Design Procedure for Two-Pipe System
1. Determine individual heat loads.
2. Select desired overall temperature drop of systems 
(∆T); i.e. 20°F (11°C), 30°F (17°C) or 40°F (22°C).
3. Compute loop fl ow rate GPM from: 
GPM = Q / 500 / ∆T
4. Use Figure 10 or the Conversion Factors in Table 9 to 
determine output of radiator models in case of lower 
supply temperatures.
5. Use the Pressure Drop Chart on pages 30-31 as a 
guide to set the fl ow setter valve for each radiator to 
ensure proper fl ow through each radiator. Adjust fl ow 
setter valves as needed based on system 
performance. Close down the fl ow setter on “hot” 
radiators by dialing in a lower setting on the adjustment 
ring, or adjust the fl ow setter to a higher setting for 
“cool” radiators.
6. Size piping based on system fl ow rate; size circulator 
based on fl ow rate and overall system pressure drop.
 Table 14
1 Select 
room 
sequence
Room 1 Room 2 Room 3 Room 4
2 Heat load 
per room
3 (BTU/hr)
4 Available 
wall space
(ft)
5 Minimum 
Required 
Heat Load 
per linear 
ft (BTU/ft)
ΔT =___ºF Supply temp(room1) =max supply 
temp= _______ ºF
6 Total 
heat load 
(BTU/ft)
Q = __________BTU/Hr
7 Total loop 
GPM GPM(loop) = Q / (500xΔT) = ______ GPM
8 Supply 
temp per 
room
____ºF ____ºF ____ºF ____ºF
9 List 
possible 
radiator 
Models 
and sizes