User Guide
Applications manual
  | 21 
Panel Radiator 
Applications Manual
Panel Radiator Applications Manual | 07.2017 Technical specifi cations are subject to change without prior notice                         
Example: One-Pipe System Layout
Design a one-pipe system for a second fl oor with 
individual room temperature control:
 Table 12
Description Heat Load Window 
Size
Hook-up 
Sequence
Bathroom 3,000 1x3 ft wide fi rst
Master Bedroom 9,000 2x4 ft wide second
Bedroom 2 6,000 1x3 ft wide third
Bedroom 3 4,000 1x3 ft wide fourth
Solution:
Step 1. Complete the Radiator Sizing Sheet to fi nd 
minimum size radiator.
Step 2. Select control strategy and size piping and pump 
using Table 7.
Step 3-4: See Table 13.
Step 5: Assume temperature drop (∆T) = 30°F (17°C), 
maximum supply temperature = 180°F (82°C).
Step 6: Add all heat loads from row 2 and enter in Step 6.
Step 7: Compute fl ow rate in the one-pipe system in 
GPM.
 The flow rate can not exceed 2 GPM when using
diverter valves. Using a larger ∆T lowers the GPM.
Step 8: Here we must compute the supply temperature 
for each room. Start with the fi rst room and 
compute each supply temperature step by step 
as shown here.
Supply Temp (1) = 180°F (82°C)
Supply Temp (2) = 180 - 3000 / (500 x 1.47) = 176°F 
(80°C)
Supply Temp (3) = 176 - 9000 / (500 x 1.47) = 164°F 
(70°C)
Supply Temp (4) = 164 - 6000 / (500 x 1.47) = 156°F 
(60°C)
Step 9: Now with each value computed in steps 4 and 8, 
locate those values in Fig. 10. The output curve 
located directly above that point identifi es the 
minimum size radiator required. Use the 18°F 
(10°C) ∆T curves if designing for a 20 to 30°F (11 
to 17°C) temperature drop, use the 36°F (20°C) 
∆T curves if designing for a 40°F (22°C) drop. 
Results: Output/ft Radiator Models
Bedroom Supply Temp = 180°F (82°C) 1500 Btu/ft 
#22 20” 
M. Bedroom Supply Temp = 176°F (80°C) 1125 Btu/ft 
#22 x 12
Bedroom #2 Supply Temp = 164°F (70°C) 2000 Btu/ft #22 
24” 
Bedroom #3 Supply Temp = 156°F (60°C) 1333 Btu/ft #22 
24” 
Use 5/8 ” PEX and diverter valves (or: 3/4” copper main 
line with 3/4” x 3/4” x 1/2” monofl ow tees) with 
thermostatic heads on all radiators for individual room 
control. Place a thermostat in the bathroom or master 
bedroom or run constant circulation. Use a Grundfos 
UP15-42, a Taco 007, or equivalent pump with a 
balancing valve to throttle the fl ow. Noise may otherwise 
develop in the diverter valves.
 Table 13
1 Select 
room 
sequence
Bathroom Master 
Bedroom
Bedroom 
2
Bedroom 
3
2 Heat load 
per room
3000 9000 6000 4000
3 Available 
wall space
(ft)
283 3
4 Minimum 
required 
heat 
load per 
linear foot 
(BTU/ft)
1500 1125 2000 1333
5 Minimum 
Required 
Heat Load 
per linear 
ft (BTU/ft)
ΔT = 30ºF 
Supply temperature (room1) 
=max supply temperature 
= 180 ºF
6 Total 
heat load 
(BTU/ft)
Q = 3000 + 9000 + 6000 + 4000 = 22000 BTU/Hr
7 Total loop 
GPM GPM = Q / 500 / ΔT = 22000 / 500 / 30 = 1.5 GPM
8 Supply 
temp per 
room
ΔT = Q / 500 / GPM
180 176 164 156
9 Possible 
radiator 
Models 
and sizes










