User Guide
10 
| 
Panel Radiator 
Applications Manual
Panel Radiator Applications Manual | 07.2017
Technical specifi cations are subject to change without prior notice
Panel radiator accessories Table 4                                                
Floor Brackets Part Number 
Optional covers for brackets 81606400
Escutions HRDA50
Flow Setter Valve:
Each radiator is equipped with a fl ow setter valve 
mounted on the same side as the water connections of 
the panel radiator. This valve consists of two part integral 
components for temperature control and fl ow balancing.
Flow Balancing:
Flow balancing is done by adjustment of the ring marked 
1-7 and N on the fl ow setter valve, lining the desired 
setting up with the dimple in the fi rst ring. Turning of the 
ring adjusts the diameter available for water fl ow. The N 
marking indicates a fully open setting; the 1 marking 
indicates nearly full restriction. The diagram on page 13 
shows the pressure drop across the radiator as a function 
of the fl ow rate and setting of the fl ow setter.
Fig. 3  Flow setter valve adjustment
Air Vent and Drain Plug
Each radiator is equipped with a manual air vent (1/2") 
and removable drain plug (1/2") for draining the radiator. 
A fl at head screw driver is needed to open the air vent.