T6--PRH, T6--NRH PREFERREDt SERIES THERMIDISTAT Installation Instructions A07045 Programmable Control A07044 Non ---Programmable Control NOTE: Read the entire instruction manual before starting the installation.
TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 INSTALLATION CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 SYSTEM START--UP AND CHECKOUT . . . . . . . . . . . . . . . . . . . . . . . . . .
INTRODUCTION Bryant’s 7--day, 5/2--day, 1--day programmable and non--programmable Preferredt Series Thermidistatt Control is a wall--mounted, low--voltage control which combines temperature and humidity control in either a single unit or a two--piece unit. In two--piece configuration, the relays are located near the equipment and a two--wire connection is used between the Display Module and the Equipment Control Module. Single--piece installation requires more wiring and results in a higher profile.
Rh terminal. Connect R from the outdoor unit to the Rc terminal. Then, break jumper on the circuit board. The W and G signals are taken from the Rh power and the Y and O signals are taken from the Rc power. If thermostat has been installed in a two--transformer application that is later changed to a single--transformer installation, installer must install a field supplied jumper between Rc and Rh. Depending on the installation, up to 14 wires may be required. Installation as two--piece unit is recommended.
Humidify Equipment and Connections The humidify output connects directly to 24VAC operated humidifiers. No other connection or interlock is required. Any of several installer--selectable operating modes are available. ! WARNING ELECTRICAL OPERATION HAZARD Failure to follow this warning could result in personal injury or death. DO NOT connect furnace HUM terminal directly to Thermidistat Control HUM terminal. This will bypass furnace safety controls.
unit and existing control wires may be used for its connection. Details are provided in sensor instructions. Remote Indoor Temperature Sensor A remote temperature sensor may be used where it is desirable to install the thermostat in a limited access location while measuring the temperature in the living space. The remote room sensor may be used as a stand alone or average with local sensor.
INSTALLATION Carton contains the following components (see Fig. 2): A07224 Fig. 2 -- Carton Contents 1. 2. 3. 4. Display Module Stand--off for Equipment Control Module Outside Air Temperature Sensor and Screws (T6--PRH model only) Equipment Control Module Thermidistat Control Location Thermidistat Control should be mounted: S Approximately 5 ft (1.5m) from floor. S Close to or in a frequently used room, preferably on an inside partitioning wall. S On a section of wall without pipes or duct work.
Thermidistat Control should NOT be mounted: S Close to a window, on an outside wall, or next to a door leading to the outside. S Exposed to direct light or heat from a lamp, sun, fireplace, or other temperature--radiating objects which could cause a false reading. S Close to or in direct airflow from supply registers and return--air registers. S In areas with poor air circulation, such as behind a door or in an alcove.
! CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation. Improper wiring or installation may damage Thermidistat Control. Check to make sure wiring is correct before proceeding with installation or turning on power. 1. Turn off all power to equipment. 2. If an existing thermostat is being replaced a. Remove existing thermostat from wall. b. Disconnect wires from existing thermostat, 1 at a time. c.
! CAUTION ENVIRONMENTAL HAZARD Failure to follow this caution may result in environmental damage. Mercury is a hazardous waste. Federal regulations require that Mercury be disposed of properly. Two-- Piece Installation The following steps should be followed for the installation of the two--piece configuration. 1. Remove mounting plate from back of Display Module by pressing the two tabs on the bottom edge and pulling away. See Fig. 3 and 4. A07225 Fig.
A07226 Fig. 4 -- Take Apart 2. Route wires through large hole in mounting base. Level mounting base against wall (for aesthetic value only—Display Module need not be leveled for proper operation) and mark wall through 2 mounting holes. See Fig. 5.
A07165 3. 4. 5. 6. Fig. 5 -- Backplate Mounting Drill two 3/16--in. mounting holes in wall where marked. Thermostat may be mounted to a standard junction box, if desired. Hole pattern on thermostat mounting base matches junction box mounting holes. Secure rear plastic mounting base to wall with 2 screws and anchors provided. Additional mounting holes are available for more secure mounting if needed. Make sure all wires extend through hole in mounting base.
