____ _____ _____ _____ _____ _____ _____ Equipment Type Clean Filter Timer Adjustment Fahrenheit/Centigrade Selection Fan (G) on with W/W1 Selection Room Air Temperature Sensing Cooling Lockout Below 55 F Selection (only available if out
E Configuration Options (cont) Option 21* Option 24* Option 25* Option 26 Option 27 Option 28 Option 29 Option 30* Option 31* Option 32 Option 33 Option 41 Option 44 _____ _____ _____ _____ _____ _____ _____ _____ _____ _____ _____ _____ _____ Keypad Lockout Programmable/Non-Programmable (programmable models only) Number of Programmable Periods Per Day (programmable models only) Minimum Cooling Setpoint Maximum Heating Setpoint UV Light Reminder Humidifier Pad Reminder Programmable Fan (programmable model
2009 Bryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 06/09 Catalog No: Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.