User Guide

12
|
Panel Radiator
Applications Manual
Panel Radiator Applications Manual | 07.2017
Technical speci cations are subject to change without prior notice
Thermostatic Sensor head:
Adding a thermostatic sensor head enables room-by-
room zone control for optimum comfort and ef ciency. It
is easily installed on the ow setter valve.
Temperature Control:
Thermostatic control head is mounted on the ow setter
valve of panel radiators and through its capillary
expansion controls the ow rate and therefore the heat
output of the panel. When using the thermostatic head
the ow setter valve needs to be in the N position. A
moveable, spring-loaded seat assembly inside the ow
setter valve regulates the water ow through thermostatic
action of the control head. This thermostatic head is
required for individual temperature control at each
radiator. The asterics provides frost protection of the
panel itself provided the heating system is operational.
The sensor indicator numbers correspond to the following
approximate temperatures:
Thermostatic Sensor Head Setting Table 5
Dial * 1 2 3 4 5
Room Temperature °F 46 54 61 68 75 82
Room Temperature °C 8 12 16 20 24 28
Fig. 6 Thermostatic Sensor Head