A07170 Fig.
A07166 Fig. 7 -- Secure Wires to Terminal Strip A07167 Fig. 8 -- Connect Pigtail Wires to Display Module 7. Push any excess wire into wall and against mounting base. Seal hole in wall to prevent air leaks. Leaks can affect operation and cause incorrect temperature and/or humidity measurement.
8. Make sure 2--wire pigtail is attached to Display Module mounting base. This should come attached from the factory. Attach two--wire pigtail to the back of the Display Module via 2 pin, keyed connector. 9. Reattach Display Module body to mounting base by first setting on at top of mounting base and then push bottom corners of Display Module to snap into place. See Fig. 9. A07169 Fig. 9 -- Attach Display to Backplate 10.
A07217 Fig. 10 -- Equipment Control Module on Equipment 11. Route wires through rear of Equipment Control Module using either a clearance hole or supplied standoff. See Fig. 11. A07227 Fig.
12. Match and connect equipment wires to proper terminals of each connector block being careful not to over tighten the screws. Correct polarity must be observed when connecting the two wires from the Equipment Control Module to the thermostat mounting base. If wires are connected incorrectly, the Display Module will not operate. See Fig. 6, 7 and 8. 13. Snap cover over top of Equipment Control Module. See Fig. 12. A07218 Fig. 12 -- Cover on Equipment Control Module 14. Turn on power to equipment.
f. h2 g. H h. C — Hybrid Heat system with 2--stage heat pump — heating only system — cooling only system Single-- Piece Installation The following steps should be followed for the installation of the single--piece configuration. 1. Remove cover from Equipment Control Module by pressing the two tabs on the bottom edge and pulling away. Route wires through large hole in Equipment Control Module.
A07219 5. 6. 7. 8. Fig. 13 -- Equipment Control Module Match and connect equipment wires to proper terminals of each connector block. Push any excess wire into wall and against Equipment Control Module. Seal hole in wall to prevent air leaks. Leaks can affect operation and cause incorrect temperature and/or humidity measurement. Remove 2--wire pigtail from thermostat mounting base and attach to Equipment Control Module terminal block (terminals V+ and Vg).
A07221 Fig. 14 -- Reattach Display Module 9. Turn on power to equipment. On power up, all display segments will light for 5 sec. For the next 5 sec a 2--digit code appears on large display which identifies Thermidistat Control configuration. Refer to Option 33. a. AC — 1--stage air conditioner b. HP — 1--stage heat pump c. A2 — 2--stage air conditioner d. H2 — 2--stage heat pump e. hh — Hybrid Heat system with 1--stage heat pump f. h2 — Hybrid Heat system with 2--stage heat pump g.
Set Thermidistat Control Configuration Configuration options enable the installer to configure the thermostat for a particular installation. Most are not presented to the homeowner and therefore must be properly set by the installer. (Only those marked with an asterisk * below are available to the homeowner.) The homeowner configurations are described in the owner’s manual. A special procedure allows entry into the configuration mode. While in configuration mode, up to 33 selections can be made.
Option 11 — Adjustable Setpoint Deadband (not available on heat only and cool only systems) Option 12 — Smart Recovery (programmable models only) Option 13 — Room Temperature Offset Adjustment Option 14 — Humidity Offset Adjustment Option 15 — Enable Auto Mode Option 16 — Cycles Per Hour Option 17 — Time Between Stages Option 18* — Backlight Configuration Option 19 — Dry Contact Option 20 — Outdoor Air Temperature Offset Adjustment Option 21* — Keypad Lockout Option 22 — High Cool Latch Temperature Option 2
Option 31* — Daylight Savings Time Configuration (programmable models only) Option 32 — Furnace Heat Staging Option 33 — Single or Two--Piece Installation Option 99 — Reset to Factory Defaults TO ENTER CONFIGURATION MODE Press and hold FAN button for approximately 10 sec. The Display Module is now in configuration mode. It will automatically exit this mode if no button is pressed for 3 minutes. Pressing the DONE button will exit configuration mode immediately.
