Installation Manual

Table Of Contents
5
Installing the boiler
Logano G115 WS US/CA – 6 720 813 418 (2019/09)18
Minimum clearances to combustible material
Minimum size of chimney
The minimum recommended chimney size is 8" x 8"
(6 ¾ " x 6 ¾ " inside liner) or 6" diameter with a minimum height of 15
feet. Use a 5" flue pipe for connection to an existing chimney.
Installing the flue pipe
Insert flue pipe 5" onto the breach and secure with
3 screws.
Install flue connections between boiler and chimney to slope up at
least ¼ " per foot to the chimney.
Connect the flue pipe to the chimney above the bottom of the
chimney to prevent blockages.
Install cleaning and service hatches.
After starting the burner, set breeching draft to -0.01 to
-0.02 inches WC using a draft gauge. The overfire pressure can be
positive. If necessary, install a barometric damper in the flue system to
maintain the underpressure in the system or to meet code requirements.
Always install the draft controller in vertical position. Use a draft gauge
when making adjustments.
Fig. 12 Installing the flue pipe
[1] Flue pipe
[2] Boiler flue socket
Flue pipe Type Minimum clearance
Double-wall L 6"
Single-wall L 18"
Table 11 Minimum clearances to combustible objects for flue systems
DANGER: Risk of death from escaping flue gases.
If the resistance to flue gas flow is too great and/or the
flue pipe diameter is smaller than the recommended size
and/or the flue pipe is too short:
Seal all vent pipe joints.
Install a CO alarm. Positive pressure combustion
ensures that the flue gas can exit the flue system.
Avoid long horizontal flue pipe runs and keep the number
of elbows to a minimum.