Install Instructions

2
Product description
Logano G115 WS US/CA – 6 720 813 418 (2014/10) 11
2.8.5 Conditions power supply
2.8.6 Conditions for hydraulic system and water quality
Operating conditions Notes – Requirement in greater detail
Power supply voltage 120 V
AC nominal
Observe the voltage range of the burner and controls used. The outer casing/boiler must be
grounded for safety reasons and in order to function correctly.
Circuit breaker 10 A
Frequency 60 Hz
Enclosure rating IP 40 (protected against contact by entry of foreign objects > 0.04 inches Ø
(> 1 mm Ø ), no water proofing)
Table 8 Power supply
Operating conditions Notes – Requirement in greater detail
Operating pressure (above
atmospheric)
15 58 psi Maximum 30 psi with the supplied safety valve.
Permissible site test pressure 45 75 psi
Safety temperature limitation by
TR temperature control
122 194 °F
Safety temperature limitation by
manual reset high limit (STB)
210 °F In combination with Beckett AquaSmart or Hydrolevel HydroStat the limit value (210°F)
may not be exceeded.
Water quality The heating system may only be filled and topped up with water of domestic water quality.
We recommend a pH value of 8.2 – 9.5.
Table 9 System configuration and water quality