H2 HP A2 AC hh h2 H — — — — — — — operates a two--speed heat pump with a fan coil operates a single--speed heat pump with a fan coil operates a two--speed AC operates a single--speed AC operates a single--speed heat pump with a furnace operates a two--speed heat pump with a furnace operates a heat--only system. Furnace or fan coil only; no outdoor unit. C — operates a cool only--system. Outdoor AC unit with an indoor fan coil with no strip heaters. Default is H2.
select OFF. Some auxiliary heaters require separate G signal to turn on blower. In this case, select On. Default is OF (off). Option 05 — Room Air Temperature Sensing (programmable models only) This selection determines which sensor the control will use for measuring room air temperature. Room air temperature can be sensed in one of three ways; the local sensor (L) located on the Display Module, the remote room air sensor (r), or the average of local and remote sensors (Lr). Settings are L, r, Lr.
OF (off) -- function is disabled. Auxiliary heat is allowed to operate whenever sufficient demand for heat is available. 5--55_F -- Outdoor temperature above which the auxiliary heat is not allowed to operate (unless MODE is set to Emergency Heat). Default is OF (off). Option 09 — Heat Pump Lockout Temperature This selection is only available on Hybrid Heat systems. A Hybrid Heat system is selected via the Option 1 Equipment Type configuration.
Option 11 — Deadband Setting Between Heat & Cool This option is not available on Heat Only and Cool Only systems. The selection allows the installer to choose how much differential exists between the heating and cooling setpoints. Allowable selections are 1--6. Default is 2. Option 12 — Smart Recovery Smart Recovery OF (off) means setpoints change precisely at setback recovery time. Thirty, 60, or 90 selects the number of minutes recovery starts before programmed recovery time.
change between heating mode and cooling mode when sufficient demand for heating or cooling exists. On — Auto mode is available. OF — Auto mode is not available. Default is On. Option 16 — Maximum Cycles Per Hour This selection limits the number of cycles per hour that the thermostat allows the system to operate. Selections are 2, 4, 6. 2 — The heating and cooling outputs will be energized no more than 2 times per hour. When an output is energized, it will not be energized again for 30 minutes.
Option 18 — Backlight Configuration When OF (off), the backlight will be lit for 10 seconds after a button is pressed. After 10 seconds of no button presses, the backlight turns off. When On, the backlight will normally be on and dim in appearance. The backlight brightness becomes brighter when a button is pressed. After 10 seconds of no button presses, the backlight will return to the dimmer level until another button press occurs. The range of brightness is 1 through 5 with 5 being full brightness.
terminal on the cooling equipment when the dry contact is closed. See Wiring Diagrams for more information. Default is OF (off). Option 19 — Dry Contact Configuration (non--programmable models only) OF — The dry contact is always de--energized. ON — The dry contact will operate as a DEHUM relay. This relay is reverse logic. When the humidity level is above the dehumidify setpoint, the dry contact D1--D2 will be opened. When the humidity level is below the dehumidify setpoint, D1--D2 will be closed.
3 — The entire keypad is locked. When a button is pressed, the backlight will turn on but none of the operating parameters will be changed. When the keypad lock selection is turned on, the padlock icon will be displayed. To unlock the keypad, press and hold the UP/DOWN buttons simultaneously for five seconds. When the keypad is unlocked, the padlock icon will turn off. The keypad will remain unlocked for two minutes after the last button press.
Option 22 — High Cool Latch Temperature An outdoor sensor is required for high cool latch feature. This selection is only available when Option 1 is set to H2, A2, or h2 and when Option 7 (zoning) is set to OF (off). Configuration settings are OF (off), 80, 85, 90, 95, 100, 105, 110, On. OF (off) — Cooling always starts in low stage (Y1) and stages up to high stage (Y1 and Y/Y2) when demand is sufficient and staging timer constraints have been satisfied.
