Commissioning the heating system
Logano G115 WS US/CA – 6 720 813 418 (2019/09)32
6.8 Manual reset high limit (STB)
The manual reset high limit interrupts the power supply if the maximum
permissible flow temperature is exceeded.
To enable a boiler reset and re-starting, the fault must be removed and
the system temperature must have fallen below the limit.
Check the function of the manual reset high limit
( controls maintenance instructions).
6.9 Installing the burner door jacket
Position the burner door panel on the hooks on the boiler casing.
Secure the burner door panel with the two screws at the sides.
The Logano G115 WS must be fitted with a burner that has an
operating range that matches the specifications of the Logano G115
WS.
Mount the selected burner to the hole circle in the burner door.
Connect burner cable to burner. ( Installation instructions of
burner).
Fig. 34 Installing the burner door jacket
DANGER: Risk of fatal injury from electric shock.
Only operate the boiler with the burner hood/door
panel fitted.
CAUTION: Risk of system damage from use of incorrect
fuel.
Only use burners which meet the technical
requirements of the Logano G115 WS ( Chapter
2.7, page 8).