On — The Y1 and Y/Y2 outputs are simultaneously energized to satisfy all heating demands. Default is OF (off). Option 24 — Programmable/Non--Programmable (programmable models only) This selection allows the installer to configure the thermostat as either programmable or non--programmable. Selections are P, nP. Default is P. Option 25 — Number of Programmable Periods (programmable models only) This selection allows the installer to configure the thermostat for two or four periods per day.
Option 27 — Maximum Heating Setpoint This selection allows the installer to configure the maximum heating setpoint. The range is based on the adjustable deadband value Option 11, such that the minimum of the range is 50_F and the maximum is 90_F minus the deadband. Default is 88_F (based on the adjustable deadband default = 2).
Option 30 — Programmable Fan (programmable models only) This selection allows the homeowner to program the fan selection to “Auto” or “On” fan operation for each of the program schedule periods. This selection is only available on programmable thermostats. OF (off) — Programmable fan is disabled and the homeowner must manually select “Auto” or “On” for fan operation. On — Programmable fan is enabled.
choose the end date for daylight savings time (Fall). To activate the function, the installer changes the “2” by pressing the up button and “On” is displayed. The setting shall be left “On” to enable the Daylight Savings Time function. Default is On (on). Option 32 — Furnace Heat Staging Control (available only when the thermostat is configured to operate AC or A2 equipment). 1 — Thermostat controls W1 output only and furnace controls the turn on and turn off of higher stages of heat.
to move the box from the 99 to the 10 (programmable model) or to flash the 10 (non--programmable model). Then press and hold the DOWN key. The 10 will start counting down toward zero. If the DOWN key is kept pressed until the count reaches zero, the reset will be performed. When the value reaches zero, the heat setpoint shall display ----. The cool setpoint shall display -- and the room air temperature shall display Fd.
installation, only 1 stage of auxiliary heat is available. Any staging of auxiliary heat must be managed by the furnace or fan coil. While the heating test is active, the humidify output can be toggled. On the programmable models, pressing the button below the humidify icon shall toggle the state of the humidify output. On the non--programmable models, pressing the features button shall toggle the state of the humidify output. Installer test for cooling is the same as described for heating above.
On the programmable models, the default setpoints and programmed schedule conform to the Energy Starr requirements of the U.S. Department of Energy for both heating and cooling. These provide energy saving temperature settings. Refer to Table 1.
the set button will cycle through the calendar, daily schedule, and vacation settings. Calendar may be changed by using the soft keys to select the Month, Day, or Year. The UP/DOWN buttons are used to change the Month, Day, or Year setting when the box surrounds it. Day of the week (Mon--Sun) is determined by calendar settings and is not directly adjustable. When changing daily schedule settings, the soft keys are used to set the days, period times, heating setpoints, and cooling setpoints.
Table 2 – Humidification Selections FAN DISPLAY HUMIDIFY SETPOINT DISPLAY Normal Humidify Blank 10 ---46 Auto Humidify AUTO 1 ---9 Humidify Off Blank OF (Off) SELECTION 1. Humidify In normal humidify, humidifier will be on if there is humidity demand and any heating equipment is on. This will include furnace, heat pump, or auxiliary heat. 2. Auto Humidify Thermidistat control will automatically adjust the humidity setpoint according to the outdoor temperature.
To Select Humidification (non--programmable) Press the features button twice. The first press displays the outdoor air temperature and the second press displays the humidity value and humidify target. Pressing the mode button shall cycle through the available humidification selections (Off, Humidify and Auto Humidify). Additional Humidify Comments The humidifier is actually turned on when humidity is 1% below setpoint and turned off when it reaches 1% above setpoint.
1. Normal Dehumidify Operation When normal dehumidify is selected, the compressor will not turn on without a cooling demand. If dehumidify demand exists while cooling, dry contact will also be active (24VAC removed). This output commands variable--speed blowers to reduce their airflow, which improves water removal from the cooled air. 2.
A06599 Fig. 15 -- Auto Humidity 3. Dehumidify Off Dehumidification can be turned off completely. This can be done without changing existing setpoints. To Select Dehumidification (programmable -- between NORMAL, COOL TO, and OFF) Press the soft key below the dehumidify icon button to bring up dehumidify selections. Dehumidify options are only available when in Cooling mode.
system is in AUTO mode, dehumidify options are available if the last system operation was a call for cooling. To Select Dehumidification (non--programmable -- between NORMAL, COOL TO, and OFF) Press the features button three times. The first press displays the outdoor air temperature, the second press displays the humidify options and the third press will display the current dehumidify selections. The mode button is used to cycle through the dehumdify selections.
Bryant FK and FV series variable--speed fan coils, all variable--speed furnaces, and select single and multi--stage furnaces with the dehumidify connection have dehumidify inputs which connect directly to Thermidistat Control dry contact. Refer to the furnace literature for dehumidification options. The FK and FV series fan coils have a terminal marked DH which should be connected to the Thermidistat control dry contact output. Jumper J1 on fan coil MUST be removed. It is located behind the DH terminal.
Vacation Setpoints A special set of temperature and humidity setpoints exist which are active in vacation mode. They are adjustable by the homeowner, are exclusively for vacation mode, and are remembered from one vacation selection to the next. See Table 3 for default values. Table 3 – Vacation Setpoints Default Values MODE Fan Heat Setpoint Cool Setpoint Humidify Setpoint Dehumidify Setpoint AUTO Auto 55 85 20 60 Vacation Humidification Normal humidify is available using vacation setpoints.
OPERATIONAL INFORMATION Timers Five--Minute Compressor Timeguard This timer prevents compressor from starting unless it has been off for at least 5 minutes. It can be overridden for 1 cycle by simultaneously pressing FAN and UP buttons. Cycle Timer Based on the selection of 2, 4, or 6 cycles per hour, this timer is set to 30, 15, or 10 minutes. This much time must elapse from the start of one cycle before another cycle can start. It serves to impose the cycles per hour limits.
signal shall be considered valid if the compressor output is energized and the defrost signal has been active for less than 15 consecutive minutes. Any defrost signal present for longer than 15 minutes shall be considered invalid.
Humidify and Dehumidify Indicators When the Display Module door is closed, the humidify icon will be displayed when humidification is active and the dehumidify icon will be displayed when dehumidification is active. Auto Changeover When auto changeover mode is selected, a change from heat to cool (or vice versa) will not occur until an opposite mode demand has existed for 20 minutes. If setpoint is changed, 20--minute requirement is deleted.
connected to one of the dry contact terminals. The other dry contact terminal is connected to the dehumidify terminal on the furnace or fan coil. This provides power to energize the dehumidify terminal on the cooling equipment when the dry contact is closed. If it is desired to operate a ventilator or other device, the D1 and D2 terminals can be connected directly to the equipment. This will provide a closed contact for the specified number of minutes per hour. See Option 19.
TROUBLESHOOTING Error Codes “----” -- If Thermidistat Control cannot properly read room temperature, display will indicate “----” and all outputs (except fan, if on) will turn off. In the case where the installer has selected to average the local sensor and the remote room sensor, the Thermidistat display will alternate between “----” for the failed sensor and the temperature sensed by the working sensor every 10 seconds. The control will operate from the temperature sensed by the working sensor.
Table 4 – Equipment Configuration Outputs HEAT STAGE 2 HEAT STAGE 3 EM HEAT STAGE 1 W/W1 - - - W/W1 W/W1 O/W2/B - - Y/Y2 Y/Y2 W/W1 - W/W1 - W/W1 EQUIPMENT CONFIGURATION OPTION #1 FACTORY CONFIGURATION COOL STAGE 1 COOL STAGE 2 HEAT STAGE 1 Single-- stage AC AC Y/Y2 - Single-- stage AC HP 2S Y/Y2 - Single-- stage HP RVS = C HP Y/Y2 O/W2/B - Single-- stage HP RVS = H HP Y/Y2 - Y/Y2 O/W2/B Y/Y2 W/W1 O/W2/B Single-- stage HP RVS = C 2S Y/Y2 O/W2/B - Y/Y2 Y/Y2 W/W1 -
Table 4 -- Equipment Configuration Outputs (cont) EQUIPMENT CONFIGURATION OPTION #1 FACTORY CONFIGURATION COOL STAGE 1 COOL STAGE 2 HEAT STAGE 1 HEAT STAGE 2 HEAT STAGE 3 EM HEAT STAGE 1 Two-- stage Hybrid Heat RVS = C 2S Y1 O/W2/B Y1 Y/Y2 O/W2/B Y1 Y1 Y/Y2 W/W1 W/W1 Two-- stage Hybrid Heat RVS = H 2S Y1 Y1 Y/Y2 Y1 O/W2/B Y1 Y/Y2 O/W2/B W/W1 W/W1 Heat Only Unit AC HP 2S - - W/W1 - - - Cool Only Unit 2S Y1 Y1 Y/Y2 - - - - Cool Only Unit AC HP Y/Y2 - - - - - 54
WIRING DIAGRAMS Display module Display module wall mount Equipment Control Module V+ Fan Coil Heat Pump V+ O O V+ Vg V+ RVS/Heat Stage 2 Vg O/B W2 W3 W2 Vg Vg Heat Stage 1 W/W1 W2 Compressor Y/Y2 Not Used Y1 Fan G G 24VAC Hot Heating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 24VAC Common C COM COM Outdoor Air Temp Y Y OAT Remote Room Sensor RRS Outdoor Sensor * OAT/RRS Com OAT/RRS Remote Room Sensor * A07164 Fig.
Thermostat Fan Coil Heat Pump O O RVS/Heat Stage 2 O/B W2 W3 W2 W2 Heat Stage 1 W/W1 Compressor Low Y1 Y1 Y1 Compressor High Y/Y2 Y/Y2 Y/Y2 Fan G G 24VAC Hot Heating Rh R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 DEHUM 24VAC Common C COM Humidify HUM Outdoor Air Temp OAT Humidifier Solenoid Valve * Remote Room Sensor RRS Outdoor Sensor * OAT/RRS Com OAT/RRS Remote Room Sensor * R COM A06573 Fig.
Thermostat Typical Fan Coil Single-Stage Heat Pump W2 O RVS/Heat Stage 2 O/B W2 W3 W2 Heat Stage 1 W/W1 Compressor Low Y1 Compressor High Y/Y2 Fan G G 24VAC Hot Heating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 COM COM Y 24VAC Common C Humidify HUM Outdoor Air Temp OAT Humidifier Solenoid Valve * Remote Room Sensor RRS Outdoor Sensor * OAT/RRS Com OAT/RRS Remote Room Sensor * A06574 Fig.
Thermostat RVS/Heat Stage 2 O/B W2 W3 Heat Stage 1 W/W1 W2 Compressor Low Y1 Compressor High Y/Y2 Fan G G 24VAC Hot Heating Rh R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 24VAC Common C Humidify HUM Outdoor Air Temp OAT Humidifier Solenoid Valve * Remote Room Sensor RRS Outdoor Sensor * OAT/RRS Com OAT/RRS Remote Room Sensor * Aux. Connection COM A06575 Fig. 19 -- Fan Coil Shown w/Aux. Connection #1 (Heat Pump/Air Conditioner removed for clarity.
Thermostat Fan Coil Air Conditioner O RVS/Heat Stage 2 O/B W2 W3 W2 Heat Stage 1 W/W1 Compressor Low Y1 Y1 Y1 Compressor High Y/Y2 Y/Y2 Y/Y2 Fan G G 24VAC Hot Heating Rh R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 24VAC Common C Humidify HUM R DEHUM COM Outdoor Air Temp OAT Humidifier Solenoid Valve * Remote Room Sensor RRS Outdoor Sensor * OAT/RRS Com OAT/RRS Remote Room Sensor * COM A06576 Fig.
Typical Fan Coil Thermostat Single-Stage Air Conditioner O RVS/Heat Stage 2 O/B W2 W3 W2 Heat Stage 1 W/W1 Compressor Low Y1 Compressor High Y/Y2 Fan G G 24VAC Hot Heating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 COM COM Y 24VAC Common C Humidify HUM Outdoor Air Temp OAT Humidifier Solenoid Valve * Remote Room Sensor RRS Outdoor Sensor * OAT/RRS Com OAT/RRS Remote Room Sensor * * A06577 Fig.
Fan Coil Thermostat RVS/Heat Stage 2 O/B W2 W3 Heat Stage 1 W/W1 W2 Compressor Low Y1 Compressor High Y/Y2 Fan G G 24VAC Hot Heating Rh R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 24VAC Common C Humidify HUM Outdoor Air Temp OAT Humidifier Solenoid Valve * Remote Room Sensor RRS Outdoor Sensor * OAT/RRS Com OAT/RRS Remote Room Sensor * Aux. Connection COM A06578 Fig. 22 -- Fan Coil Shown w/Aux. Connection #2 (Heat Pump/Air Conditioner removed for clarity.
Thermostat Fan Coil Heat Pump O O RVS/Heat Stage 2 O/B W2 W3 W2 W2 Heat Stage 1 W/W1 Compressor Low Y1 Y1 Compressor High Y/Y2 Y/Y2 Fan G G 24VAC Hot Heating Rh R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 DEHUM 24VAC Common C COM Humidify HUM Outdoor Air Temp OAT Humidifier Solenoid Valve * Remote Room Sensor RRS Outdoor Sensor * OAT/RRS Com OAT/RRS Remote Room Sensor * Y R COM A06579 Fig.
Typical Fan Coil Thermostat RVS/Heat Stage 2 O/B W2 W3 Heat Stage 1 W/W1 W2 Compressor Low Y1 Compressor High Y/Y2 Fan G G 24VAC Hot Heating Rh R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 24VAC Common C Humidify HUM COM Outdoor Air Temp OAT Humidifier Solenoid Valve * Remote Room Sensor RRS Outdoor Sensor * OAT/RRS Com OAT/RRS Remote Room Sensor * A06580 Fig. 24 -- Typical Fan Coil Heating Only * Indicates connection may not be required/available.
Thermostat RVS/Heat Stage 2 O/B W2 Heat Stage 1 W/W1 Compressor Low Y1 Compressor High Y/Y2 Fan G G 24VAC Hot Heating Rh R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 24VAC Common C Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT/RRS Com OAT/RRS C A06581 Fig. 25 -- Thermostat w/Dry Contact Control for Fan Run Time * Indicates connection may not be required/available.
Thermostat Fan Coil Air Conditioner O RVS/Heat Stage 2 O/B W2 W3 W2 Heat Stage 1 W/W1 Compressor Low Y1 Y1 Compressor High Y/Y2 Y/Y2 Fan G G 24VAC Hot Heating Rh R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 DEHUM 24VAC Common C COM Humidify HUM Outdoor Air Temp OAT Humidifier Solenoid Valve * Remote Room Sensor RRS Outdoor Sensor * OAT/RRS Com OAT/RRS Remote Room Sensor * Y R * COM A06582 Fig.
Typical Fan Coil Thermostat RVS/Heat Stage 2 O/B W2 Heat Stage 1 W/W1 Single-Stage Air Conditioner Compressor Low Y1 Compressor High Y/Y2 Fan G G 24VAC Hot Heating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 COM COM 24VAC Common C Humidify HUM Y Outdoor Air Temp OAT Humidifier Solenoid Valve * Remote Room Sensor RRS Outdoor Sensor * OAT/RRS Com OAT/RRS Remote Room Sensor * * A06583 Fig.
Thermostat Furnace Heat Pump O RVS/Heat Stage 2 O/B W2 W2 Heat Stage 1 W/W1 W/W1 W2 Compressor Low Y1 Y1 Y1 Compressor High Y/Y2 Y/Y2 Y/Y2 Fan G G 24VAC Hot Heating Rh R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 DEHUM 24VAC Common C COM Humidify HUM Outdoor Air Temp OAT Humidifier Solenoid Valve * Remote Room Sensor RRS Outdoor Sensor * OAT/RRS Com OAT/RRS Remote Room Sensor * * R COM A06584 Fig.
Single-Stage Furnace Thermostat Single-Stage Heat Pump O RVS/Heat Stage 2 O/B W2 Heat Stage 1 W/W1 Compressor Low Y1 W W2 Compressor High Fan Y/Y2 Y Y G G 24VAC Hot Heating Rh R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 DEHUM 24VAC Common C COM Humidify HUM Outdoor Air Temp OAT Humidifier Solenoid Valve * Remote Room Sensor RRS Outdoor Sensor * OAT/RRS Com OAT/RRS Remote Room Sensor * * R COM A006585 Fig.
Thermostat Furnace RVS/Heat Stage 2 O/B W2 W2 Heat Stage 1 W/W1 W1 Air Conditioner Compressor Low Y1 Y1 Y1 Compressor High Y/Y2 Y/Y2 Y/Y2 Fan G G 24VAC Hot Heating Rh R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 24VAC Common C Humidify HUM R DEHUM COM Outdoor Air Temp OAT Humidifier Solenoid Valve * Remote Room Sensor RRS Outdoor Sensor * OAT/RRS Com OAT/RRS Remote Room Sensor * COM A06586 Fig.
Single-Stage Furnace Thermostat RVS/Heat Stage 2 O/B W2 Heat Stage 1 W/W1 Compressor Low Y1 Compressor High Y/Y2 Y Fan G G 24VAC Hot Heating Rh R 24VAC Hot Cooling Rc Single-Stage Air Conditioner W Dry Contact 1 D1 Dry Contact 2 D2 DEHUM 24VAC Common C COM Humidify HUM Outdoor Air Temp OAT Humidifier Solenoid Valve * Remote Room Sensor RRS Outdoor Sensor * OAT/RRS Com OAT/RRS Remote Room Sensor * Y R * COM A06587 Fig.
Thermostat Furnace Heat Pump O RVS/Heat Stage 2 O/B W2 W2 Heat Stage 1 W/W1 W1 Compressor Low Y1 Y1 Compressor High Y/Y2 Y/Y2 Fan G G 24VAC Hot Heating Rh R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 DEHUM 24VAC Common C COM Humidify HUM Outdoor Air Temp OAT Humidifier Solenoid Valve * Remote Room Sensor RRS Outdoor Sensor * OAT/RRS Com OAT/RRS Remote Room Sensor * W2 * Y R COM A06588 Fig.
Single-Stage Furnace Thermostat RVS/Heat Stage 2 O/B W2 Heat Stage 1 W/W1 Compressor Low Y1 Compressor High Y/Y2 W Fan G G 24VAC Hot Heating Rh R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 DEHUM 24VAC Common C COM Humidify HUM Outdoor Air Temp OAT Humidifier Solenoid Valve * Remote Room Sensor RRS Outdoor Sensor * OAT/RRS Com OAT/RRS Remote Room Sensor * A06589 Fig.
Variable Speed/Multi-Stage Furnace Thermostat RVS/Heat Stage 2 O/B W2 W2 Heat Stage 1 W/W1 W1 Compressor Low Y1 Y1 Compressor High Y/Y2 Y/Y2 Fan G G 24VAC Hot Heating Rh R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 24VAC Common C Humidify HUM Air Conditioner Y R * DEHUM COM Outdoor Air Temp OAT Humidifier Solenoid Valve * Remote Room Sensor RRS Outdoor Sensor * OAT/RRS Com OAT/RRS Remote Room Sensor * COM A06590 Fig.
THERMIDISTAT CONFIGURATION RECORD Installer _________________________ Model Number ______________________________ Date _________________________ A. Hardware Configuration __________ Seal Hole In Wall B. Mode Settings __________ Mode (Off, Heat, Cool, Auto, Em Heat) __________ Heating Setpoint Value __________ Cooling Setpoint Value __________ Fan (Auto or On) C. Home, Away, Sleep Settings Home Away Sleep Heat Cool ____ ____ ____ ____ ____ ____ D.
E.
E.